7 Configuration
Installation manual
41
RWEQ96~432TAYD
∗
+ RWEQ96~432TATJ
∗
VRV W T-Series water-cooled system air conditioner
Heat pump lockout
[2-16]
Heat pump lockout 1.
Heat pump is always locked out when this setting is ON. If the indoor fan control needs to be changed or the auto-backup function is required,
refer to the setting [2-37].
[2-16]
Heat pump lockout 1
0 (default)
OFF
1
ON
[2-37]
Heat pump lockout 2.
Heat pump is locked out when this setting and an external input to ABC terminal are made.
[2-37]
Heat pump lockout 2
0 (default)
OFF
1
Mode 1
2
Mode 2
Mode
Description
Actions
Field setting
Shorted
between
Heating Thermo-on
Heating Thermo-off
Heater
Fan
Heater
Fan
Mode 1
Lockout is controlled by an
external input to ABC
terminal
2-37: Mode 1
A-C
ON
ON (H/L)
OFF
LL (*2)
B-C
OFF
Mode 2
(*1)
2-37: Mode 2
A-C
LL
LL (*2)
B-C
LL
OFF
*1. For a heater which does not need airflow
*2. Depends on the indoor unit field setting 12(22)-3.
[2-74]
Heat rejection cancellation setting temperature.
If the unit internal temperature is higher than the zero energy
dissipation setting temperature, the zero energy dissipation control
will start and cool down the unit.
[2-74]
Description
0
77°F (25°C)
1
80.6°F (27°C)
2
84.2°F (29°C)
3 (default)
87.8°F (31°C)
4
91.4°F (33°C)
5
95°F (35°C)
6
98.6°F (37°C)
7
102.2°F (39°C)
[2-81]
Cooling comfort setting.
This setting is used in conjunction with setting [2-8].
[2-81]
Cooling comfort setting
0
Eco
1 (default)
Mild
2
Quick
3
Powerful
[2-82]
Heating comfort setting.
This setting is used in conjunction with setting [2-9].
[2-82]
Heating comfort setting
0
Eco
1 (default)
Mild
2
Quick
3
Powerful
[2-92]
Te target temperature upper limit.
Default value=1.
[2-92]
Te target temperature upper limit
0
L
1
M
2
H
If Auto Te, then use this setting to address different load profiles. If
the frequent operation is at lower system load, then use a higher
setting under [2-92].
Note: In high humid areas, it is recommended to keep this setting to
0 or 1.
Refer to supplemental documents for Heat pump lockout setting.