3 Identification and system layout
Installation manual
6
RWEQ96~432TAYD
∗
+ RWEQ96~432TATJ
∗
VRV W T-Series water-cooled system air conditioner
Unit: inch (mm)
Accessory pipes
MBH
Øa
Øb
High pressure/Low
pressure gas pipe
▪ Top connection
Øa
Øb
96
1
(25.4)
3/4
(19.1)
120
7/8
(22.2)
144
2 .4
Method for removing shipping
plate
NOTE
If the unit is operated with the transportation stay attached,
abnormal vibration or noise may be generated.
The compressor transportation stay must be removed. It is installed
under the compressor leg in order to protect the unit during
transport. Proceed as shown in the figure and procedure below.
1
Remove the bolt.
2
Lift the insulation to access the compressor mounting bolt.
3
Slightly loosen the mounting bolt.
4
Remove the transportation stay as shown in the figure below.
5
Tighten the mounting bolt to 9.1 ft·lbf (12.3 N·m) of torque.
2
2
3
5
1
(9.1 ft·lbf
(12.3 N·m))
3
Identification and system
layout
3 .1
Standard operation limit
The figures below assume following operating conditions for indoor
and outside units:
Equivalent pipe length ......................................... 25 ft (7.6 m)
Level difference..................................................................... 0
Cooling Heating
50 (10)
60 (15.6)
70 (21.1)
80 (26.7)
90 (32.2)
100 (37.8)
110 (43.3)
120 (48.9)
60
(15.6)
50
(10)
70
(21.1)
80
(26.7)
90
(32.2)
A
A
C
B
50 (10)
60 (15.6)
70 (21.1)
80 (26.7)
90 (32.2)
100 (37.8)
110 (43.3)
120 (48.9)
60
(15.6)
50
(10)
70
(21.1)
80
(26.7)
90
(32.2)
<In case of antifreeze usage>
Cooling Heating
20 (–6.7)
60 (15.6)
70 (21.1)
80 (26.7)
90 (32.2)
100 (37.8)
110 (43.3)
120 (48.9)
10 (–12.2)
60 (15.6)
70 (21.1)
80 (26.7)
90 (32.2)
100 (37.8)
110 (43.3)
50 (10)
50 (10)
40 (4.4)
40 (4.4)
30 (–1.1)
30 (–1.1)
20 (–6.7)
A
A
C
B
60
(15.6)
50
(10)
70
(21.1)
80
(26.7)
90
(32.2)
60
(15.6)
50
(10)
70
(21.1)
80
(26.7)
90
(32.2)
A
Entering water temperature °F (°C)
B
Indoor temperature °FWB (°CWB)
C
Indoor temperature °FDB (°CDB)
Range for continuous operation
Range for operation
Range for pull down operation
Range for warming up operation
▪
Operation range of water flow rate is
13 .2-39 .6 gpm (50-150 L/min)
.
(21.2-39.6 gpm (80-150 L/min) in case of antifreeze usage.)
▪
The unit is designed for the following operation range;
Entering water temperature: 67-95°F (20-35°C)
Relative humidity below 80%
Water flow rate: 15 .9 gpm (60 L/min) or more
▪ During cooling operation when the outside temperature is very
low, it is possible that the thermostat switches off automatically in
order to protect the unit from freezing.
▪ Hold ambient temperature at 35-104°FDB (2-40°CDB).
Heat release from the unit (approx.): RWEQ96: 2730 Btu/h (0.8 kW),
RWEQ120: 3412 Btu/h (1.0 kW), RWEQ144: 4436 Btu/h (1.3 kW)
There is no heat release from the unit if the heat rejection
cancellation is activated.
It is recommended to always ventilate the room if this function is not
activated.