Installation Guidelines

• Where a wall or other obstacle is in the path of outdoor unit’s intake or exhaust airflow, follow the installation guidelines below.
• For any of the below installation patterns, the wall height on the exhaust side should be 1200mm or less.

Outdoor Unit Installation

1.

Installing Outdoor Unit

1) When installing the outdoor unit, refer to “Precautions for Selecting the Location” and the “Outdoor Unit Installation Drawings”.
2) If drain work is necessary, follow the procedures below.

2.

Drain Work

• Use drain plug for drainage.
• If the drain port is covered by a mounting base or floor surface, place additional foot bases of at least 100mm in height under the outdoor unit’s feet.
• In cold areas, do not use a drain hose with the outdoor unit.  (Otherwise, drain water may freeze, impairing heating performance.)

1) Insert drain receiver (C) onto drain socket (A) and drain cap (B) beyond 

4 projections around drain socket and drain cap. 

2) Insert drain socket and drain caps into their matching drain hole ; Drain socket 

(A) into drain hole   and drain caps (B) into drain hole   and  . After insertion, 
turn them about 40

°

 clockwise.

NOTE

Check that the drain receiver (C) is correctly engaged with the projections of the 
drain socket (A) and drain cap (B). Otherwise, water leakage may result. 

3) Connect vinyl hose on the market (intemal diameter of 25mm) to drain 

socket (A). 
(If the house is too long and hangs down, fix it carefully to prevent the 
kinks.)

4) Make sure that there is no water leakage from portion  ,  , or  .

NOTE

If the drain holes of the outdoor unit are covered with the mounting bracket or the floor, raise the unit to provide the space of more 
than 100mm under the leg of the outdoor unit.

More than 100

More than 350

Side view

1200
or less

More than 50

More than 50

More than 350

Top view

More 
than 100

Top view

Unit: mm

More than 100

More than 350

More than 50

Wall facing one side

Walls facing two sides

Walls facing three sides

Projections

Projections

(C) Drain receiver

(A) Drain socket

(B) Drain cap

I

II

III

(Be sure not to insert them into wrong drain holes,
or there causes water leakage.)

(View from bottom)

Projections 
(4 points)

Projections 
(4 points)

3PEN188780-2R.book  Page 4  Wednesday, March 16, 2016  3:46 PM

Summary of Contents for RKS71FAV1B

Page 1: ...INSTALLATION MANUAL R410A Split Series Models RXS71FAV1B8 RKS71FAV1B RX71GV1B8 RKS71FV1B RXS71FAV1B9 RX71GV1B9 RXS71FAV1B RXS71FV1B RX71GV1B 3PEN188780 2R book Page 1 Wednesday March 16 2016 3 46 PM...

Page 2: ...ompatibility 2004 108 EC 3SB64526 7F Shinri Sada Manager Quality Control Department 25th of Nov 2009 DAIKIN TCF 015 M18 11 2009 RXS71FV1B RKS71FV1B RXS71FAV1B RKS71FAV1B RX71GV1B KEMA Quality B V 7473...

Page 3: ...2 DEKRA Certification B V NB0344 74736 KRQ EMC97 4957 6 Shinri Sada Manager Quality Control Department RXS71FAV1B9 RX71GV1B9 Machinery 2006 42 EC Electromagnetic Compatibility 2004 108 EC Low Voltage...

Page 4: ...vamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo de B...

Page 5: ...3SB65451 4 fm Page 2 Thursday October 27 2011 4 49 PM 3PEN188780 2R book Page 4 Wednesday March 16 2016 3 46 PM...

Page 6: ...als If refrigerant gas leaks during installation ventilate the area immediately Toxic gas may be produced if the refrigerant comes into contact with fire After completing installation check for refrig...

Page 7: ...may shorten the life of the air conditioner 9 Since drain flows out of the outdoor unit do not place under the unit anything which must be kept away from moisture NOTE Cannot be installed hanging fro...

Page 8: ...noise and vibration may occur depending on how the unit is installed and the environment in which it is used 25cm from wall Right side plate 35cm Foot bolt hole centres Foot bolt hole centres 62cm CA...

Page 9: ...g drain hole Drain socket A into drain hole and drain caps B into drain hole and After insertion turn them about 40 clockwise NOTE Check that the drain receiver C is correctly engaged with the project...

Page 10: ...en tightening the flare nuts to prevent damage to the flare nuts and gas leakage Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand Then tighten them fully with the torqu...

Page 11: ...valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressure valve Hi High pressure valve subsequently requires no operation 3 Do vacuum pumping and...

Page 12: ...ow Use separate thermal insulation pipes for gas and liquid refrigerant pipes Gas side Liquid side Gas pipe thermal insulation Liquid pipe ther mal insulation O D 15 9mm O D 6 4mm I D 16 20mm I D 8 10...

Page 13: ...a human 1 You can expand the operation range to 15 C by turning on switch B SW4 on the PCB If the outdoor temperature falls to 20 C or lower the operation will stop If the outdoor temperature rises t...

Page 14: ...nternational Technical Standard setting the limits for harmonic currents produced by equipment connected to public low voltage systems with input current 16 A and 75 A per phase Observe the notes ment...

Page 15: ...ection the unit disables restart operation for 3 minutes after it is turned off 1 3 Carry out the test operation in accordance with the Operation Manual to ensure that all functions and parts such as...

Page 16: ...1603 HT 3P188780 2R M12B051C Two dimensional bar code is a code for manufacturing 3PEN188780 2R book Page 1 Wednesday March 16 2016 3 46 PM...

Reviews: