Troubleshooting by Remote Controller
Troubleshooting
112
2.8
“
E3
”
Outdoor Unit: Actuation of High Pressure Switch
Remote
Controller
Display
E3
Applicable
Models
RQYQ-PY1
RQEQ-PY1
Method of
Malfunction
Detection
Use the protection device circuit to detect continuity at the high pressure switch.
Malfunction
Decision
Conditions
Abnormality is detected when the contact of the high pressure protection switch opens.
(Reference) Operating pressure of high pressure switch
Operating pressure: 4.0MPa
Reset pressure:
3.0MPa
Supposed
Causes
Actuation of outdoor unit high pressure switch
Defect of high pressure switch
Defect of outdoor unit main PCB (A1P)
Instantaneous power failure
Faulty high pressure sensor