39

3P362438-3H English

No matter which control is selected, variations on the behavior of the 
system are still possible due to protection controls to keep the unit 
operating under reliable conditions. The intentional target, however, 

is fixed and will be used to obtain the best balance between energy 

consumption and comfort, depending on the application type. 

15 .4 .  Test operation

After installation and once the field settings are defined, the installer 

is obliged to verify correct operation. Therefore a test run must be 
performed according to the procedures described below.

15 .4 .1 .  Precautions before starting test operation

During test operation, the outdoor unit, the BS unit and the indoor 
units will start up:

• 

Make sure that the preparations of all BS units and all indoor units 

are finished (field piping, electrical wiring, air purge, etc.). See 

installation manual of the BS units and the indoor units for details.

 CAUTION

Do not insert fingers, rods or other objects into the air inlet or outlet. 

When the fan is rotating at high speed, it will cause injury.

 CAUTION

Do not perform the test operation while working on the BS units and 
the indoor units.
When performing the test operation, not only the outdoor unit, but the 
connected indoor unit will operate as well. 
Working on an indoor unit or BS unit while performing a test operation 
is dangerous.

 CAUTION

• 

During tests never pressurize the appliances with a pressure higher 

than the maximum allowable pressure (as indicated on the name

-

plate of the unit).

•  If refrigerant gas leaks, ventilate the area immediately. Toxic gas 

may be produced if refrigerant gas comes into contact with fire.

• 

Never directly touch any accidental leaking refrigerant. This could 
result in severe wounds caused by frostbite.

• 

Test run is possible for ambient temperatures between -4°F and 
95°F (-20°C and 35°C).

 DANGER: DO NOT TOUCH PIPING AND INTERNAl PARTS

See Safety considerations on page i.

 DANGER:ElECTRICAl SHOCk

See Safety considerations on page i.

• 

Provide a logbook and machine card.
In accordance with the applicable legislation, it may be necessary to 
provide a logbook with the equipment containing at least: informa-
tion on maintenance, repair work, results of tests, stand-by periods, 
etc.

 INFORMATION

Note that during the first running period of the unit, required power in

-

put may be higher. This phenomenon originates from the compressor 
that requires a 50 hour run elapse before reaching smooth operation 
and stable power consumption. Reason is that the scroll is made out 
of iron and that it takes some time to smooth the surfaces that make 
contact.

 NOTE

To protect the compressor, be sure to turn on the power supply 6 
hours before starting operation.

15 .4 .2 .  Test operation

The procedure below describes the test operation of the complete 
system. This operation checks and judges following items:

• 

Check of wrong wiring (communication check with indoor units).

• 

Check of the stop valves opening.

•  Judgment of piping length.

On top of this system test operation, BS units and indoor units opera-
tion should also be checked separately.

•  Make sure to carry out the system test operation after the first 

installation. Otherwise, the malfunction code U3 will be displayed 
on the user interface and normal operation or individual BS unit and 
indoor unit test run cannot be carried out.

• 

Abnormalities on BS unit and indoor units cannot be checked for 

each unit separately. After the test operation is finished, check the 

BS units and the indoor units one by one by performing a normal 
operation using the user interface. Refer to the BS unit and the 
indoor unit installation manual for more details concerning the 
individual test run.

 INFORMATION

• 

It may take 10 minutes to achieve a uniform refrigerant state before 
the compressor starts. 

• 

During the test operation, the refrigerant running sound or the mag-
netic sound of a solenoid valve may become loud and the display 
indication may change. 
These are not malfunctions.

Procedure

Close all front panels in order to not let it be the cause of misjudg-
ment.

Make sure all field settings you want are set; see 15.2. Monitoring 
function and field settings on page 33.

Turn ON the power to the outdoor unit, the connected BS units and 
the connected indoor units.

 NOTE

Be sure to turn on the power 6 hours before operation in order to have 
power running to the crankcase heater and to protect the compressor.

Make sure the default (idle) situation is existing; see 13.2. Operat

-

ing the push buttons and DIP switches on the printed circuit board 

on page 24. Push BS2 for 5 seconds or more. The unit will start 

test operation.

01_EN_3P362438-3H.indb   39

1/14/2015   10:20:24 AM

Summary of Contents for REYQ120TTJU

Page 1: ...REYQ264TTJU REYQ288TTJU REYQ312TTJU REYQ336TTJU REYQ360TTJU REYQ384TTJU REYQ408TTJU REYQ432TTJU REYQ456TTJU REYQ72TYDN REYQ96TYDN REYQ120TYDN REYQ144TYDN REYQ168TYDN REYQ192TYDN REYQ216TYDN REYQ240TYD...

Page 2: ...ING Only qualified personnel must carry out the installation work Installation must be done in accordance with this installation manual Improper installation could result in water leakage electric sho...

Page 3: ...away from fluorescent lamps as much as possible Indoor units are for indoor installation only Outdoor units can be installed either outdoors or indoors This unit is for indoor use Do not install the a...

Page 4: ...ize 9 7 4 Selection of refrigerant branch kits 10 7 5 System piping length limitations 11 8 Precautions on refrigerant piping 14 8 1 Caution for brazing 14 8 2 Connecting the refrigerant piping 14 8 3...

Page 5: ...1 REYQ120TTJU TYDN 1 REYQ144TTJU TYDN 1 72 96 120 144 168 REYQ168TTJU TYDN 1 REYQ192TTJU TYDN 1 1 REYQ216TTJU TYDN 1 1 REYQ240TTJU TYDN 1 1 REYQ264TTJU TYDN 1 1 REYQ288TTJU TYDN 2 REYQ312TTJU TYDN 1...

Page 6: ...accessories is shown in the figure below Accessories assy piping Accessories assy operation and installation manual NOTE Do not throw away any of the accessories until installation is complete They ar...

Page 7: ...e reasonable protection against such interference However there is no guarantee that inter ference will not occur in a particular installation It is therefore recommended to install the equipment and...

Page 8: ...nopy 2 Construct a pedestal NOTE When operating the unit in a low outdoor ambient temperature with high humidity conditions make sure to take precautions to keep the drainholes of the unit free by usi...

Page 9: ...a Front side Suction side b h2 2 or more Service space h1 2 or more h1 b a 59 in 1500 mm b 19 5 8 in 500 mm In case of an installation site where sides A B C D have obsta cles the wall heights of sid...

Page 10: ...y attention to the position of the unit s center of gravity NOTE Use a belt sling of 3 4 in 20 mm wide that adequately bears the weight of the unit A forklift can only be used for transport as long as...

Page 11: ...0 mm above the foundation surface A A 13 16 in 20 mm NOTE There are restrictions on the refrigerant pipe connecting order between outdoor unit in the case of the multi system See 1 2 2 Outdoor unit co...

Page 12: ...r other contamination Foreign materials inside pipes including oils for fabrication must be 0 14 gr 10 ft 30 mg 10 m or less Use the following items for the refrigerant piping Material Jointless phosp...

Page 13: ...e on page 9 When using REFNET joints at the first branch from the outdoor unit choose from the following table in accordance with the capacity of the outdoor unit example REFNET joint a see 7 3 Select...

Page 14: ...i connection piping kit must always be installed horizontally paying attention to the installation restrictions indicated in 8 Precautions on refrigerant piping Example of connection 8 indoor units ar...

Page 15: ...t 40 m From indoor unit to indoor unit Height difference From outdoor unit to outdoor unit Height difference Height difference between outdoor units H3 16 ft 5 m Allowable length after branch 3 Actual...

Page 16: ...8 A G p Indoor unit 1 8 j k BS BS BS BS BS BS BS 2 s r q b c d e f g p 130 ft 40 m From outdoor unit to the farthest indoor unit 9 From outdoor unit to the nearest indoor unit 1 2 The total piping len...

Page 17: ...gh with Dry Nitrogen prevents the creation of large quantities of oxidized film on the inside of the piping An oxidized film ad versely affects valves and compressors in the refrigerating system and p...

Page 18: ...cting with the burner flame Liquid pipe stop valve Suction gas pipe stop value Protective plate Stop valve mounting plate High Low pressure gas pipe stop valve 5 Cut off the lower part of the smaller...

Page 19: ...ions to the branch kits are the responsibility of the installer field piping 8 2 4 Precautions when connecting piping between outdoor units multiple outdoor unit system To connect the piping between o...

Page 20: ...branches either horizontally or vertically Mount the REFNET header so that it branches horizontally 2 Installation of the multi connection piping kit A 1 B 1 C D 15 C 4 3 4 in 120 mm D 19 11 16 in 50...

Page 21: ...installed by a licensed elec trician and must comply with relevant local and national regulations Be sure to use a dedicated power circuit Never use a power supply shared by another appliance Never in...

Page 22: ...61 9A 61 9A 43 0A 43 0A 43 0A 38 0A 43 0A 61 9A 38 0A 55 0A 61 9A 55 0A 55 0A 55 0A 55 0A 55 0A 61 9A 15 2A 21 1A 21 1A 31 9A 36 1A 15 2A 21 1A 21 1A 21 1A 21 1A 31 9A 21 1A 31 9A 31 9A 31 9A 31 9A 3...

