SiBE341001
Troubleshooting by Remote Controller
Troubleshooting
122
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Turn power supply off, and
turn power supply on again.
Return to normal?
YES
External factor other than
malfunction (for example, noise
etc.).
Check the electronic expansion valve corresponding to the malfunction code “
E9
” in the monitor
mode.
(Refer to P.106~P.107 for how to check.)
{
When Confirmation of malfunction 4 shows as follows:
→
Electronic expansion valve for main use (Y1E)
{
When Confirmation of malfunction 4 shows as follows:
→
Electronic expansion valve for refrigerant charge (Y2E)
{
When Confirmation of malfunction 4 shows as follows:
→
Electronic expansion valve for subcooling (Y3E)
{
Explanation of “ ”
Master unit
Slave unit 1
Slave unit 2
System
The connector of
outdoor unit PCB
(A1P) for electronic
expansion valve is
connected.
The coil resistance of
electronic expansion
valve is normal.
(Refer to
∗
1)
NO
Ensure correct connection.
NO
NO
YES
YES
Replace the electronic
expansion valve coil.
Replace the outdoor unit PCB
(A1P).
∗
Make measurement of resistance between the connector pins, and then make sure the resistance
falls in the range of 40 to 50
Ω
.
(Orange) 1
(Red) 2
(Yellow) 3
(Black) 4
5
COM[+] (Gray) 6
Measuring points
1 - 6
2 - 6
3 - 6
4 - 6
Judgement criteria
40~50
Ω
Summary of Contents for RQYQ140-180PY1
Page 216: ...Piping Diagrams SiBE341001 207 Appendix 1 2 BS Unit BSVQ100 160 250PV1 4D057985B...
Page 217: ...SiBE341001 Piping Diagrams Appendix 208 BSV4Q100PV1 3D064148...
Page 218: ...Piping Diagrams SiBE341001 209 Appendix BSV6Q100PV1 3D064149...
Page 220: ...Wiring Diagrams for Reference SiBE341001 211 Appendix 2 2 BS Unit BSVQ100 160 250PV1 3D055928C...
Page 221: ...SiBE341001 Wiring Diagrams for Reference Appendix 212 BSV4Q100PV1 3D063928B...
Page 222: ...Wiring Diagrams for Reference SiBE341001 213 Appendix BSV6Q100PV1 3D063929B...
Page 223: ...SiBE341001 Option List Appendix 214 3 Option List 3 1 Option Lists Outdoor Unit 3D066354...