41
3P362438-3H English
Malfunction code
Contents
Solution
Main
code
Sub code
Master/sub 1/sub 2
F3
01/02/03
•
Reverse connection of HP/LP gas pipe and suction
gas pipe of the BS unit
•
Check connection of HP/LP gas pipe and suction
gas pipe.
01/03/05
Discharge temperature too high (R2T/R21T/R22T):
•
Stop valve closed
•
Refrigerant shortage
•
Open stop valves.
•
Check refrigerant recharge unit.
20/21/22
Compressor casing temperature too high (R14T):
•
Stop valve closed
•
Refrigerant shortage
•
Open stop valves.
•
Check refrigerant recharge unit.
F6
02
•
Refrigerant overcharge
•
Stop valve closed
•
Check refrigerant recharge unit.
•
Open stop valves.
F9
01
02
05
Electronic expansion valve malfunction (BS unit)
Check connection on printed circuit board or actuator.
H9
01/02/03
Temperature sensor malfunction
(R1T) – A1P (X18A)
Check connection on printed circuit board or actuator.
J3
16/22/28
Temperature sensor malfunction
(R2T, R21T) – A1P (X19A)
Check connection on printed circuit board or actuator.
17/23/29
Temperature sensor malfunction
(R2T, R21T) – A1P (X19A)
Check connection on printed circuit board or actuator.
18/24/30
Temperature sensor malfunction
(R22T) – A1P (X19A)
Check connection on printed circuit board or actuator.
19/25/31
Temperature sensor malfunction
(R22T) – A1P (X19A)
Check connection on printed circuit board or actuator.
47/49/51
Temperature sensor malfunction
(R14T) – A1P (X19A)
Check connection on printed circuit board or actuator.
48/50/52
Temperature sensor malfunction
(R14T) – A1P (X19A)
Check connection on printed circuit board or actuator.
J5
01/03/05
Temperature sensor malfunction
(R12T) – A8P (X15A)
Check connection on printed circuit board or actuator.
18/19/20
Temperature sensor malfunction
(R10T) – A1P (X29A)
Check connection on printed circuit board or actuator.
J6
01/02/03
Temperature sensor malfunction
(R11T) – A8P (X15A)
Check connection on printed circuit board or actuator.
08/09/10
Temperature sensor malfunction
(R8T) – A1P (X29A)
Check connection on printed circuit board or actuator.
11/12/13
Temperature sensor malfunction
(R9T) – A1P (X29A)
Check connection on printed circuit board or actuator.
J7
01/02/03
Temperature sensor malfunction
(R3T) – A1P (X30A)
Check connection on printed circuit board or actuator.
06/07/08
Temperature sensor malfunction
(R7T) – A1P (X30A)
Check connection on printed circuit board or actuator.
J8
01/02/03
Temperature sensor malfunction
(R4T) – A1P (X30A)
Check connection on printed circuit board or actuator.
08/09/10
Temperature sensor malfunction
(R5T) – A1P (X30A)
Check connection on printed circuit board or actuator.
11/12/13
Temperature sensor malfunction
(R15T) – A8P (X15A)
Check connection on printed circuit board or actuator.
J9
01/02/03
Temperature sensor malfunction
(R6T) – A1P (X30A)
Check connection on printed circuit board or actuator.
11/12/13
Temperature sensor malfunction
(R13T) – A8P (X17A)
Check connection on printed circuit board or actuator.
JA
06/08/10
High pressure sensor malfunction (S1NPH): open
circuit – A1P (X32A)
Check connection on printed circuit board or actuator.
07/09/11
High pressure sensor malfunction (S1NPH): short
circuit – A1P (X32A)
Check connection on printed circuit board or actuator.