Wiring

WARNING

1) Do not use tapped wires, stranded wires, extension cords, or starburst connections, as they may cause overheating, electrical shock, or 

fire.

2) Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the 

terminal block.) Doing so may cause electric shock or fire.

3) Be sure to install an earth leak detector. (One that can handle higher harmonics.)

(This unit uses an inverter, which means that it must be used an earth leak detector capable handling harmonics in order to 
prevent malfunctioning of the earth leak detector itself.)

4) Use an all-pole disconnection type breaker with at least 3mm between the contact point gaps.
5) Do not connect the power wire to the indoor unit. Doing so may cause electric shock or fire.

• Equipment complying with EN/IEC 61000-3-12

(1)

• Do not turn ON the safety breaker until all work is completed.

1) Strip the insulation from the wire (20mm).
2) Connect the connection wires between the 

indoor and outdoor units 

so that the terminal 

numbers match.

 Tighten the terminal screws 

securely. We recommend a flathead screw-
driver be used to tighten the screws. 

NOTE

(1)

European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-
voltage systems with input current >16 A and 

75 A per phase. 

Observe the notes mentioned following when wiring to the power supply 
terminal board.
Precautions to be taken for power supply wiring. 
Use a round crimp-style terminal for connection to the power supply  terminal 
board. In case it cannot be used due to unavoidable reasons, be sure to 
observe the following instruction. 
Place the round crimp-style terminals on the wires up to the covered part and 
secure in place. 

• Ground terminal installation 

Use the following method when installing the round 
crimp-style terminal. 

1
2
3

1 2 3

L N

Safety 
breaker 
20A

Earth leakage 
circuit breaker

Earth

Firmly fix the wires with 
the terminal screws.

Outdoor unit

Indoor 
unit

Power
supply
50Hz 220-240V 

Firmly fix the wires with 
the terminal screws.

Inter-unit wire
4-core 1.5mm² or more
H05RN

Power supply wire
3-core 2.5mm² or more
H05RN

Use the specified wire type 
and connect it securely.

Firmly secure wire retainer 
so wire terminations will not 
receive external stress.

Power supply 
terminal block

L

N

1

2

3

Stranded 
Wire

Round crimp-style
terminal

Good

Wrong

Round crimp-
style terminal

Flat washer

Screw

Flat washer

Round crimp-
style terminal

Screw

3PEN188780-2R.book  Page 9  Wednesday, March 16, 2016  3:46 PM

Summary of Contents for RKS71FAV1B

Page 1: ...INSTALLATION MANUAL R410A Split Series Models RXS71FAV1B8 RKS71FAV1B RX71GV1B8 RKS71FV1B RXS71FAV1B9 RX71GV1B9 RXS71FAV1B RXS71FV1B RX71GV1B 3PEN188780 2R book Page 1 Wednesday March 16 2016 3 46 PM...

Page 2: ...ompatibility 2004 108 EC 3SB64526 7F Shinri Sada Manager Quality Control Department 25th of Nov 2009 DAIKIN TCF 015 M18 11 2009 RXS71FV1B RKS71FV1B RXS71FAV1B RKS71FAV1B RX71GV1B KEMA Quality B V 7473...

Page 3: ...2 DEKRA Certification B V NB0344 74736 KRQ EMC97 4957 6 Shinri Sada Manager Quality Control Department RXS71FAV1B9 RX71GV1B9 Machinery 2006 42 EC Electromagnetic Compatibility 2004 108 EC Low Voltage...

Page 4: ...vamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo de B...

Page 5: ...3SB65451 4 fm Page 2 Thursday October 27 2011 4 49 PM 3PEN188780 2R book Page 4 Wednesday March 16 2016 3 46 PM...

Page 6: ...als If refrigerant gas leaks during installation ventilate the area immediately Toxic gas may be produced if the refrigerant comes into contact with fire After completing installation check for refrig...

Page 7: ...may shorten the life of the air conditioner 9 Since drain flows out of the outdoor unit do not place under the unit anything which must be kept away from moisture NOTE Cannot be installed hanging fro...

Page 8: ...noise and vibration may occur depending on how the unit is installed and the environment in which it is used 25cm from wall Right side plate 35cm Foot bolt hole centres Foot bolt hole centres 62cm CA...

Page 9: ...g drain hole Drain socket A into drain hole and drain caps B into drain hole and After insertion turn them about 40 clockwise NOTE Check that the drain receiver C is correctly engaged with the project...

Page 10: ...en tightening the flare nuts to prevent damage to the flare nuts and gas leakage Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand Then tighten them fully with the torqu...

Page 11: ...valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressure valve Hi High pressure valve subsequently requires no operation 3 Do vacuum pumping and...

Page 12: ...ow Use separate thermal insulation pipes for gas and liquid refrigerant pipes Gas side Liquid side Gas pipe thermal insulation Liquid pipe ther mal insulation O D 15 9mm O D 6 4mm I D 16 20mm I D 8 10...

Page 13: ...a human 1 You can expand the operation range to 15 C by turning on switch B SW4 on the PCB If the outdoor temperature falls to 20 C or lower the operation will stop If the outdoor temperature rises t...

Page 14: ...nternational Technical Standard setting the limits for harmonic currents produced by equipment connected to public low voltage systems with input current 16 A and 75 A per phase Observe the notes ment...

Page 15: ...ection the unit disables restart operation for 3 minutes after it is turned off 1 3 Carry out the test operation in accordance with the Operation Manual to ensure that all functions and parts such as...

Page 16: ...1603 HT 3P188780 2R M12B051C Two dimensional bar code is a code for manufacturing 3PEN188780 2R book Page 1 Wednesday March 16 2016 3 46 PM...

Reviews: