Split System air conditioners
4PW23690-1C

Installation manual

4

I

NSTALLATION

 

SERVICING

 

SPACE

The numerical figures used in here represent the dimensions for the
71-100-125 class models. Figures between (  ) indicate the
dimensions for the 100-125 class models. (Unit: mm)

(Refer to 

"Precautions on installation" on page 3

)

Precaution

(A) In case of non-stacked installation 

(See figure 1)

(B) In case of stacked installation

1.

In case obstacles exist in front of the outlet side.

2.

In case obstacles exist in front of the air inlet.

Do not stack more than one unit.

About 100 mm is required as the dimension for laying the upper
outdoor unit's drain pipe. Get the portion A sealed so that air from the
outlet does not bypass.

(C) In case of multiple-row installation (for roof top use, etc.)

1.

In case of installing one unit per row.

2.

In case of installing multiple units (2 units or more) in lateral
connection per row.

Relation of dimensions of H, A and L are shown in the table below.

R

EFRIGERANT

 

PIPE

 

SIZE

 

AND

 

ALLOWABLE

 

PIPE

 

LENGTH

Selection of piping material

Construction material: phosphoric acid deoxidized seamless
copper for refrigerant.

Temper grade: use piping with temper grade in function of the
pipe diameter as listed in table below.

The pipe thickness of the refrigerant piping should comply with
relevant local and national regulations. The minimal pipe
thickness for R410A piping must be in accordance with the table
below.

O=Annealed
1/2H=Half hard

Suction side obstacle

Obstacle is present

Discharge side obstacle

1

In these cases, close the 
bottom of the installation 
frame to prevent the 
discharged air from 
being bypassed

Left side obstacle

Right side obstacle

2

In these cases, only 2 
units can be installed.

Top side obstacle

This situation is not 
allowed

1000

100

A

200

(300)

100

A

500 (1000)

100 (200)

1000 (2000)

50 (100)

L

A

L

H

0<L

1/2H

150 (250)

1/2H<L

200 (300)

H<L

Installation impossible

All field piping must be installed by a licensed refrigeration
technician and must comply with relevant local and
national regulations.

NOTE

To persons in charge of piping work:

Be sure to open the shut-off valve after installing
piping and vacuming is complete. (Running the
system with the valve closed may break the
compressor.)

It is forbidden to discharge refrigerant into the
atmosphere. Collect the refrigerant in accordance
with relevant local and national regulations.

Do not use flux when brazing the refrigerant piping.
For brazing, use phosphor copper brazing filler metal
(BCuP) which does not require a flux.
(If a chlorine flux is used, the piping will corrode, and if
the flux contains fluoride, it will cause the coolant oil to
deteriorate, adversely affecting the coolant piping
system.)

Pipe Ø

Temper grade of piping 

material

Minimal thickness t(mm)

9.5

O

0.80

15.9

O

1.20

19.1

1/2H

1

1000 (1500)

400 (600)

2000 (3000)

A

H

L

Summary of Contents for REQ71B8V3B

Page 1: ...INSTALLATION MANUAL REQ71B8V3B REQ71B2V3B REQ100B8V3B REQ71B8W1B REQ71B2W1B REQ100B8W1B REQ125B8W1B Split System air conditioners...

Page 2: ...4 5 6 6 3 1 2 3 4 5 A B A E B C D H H1 L1 A A B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 A A B1 B1 B1 B1 B1 B1 B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 1 1 2...

Page 3: ...hold til bestemmelsene i 13 noudattaen m r yksi 14 za dodr en ustanoven p edpisu 15 prema odredbama 16 k veti a z 17 zgodnie z postanowieniami Dyrektyw 18 n urma prevederilor 19 ob upo tevanju dolo b...

Page 4: ...cuit Insufficient capacity of the power supply circuit or improper electrical construction may lead to electric shocks or fire Make sure that all wiring is secure using the specified wires and ensurin...

Page 5: ...thinner or gasoline are handled Such gases may cause a fire Where the air contains high levels of salt such as that near the ocean Where voltage fluctuates a lot such as that in factories In vehicles...

Page 6: ...ease install a waterproof plate within 150 mm of the underside of the unit in order to prevent the invasion of water from the lower direction 6 When installing the unit in a place frequently exposed t...

Page 7: ...omply with relevant local and national regulations The minimal pipe thickness for R410A piping must be in accordance with the table below O Annealed 1 2H Half hard Suction side obstacle Obstacle is pr...

Page 8: ...rd If oil color is identical to the circled color or darker replace the piping install new piping or clean the piping thoroughly If oil color is lighter the pipes can be reused without cleaning An oil...

Page 9: ...erly Check for refrigerant leakage after tightening the cap Cautions for handling service port After the work tighten the valve cover in place Tightening torque 10 8 14 7 N m Precautions when connecti...

Page 10: ...arming potential Please fill in with indelible ink the factory refrigerant charge of the product the additional refrigerant amount charged in the field and the total refrigerant charge on the fluorina...

Page 11: ...ulations NOTE Piping length is the 1 way length gas or liquid Connected piping length is between Class 7 5 30 m 30 40 m 40 50 m 71 0 20 0 70 1 20 100 125 0 10 0 60 1 10 NOTE In case of complete rechar...

Page 12: ...not use a wire conduit be sure to protect the wires with vinyl tubes to prevent the edge of the knock out hole from cutting the wires Follow the electric wiring diagram for electrical wiring works For...

Page 13: ...in case of W1 units E0 or E6 will be displayed on the remote controller of the indoor unit Operation will be impossible with either one of these phenomena If this happens turn off the power re check...

Page 14: ...A Q1M Q2M Thermo switch M1F M2F Q1RP Phase reverse circuit R1T Thermistor air R2T Thermistor coil R3T Thermistor discharge RC Signal receiver circuit S1PH Pressure switch HIGH S1PL Pressure switch LOW...

Page 15: ...NOTES NOTES...

Page 16: ...4PW23690 1C Copyright Daikin...

Reviews: