Forced Cooling Operation
SiUS041111
222
Trial Operation and Field Settings
2. Forced Cooling Operation
Indoor Unit (09/12 class)
Indoor Unit (15/18/24 class)
Outdoor Unit (15/18/24 class only)
Item
Forced Cooling
Conditions
The forced cooling operation is allowed when both the following conditions are
met.
1) The outdoor unit is not abnormal and not in the 3-minute standby mode.
2) The outdoor unit is not operating.
Start
The forced cooling operation starts when any of the following conditions is fulfilled.
1) Press the forced cooling operation ON/OFF button (SW1) on the indoor unit for
5 seconds.
2) Press the forced cooling operation ON/OFF switch (SW1) on the outdoor unit.
(15/18/24 class only)
Command
frequency
58 Hz: 09/12 class
30 Hz: 15/18/24 class
End
The forced cooling operation ends when any of the following conditions is fulfilled.
1) The operation ends automatically after 15 minutes.
2) Press the forced cooling operation ON/OFF button (SW1) on the indoor unit
again.
3) Press the ON/OFF button on the remote controller.
4) Press the forced cooling operation ON/OFF switch (SW1) on the outdoor unit.
Others
The protection functions are prior to all others in the forced cooling operation.
ON/OFF
(R14578)
ON/OFF button
(
SW1
)
ON/OFF button (SW1)
(R14258)
1
2
3
Screwdriver
SW1
(R14259)