SiBE341001
Troubleshooting by Remote Controller
Troubleshooting
170
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Confirmation of malfunction 3 Confirmation of malfunction 4
Diagnosis Flow 6
Correct the manual address
settings.
(For detail, refer to information in
the "AIRNET Installation Manual".)
Are manual address settings (of the
slave units 1, 2 and 3) correct in order
to connect the AIRNET?
NO
Confirmation of malfunction 4
Diagnosis Flow 7
Correct the connecting wires of
the outdoor multi and then reset
the power supply.
In the connection status of
the outdoor multi, check if
more than 5 outdoor units
are connected.
NO
Confirmation of malfunction 3 Confirmation of malfunction 4
Diagnosis Flow 8
Correct the connecting wires of the
outdoor multi and then reset the
power supply.
Check the connection status of the
connecting wires of outdoor multi. to
SLAVE 3 Check if the wiring has any
connection error or broken, or is about
to be disconnected.
NO
YES
YES
YES
YES
NO
Check the connection status of one of
the connecting wires of outdoor multi.
Check if the wiring is broken or
disconnected.
Correct the connecting wires of the
outdoor multi and then reset the
power supply.
Replace the main PCB (A1P) of the
outdoor unit.
Confirmation of malfunction 3
Replace the main PCB (A1P) of
the outdoor unit.
Replace the outdoor unit main PCB
of the SLAVE 3.
Summary of Contents for RQYQ140-180PY1
Page 216: ...Piping Diagrams SiBE341001 207 Appendix 1 2 BS Unit BSVQ100 160 250PV1 4D057985B...
Page 217: ...SiBE341001 Piping Diagrams Appendix 208 BSV4Q100PV1 3D064148...
Page 218: ...Piping Diagrams SiBE341001 209 Appendix BSV6Q100PV1 3D064149...
Page 220: ...Wiring Diagrams for Reference SiBE341001 211 Appendix 2 2 BS Unit BSVQ100 160 250PV1 3D055928C...
Page 221: ...SiBE341001 Wiring Diagrams for Reference Appendix 212 BSV4Q100PV1 3D063928B...
Page 222: ...Wiring Diagrams for Reference SiBE341001 213 Appendix BSV6Q100PV1 3D063929B...
Page 223: ...SiBE341001 Option List Appendix 214 3 Option List 3 1 Option Lists Outdoor Unit 3D066354...