Page 23: ...11 BS unit 12 Indoor unit 13 Indoor unit Cooling only The Outdoor unit that connect the transmission wiring to BS unit is Master unit of the multi system And the other units are Sub unit In this figur...

Page 24: ...230 V 60 Hz 2 Branch switch Overcurrent breaker 3 Ground wire 4 Control box 5 Only REYQ TYDN Control box 2 6 Only REYQ TYDN Do not open the control box 2 cover There are no work when installation 7 At...

Page 25: ...connect it using a conduit Choose an appropriate knockout hole for conduit size suitable for the power and ground line to be used Transmission line Connect it using a conduit in the knockout hole on t...

Page 26: ...uge rises or not If it rises the system may either contain moisture inside or have leaks NOTE During the rainy season moisture might enter the piping If working during a rainy season and the work take...

Page 27: ...To access you can remove the front inspection door of the front panel see figure Now you can open the inspection door of the control box front panel see figure You can see 3 push buttons and 3 seven s...

Page 28: ...situation is the amount of indoor units which are con nected to the system Result mode 1 setting 10 is addressed and selected return value is monitored information To leave the monitoring function pus...

Page 29: ...efriger ant charge In case recharge is required refer to the nameplate of the unit It states the type of refrigerant and necessary amount 14 2 Calculating the additional refrigerant charge NOTE The re...

Page 30: ...REYQ120TTJU BS units BS4Q54T 1 BSQ60T 1 BSQ96T 1 Indoor units FXMQ type 18 1 24 2 36 1 54 1 FXFQ type 36 2 Other 48 1 Liquid piping a f3 4 60 ft e f1 4 15 ft i f3 8 20 ft m f3 8 20 ft r f1 2 10 ft b f...

Page 31: ...r refrigerant to reach R Q Step 4b Close valve B R Q Step 5 Open all outdoor unit stop valves Step 6 Proceed with automatic or manual charge A Automatic charge B Manual charge Step 6a Push BS2 once 88...

Page 32: ...des appear E 2 indoor temperature out of range and E 3 outdoor temperature out of range In this case perform automatic charging procedure again See figure Location of valves next page for more informa...

Page 33: ...ns to be taken see 14 3 1 Flow chart on page 28 To speed up the process of pre charging refrigerant for large systems it is recommended to first charge a portion of the refrigerant before performing a...

Page 34: ...he unit indicates E 2 or E 3 the ambient conditions are NOT favorable to execute the test run Push BS1 to finish the automatic charging procedure INFORMATION In case a malfunction code occurred during...

Page 35: ...ing for each outdoor unit and calculate the average subcooling of the outdoor unit Systems should have a subcooling of 11 3 F 6 2 C a If average subcooling is low add charge to raise subcooling to 11...

Page 36: ...nominal operating conditions Low noise operation can be set in mode 2 There are two methods to activate low noise operation of the outdoor unit system The first method is to enable an automatic low n...

Page 37: ...onsumption limitation conditions when an external signal is sent to the unit this setting should be changed This setting will only be effective when the optional external control adaptor DTA104A61 62...

Page 38: ...efines the level power consumption limitation that will be applied continuously The level is according to the table Default value 0 OFF Value 2 32 Restriction reference 0 Function not active default 1...

Page 39: ...ing is used in conjunction with setting 2 9 For more information and advice about the impact of these settings see 15 3 Energy saving and optimum operation 15 3 Energy saving and optimum operation Thi...

Page 40: ...ion or undershoot during cooling operation is allowed compared to the requested refrigerant tem perature in order to achieve the required room temperature very fast The overshoot is allowed from the s...

Page 41: ...erature evolution A B C D E F A Indoor unit set temperature B Operation start C Operating time D Mild E Quick F Powerful Example Automatic mode during cooling A B 100 70 E Tc C D 120 F 49 C F 115 F 46...

Page 42: ...sts stand by periods etc INFORMATION Note that during the first running period of the unit required power in put may be higher This phenomenon originates from the compressor that requires a 50 hour ru...

Page 43: ...ting the abnormality press BS3 to reset the malfunction code and retry operation The malfunction code which is displayed on the outdoor unit will indi cate a main malfunction code and a sub code The s...

Page 44: ...r malfunction R14T A1P X19A Check connection on printed circuit board or actuator J5 01 03 05 Temperature sensor malfunction R12T A8P X15A Check connection on printed circuit board or actuator 18 19 2...

Page 45: ...V1 voltage power shortage or open phase Check if power supply is within range Correct phase order 02 09 12 INV1 reversed or open power supply phase Check if power supply is within range Correct phase...

Page 46: ...3P362438 3H EM14A006B 1502 HT...