39
input
Other values : Min. capacity modulating pump.
d
Minimum rpm hot water
30
30
Settings reach 20 – 50%
E
Min. flow temperature at OT (OpenTherm)
or RF thermostat
40
40
Settings reach 10 – 60°C
E.
Reaction OT and RF room thermostat
1
1
0= do not respond to CH request if requested temperature is
lower than the set value par. E
1= respond to CH request with minimum flow water
temperature limited to set value par. E
2= respond to CH request with maximum flow temperature as
set in the display (on/off function)
F
Start rpm CH
70
70
Settings reach 40 - 99% of the set maximum rpm
F.
Start rpm hot water
70
70
Settings reach 40 - 99% of the set maximum rpm
h
Max. rpm fan (* 100 rpm)
45
46
Setting reach 40 – 50
This parameter can be used to set the maximum rpm
L
Legionella prevention
0
0
0 = not active
1 = legionella prevention once per week
2 = legionella prevention day to day
n
Regulated flow temperature during boiler
operation (Ta)
80
80
Setting reach 60°C - 90°C
n.
Keep hot water temperature at Comfort/Eco
0
0
Setting reach: 0 or 40°C – 60°C
0= reheating temperature is equal to hot water temperature
Not applicable for heating only boilers
O.
Delay time CH request response
0
0
Settings reach 0 – 15 minutes
o
Delay time CH operation after hot water
operation
0
0
Settings reach 0 – 15 minutes
o.
Number of eco days
3
3
Settings reach 0, 1 to 10.
Not applicable for heating only boilers.
P
Anti-recycling time during CH operation
5
5
Minimum switch off time on CH operation
Can be set to 0 - 15 minutes
P.
Reference value hot water
0
0
Setting reach : 0, 24, 30, 36
Not applicable for heating only boilers.
q
Summer mode
0
0
0 = Summer mode deactivated
1 = Summer mode to be activated by button
(code in display : Su)
2 = Summer mode to be activated by button
(code in display : So)
3 = Summer mode to be activated by button
(code in display : Et)
r
Heating curve coefficient
0
0
Not active