Installation manual

5

REQ71+10 REQ7 REQ71~12 REQ71B2W1B

Split System air conditioners

4PW23690-1C

Refrigerant pipe size

Pair system 

(See figure 2)

Allowable pipe length and height difference

See the table below concerning lengths and heights. Refer to

figure 2

.

The minimal piping length should be 5 m. If installation is performed
with less field piping, the system will be overcharged (abnormal HP,
etc.). If the distance between indoor and outdoor unit is less than
5 m, please make sure that the piping length is 

5 m by additional

bending of the pipes.

P

RECAUTIONS

 

ON

 

REFRIGERANT

 

PIPING

Do not allow anything other than the designated refrigerant to
get mixed into the freezing cycle, such as air, etc. If any
refrigerant gas leaks while working on the unit, ventilate the
room thoroughly right away.

Use R410A only when adding refrigerant
Installation tools:
Make sure to use installation tools (gauge manifold charge hose,
etc.) that are exclusively used for R410A installations to
withstand the pressure and to prevent foreign materials (e.g.
mineral oils and moisture) from mixing into the system.
Vacuum pump:
Use a 2-stage vacuum pump with a non-return valve
Make sure the pump oil does not flow oppositely into the system
while the pump is not working.
Use a vacuum pump which can evacuate to –100.7 kPa (5 Torr,
–755 mm Hg).

In order to prevent dirt, liquid or dust from entering the piping,
cure the piping with a pinch or taping.

Great caution is needed when passing copper tubes through
walls.

When using existing refrigerant piping
Pay attention to the following points when using existing
refrigerant piping.

Perform a visual check on quality of residual oil in existing
refrigerant piping.
This check is extremely important because using existing
piping with deteriorated oil will cause compressor
breakdown.
- Put some residual oil of the pipes you want to reuse on a 

piece of white paper or on the white surface of an oil 
checking reference card and compare that oil color with the 
circled color of the oil checking reference card.

- If oil color is identical to the circled color or darker, replace 

the piping, install new piping or clean the piping thoroughly.

- If oil color is lighter, the pipes can be reused without 

cleaning.

An oil checking reference card is indispensable for such
evaluation and can be obtained at your dealer.

In the following situations, the existing piping should not be
re-used and new piping should be installed.
- If the previously used model had problems with its 

compressor (this might cause oxidized coolant oil, scale 
residue and other adverse effects).

- If the indoor or outdoor units were disconnected from the 

piping for a long period of time (water or dirt might have 
gotten into the piping).

- If copper piping is corroded.

Flares should not be re-used but rather new ones made in
order to prevent leaks.

Check welded connections for gas leaks, if the local piping
has welded connections.

Replace deteriorated insulation with new material.

R

EFRIGERANT

 

PIPING

Field pipes can be installed in four directions.

Figure - Field pipes in four directions

Cutting out the two slits makes it possible to install as shown in
the 

figure "Field pipes in four directions"

.

(Use a metal saw to cut out the slits.)

To  install the connecting pipe to the unit in a downward
direction, make a knockout hole by penetrating the center area
around the knockout hole using a 

Ø

6 mm drill. (See 

figure "Field

pipes in four directions"

.)

After knocking out the knock-out, it is recommended to apply
repair paint to the edge and the surrounding end surfaces to
prevent rusting.

Refrigerant pipe size

Gas pipe

Class

Standard size

Size-up

Liquid pipe

71, 100, 125

Ø15.9

Ø19.1

Ø9.5

Allowable pipe length

Maximum allowable piping length (Parenthesized 
figure represents equivalent length)

L1

50 m (70 m)

Maximum height between indoor and outdoor

H1

30 m

Chargeless length

L1

7.5 m

Place

Installation period

Protection method

Outdoor unit

More than a month

Pinch the pipe

Less than a month

Pinch or tape the 

pipe

Indoor

Regardless of the 

period

1

Drill

2

Center area around knockout hole

3

Knockout hole

4

Slit

5

Connecting pipe

6

Bottom frame

7

Front plate

8

Pipe outlet plate

9

Screw front plate

10

Pipe outlet plate screw

A

Forward

B

Backward

C

Sideways

D

Downward

4

4

3

2

1

7

8

9

10

A

D

C

B

5

6

Summary of Contents for REQ71B8V3B

Page 1: ...INSTALLATION MANUAL REQ71B8V3B REQ71B2V3B REQ100B8V3B REQ71B8W1B REQ71B2W1B REQ100B8W1B REQ125B8W1B Split System air conditioners...

Page 2: ...4 5 6 6 3 1 2 3 4 5 A B A E B C D H H1 L1 A A B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 A A B1 B1 B1 B1 B1 B1 B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 1 1 2...

Page 3: ...hold til bestemmelsene i 13 noudattaen m r yksi 14 za dodr en ustanoven p edpisu 15 prema odredbama 16 k veti a z 17 zgodnie z postanowieniami Dyrektyw 18 n urma prevederilor 19 ob upo tevanju dolo b...

Page 4: ...cuit Insufficient capacity of the power supply circuit or improper electrical construction may lead to electric shocks or fire Make sure that all wiring is secure using the specified wires and ensurin...

Page 5: ...thinner or gasoline are handled Such gases may cause a fire Where the air contains high levels of salt such as that near the ocean Where voltage fluctuates a lot such as that in factories In vehicles...

Page 6: ...ease install a waterproof plate within 150 mm of the underside of the unit in order to prevent the invasion of water from the lower direction 6 When installing the unit in a place frequently exposed t...

Page 7: ...omply with relevant local and national regulations The minimal pipe thickness for R410A piping must be in accordance with the table below O Annealed 1 2H Half hard Suction side obstacle Obstacle is pr...

Page 8: ...rd If oil color is identical to the circled color or darker replace the piping install new piping or clean the piping thoroughly If oil color is lighter the pipes can be reused without cleaning An oil...

Page 9: ...erly Check for refrigerant leakage after tightening the cap Cautions for handling service port After the work tighten the valve cover in place Tightening torque 10 8 14 7 N m Precautions when connecti...

Page 10: ...arming potential Please fill in with indelible ink the factory refrigerant charge of the product the additional refrigerant amount charged in the field and the total refrigerant charge on the fluorina...

Page 11: ...ulations NOTE Piping length is the 1 way length gas or liquid Connected piping length is between Class 7 5 30 m 30 40 m 40 50 m 71 0 20 0 70 1 20 100 125 0 10 0 60 1 10 NOTE In case of complete rechar...

Page 12: ...not use a wire conduit be sure to protect the wires with vinyl tubes to prevent the edge of the knock out hole from cutting the wires Follow the electric wiring diagram for electrical wiring works For...

Page 13: ...in case of W1 units E0 or E6 will be displayed on the remote controller of the indoor unit Operation will be impossible with either one of these phenomena If this happens turn off the power re check...

Page 14: ...A Q1M Q2M Thermo switch M1F M2F Q1RP Phase reverse circuit R1T Thermistor air R2T Thermistor coil R3T Thermistor discharge RC Signal receiver circuit S1PH Pressure switch HIGH S1PL Pressure switch LOW...

Page 15: ...NOTES NOTES...

Page 16: ...4PW23690 1C Copyright Daikin...

Reviews: