![background image](http://html1.mh-extra.com/html/daikin/rweq96tayd-series/rweq96tayd-series_installation-manual_4699714007.webp)
3 Identification and system layout
Installation manual
7
RWEQ96~432TAYD
∗
+ RWEQ96~432TATJ
∗
VRV W T-Series water-cooled system air conditioner
3 .2
Identification label: Outside unit
Location
Model identification
Example:
RW E Q 96 T A YD
∗
Code
Explanation
RW
Water-cooled
E
Heat pump system
Q
Refrigerant R410A
96
Capacity class
T
Model series
A
Minor model change
YD, TJ
Power supply
YD: 460 V
TJ: 208/230 V
∗
Minor revision
3 .3
About the outside unit
This installation manual concerns the VRV W water-cooled system
air conditioner. The unit is full inverter driven, and can be used for
cooling, heat pump and heat recovery applications.
Model line up:
Model
Description
RWEQ96~432
Heat pump and Heat recovery model for
single or multi-use
Depending on the chosen type of unit, some functionality will or will
not exist. It will be indicated throughout this installation manual and
brought to your attention. Certain features have exclusive model
rights.
These units are intended for indoor installation and aimed for heat
pump applications including water to air.
The normal operating water inlet temperature must be between 50°F
(10°C) and 113°F (45°C). Use of antifreeze/brine will allow extension
of operating ranges to 14°F (–10°C) in heating and 23°F (–5°C) in
cooling.
3 .4
System layout
INFORMATION
Not all combinations of indoor units are allowed.
Heat recovery system
1
i
e
c
g
e
c
h
e
e
b
a
h
g
g
g
d
2
3
e
f
c
a
Unit
b
Refrigerant piping
c
Branch selector unit
d
Multi branch selector unit
e
VRV indoor unit
f
Cooling only VRV indoor unit
g
User interface (dedicated depending on indoor unit type)
h
User interface (wireless, dedicated depending on indoor
unit type)
i
Water system connection
Heat pump system
d
d
d
d
e
c
c
c
c
f
g
b
a
a
Unit
b
Refrigerant piping
c
VRV indoor unit
d
User interface (dedicated depending on indoor unit type)
e
User interface (wireless, dedicated depending on indoor
unit type)
f
Cool/heat selector
g
Water system connection
01_EN_4P602454-1C.indd 7
2020/07/29 16:16:38