SiUS041111
Troubleshooting
Service Diagnosis
91
4.10 Compressor Lock
Remote
Controller
Display
E6
Method of
Malfunction
Detection
A compressor lock is detected by the current waveform generated when applying high-frequency
voltage to the motor.
Malfunction
Decision
Conditions
If the error repeats, the system is shut down
Reset condition: Continuous run for about 11 minutes without any other error
Supposed
Causes
Compressor locked
Disconnection of compressor harness
Troubleshooting
Check No.15
Refer to P.120
(R14439)
Caution
NO
YES
YES
NO
NO
YES
Correct the power supply
or replace the outdoor unit
PCB.
∗
Inverter checker
Part No.: 1225477
Replace the compressor.
Replace the compressor.
Check the electronic
expansion valve.
Replace it as required.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
(Precaution before turning on the power again)
Make sure the power has been off for at least 30 seconds.
Turn off the power. Disconnect the
harnesses U, V, and W.
Check No.15
Check with the inverter checker (
∗
).
Turn off the power and reconnect
the harnesses. Turn on the power
again and restart the system.
Normal?
Emergency
stop without compressor
running?
System shut
down after errors repeated
several times?