SiUS181305E
Outdoor Unit
Printed Circuit Board Connector Wiring Diagram
14
1. Outdoor Unit
1.1
RMXS48LVJU
A1P: Main PCB
1) X5A
Connector to service PCB (A2P)
2) X11A
Connector for outdoor temperature thermistor
3) X12A
Connector for thermistors
(suction pipe 1, suction pipe 2, outdoor heat exchanger,
discharge pipe)
4) X13A
Connector for thermistors (subcooling outlet, liquid pipe)
5) X17A
Connector for high pressure sensor
6) X18A
Connector for low pressure sensor
7) X21A
Connector for electronic expansion valve coil (main)
8) X22A
Connector for electronic expansion valve coil (subcooling)
9) X25A
Connector for solenoid valve coil (four-way valve)
10)X26A
Connector for solenoid valve coil (hot gas bypass valve)
11)X27A
Connector for solenoid valve coil (unloading)
12)X28A
Connector for crankcase heater
13)X32A
Connector for high pressure switch
14)X37A
Connector for power supply for optional PCB (16 VDC)
15)X66A
Connector for cool / heat selector PCB (A4P)
16)X81A
Connector for terminal board (inter-unit wiring)
17)X106A
Connector for fan motor (upper)
18)X107A
Connector for fan motor (lower)
19)X111A
Connector for radiation fin thermistor
20)LD, LE
Connector for reactor
21)LC, NC
Terminal for noise filter PCB (A3P)
22)P
Connector for capacitor C4 +
23)N
Connector for capacitor C4 –
24)U, V, W
Connector for compressor
25)F4U
Fuse (6.3 A / 250 V)
26)F6U
Fuse (5.0 A / 250 V)
27)HAP
Operation pilot lamp (LED for service monitor: green)
28)HBP