SiUS371901E
Troubleshooting by Error Code
Service Diagnosis
302
3.37.2 Outdoor Fan Motor Abnormality (REYQ-XAYCU)
Error Code
E7
Applicable
Models
REYQ-XAYCU
Method of Error
Detection
Detects according to the value of current flowing through the fan PCB.
Error Decision
Conditions
Overcurrent is detected from the fan PCB (Detecting overcurrent 4 times will shut down the
system).
Current does not increase at fan motor startup or while the fan motor is in operation (Detecting 4
times will shut down the system).
Supposed
Causes
Fan motor failure
Neglect to connect or defective connection of harness/connector between the fan motor and the
PCB
Fan does not rotate due to foreign matter caught in it.
Clearing condition: fan motor performs normal operation for a period of 5 minutes
Troubleshooting
There are
foreign matter around the
applicable fan.
Remove the foreign matter.
YES
Check for the connections of all fan motor connectors. (
∗
1)
NO
Turn OFF the power supply, and then wait for a period of 10 minutes.
Some connectors are
disconnected.
Insert the connector.
YES
NO
NO
There is a relay
connection error.
Correct the connection of the
relay harness.
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
A
Check for any wire connection errors in 2 fan motors.
M1F: Connectors are white both on the PCB side and motor side.
M2F: Connectors are white on the PCB side and red on the motor side.
Check for Connection of Connector
Check for Colors of Connectors
There is no
continuity across the
fuse (F101U) on the fan
PCB.
Replace the fan PCB (A5P, A6P).
YES
NO
Outdoor units are equipped with 2 fan motors.
Check for M1F or M2F applicable to the error code
E7
while in
monitor mode of the outdoor unit.
Check in Monitor Mode
Go to the next page.
Summary of Contents for REYQ72-456XATJU
Page 415: ...SiUS371901E Wiring Diagrams Appendix 402 REYQ144 168XATJU 2D119206A ...
Page 416: ...Wiring Diagrams SiUS371901E 403 Appendix REYQ72 96 120XAYDU 2D119207B ...
Page 417: ...SiUS371901E Wiring Diagrams Appendix 404 REYQ144 168XAYDU 2D119208B ...
Page 418: ...Wiring Diagrams SiUS371901E 405 Appendix REYQ72 96 120 144 168XAYCU 2D119209A ...
Page 421: ...SiUS371901E Wiring Diagrams Appendix 408 FXZQ05 07 09 12 15 18TAVJU 3D110443A ...
Page 423: ...SiUS371901E Wiring Diagrams Appendix 410 FXEQ07 09 12 15 18 24PVJU 3D098557A ...
Page 426: ...Wiring Diagrams SiUS371901E 413 Appendix FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B ...
Page 428: ...Wiring Diagrams SiUS371901E 415 Appendix FXHQ12 24 36MVJU 3D048116C ...
Page 429: ...SiUS371901E Wiring Diagrams Appendix 416 FXAQ07 09 12 18 24PVJU C 3D075354D ...
Page 435: ...SiUS371901E Wiring Diagrams Appendix 422 VAM1200GVJU 3D073270D ...
Page 437: ...SiUS371901E Wiring Diagrams Appendix 424 1 4 2 Multi Branch Selector Unit BS4Q54TVJ 3D089123B ...
Page 438: ...Wiring Diagrams SiUS371901E 425 Appendix BS6 8Q54TVJ 2D089122B ...
Page 439: ...SiUS371901E Wiring Diagrams Appendix 426 BS10 12Q54TVJ 2D089121B ...
Page 440: ...Revision History Month Year Version Revised contents 04 2019 SiUS371901E First edition ...