The filled out label must be adhered on the inside of the product and
in the proximity of the product charging port (e.g. on the inside of the
service cover).

Precaution for servicing

This unit requires additional charging of refrigerant according to the
length of piping connected at the site. Charge the refrigerant to the
liquid pipe in its liquid state. Since R410A is a mixed refrigerant, its
composition changes if charged in a state of gas and normal system
operation would no longer be assured.

On this model it is not necessary to charge additionaly if the piping
length 

7.5 m.

Additional charging of refrigerant

Over 7.5 m, please add refrigerant quantity according to the
following table. 

For future servicing, mark with a circle the selected amount on the
table below.

Additional charging amount <unit: kg>

Total charging weight of the refrigerant (after a leak, 
etc.)

When the entire refrigerant pipe length is within 7.5 meters, charge
the refrigerant in accordance with the amount mentioned in the
nameplate, and when the pipe length exceeds 7.5 meters, the
charging amount mentioned in the nameplate and that required for
additional charging are to be totalled as the net charging amount.

Precaution for pumping-down operation

The outdoor unit is equipped with a low-pressure switch to protect the
compressor. 

Take the following steps to perform the pumping-down operation.

This is the end of pumping-down operation. After pumping-down
operation, the remote controller can show the following:

-

"U4"

-

blank screen

-

indoor fan operates for about 30 seconds

Even when the ON button on the remote controller is pressed, it will
not operate. Turn off the main power supply switch and turn it on
again in need of operation.

E

LECTRICAL

 

WIRING

 

WORK

NOTE

National implementation of EU regulation on certain
fluorinated greenhouse gases may require to provide the
appropriate official national language on the unit.
Therefore, an additional multilingual fluorinated
greenhouse gases label is supplied with the unit.

Sticking instructions are illustrated on the backside of that
label.

When performing service on the unit requiring the
refrigerant system to be opened, refrigerant must be
evacuated according to local regulations.

NOTE

Piping length is the 1 way length, gas or liquid.

Connected piping length is between

Class

7.5~30 m

30~40 m

40~50 m

71

+0.20

+0.70

+1.20

100+125

+0.10

+0.60

+1.10

NOTE

In case of complete recharge of the refrigerant, please first
execute vacuuming. Execute this vacuuming from the
service port. Do not use the port of the stop valve for
vacuuming. Vacuuming can not be executed completely
using such port.

Position of service port:

Heat pump units have 2 ports on the piping. One
between the liquid receiver and the electronic
expansion valve and another one between the heat
exchanger and the 4-way valve.

3

5

6

2

1

4

1

factory refrigerant charge 
of the product:
see unit name plate

2

additional refrigerant 
amount charged in the 
field

3

total refrigerant charge

4

Contains fluorinated 
greenhouse gases 
covered by the Kyoto 
Protocol

5

outdoor unit

6

refrigerant cylinder and 
manifold for charging

NOTE

Never short-circuit the low pressure switch in this
operation.

Procedure

Precaution

1

Put a pressure gauge at the 
service port of the gas stop valve.

Use a pressure gauge reserved for 
R410A exclusively.

2

Start the fan operation with the 
remote controller.

Confirm that stop valves both on 
the liquid and gas side are open.

3

Push the pumping-down button on 
the PC board of the outdoor unit.

Compressor and outdoor fan will 
start operation automatically.
If step 3 is performed before step 
2, then the indoor fan may 
automatically start running. Please 
pay attention to this.

4

Continue operation for 2 minutes 
until operation condition stabilizes.

5

Close the stop valve on the liquid 
side securely. (See 

"How to use 

the shut-off valve" on page 6

)

Insecure closing of the valve may 
result in burning of the 
compressor.

6

When the low-pressure switch is 
activated, the unit stops working. 
At this time, close the stop valve on 
the gas side.

All wiring must be performed by an authorized
electrician.

All components procured on the site and all electric
construction should comply with the applicable local
and national codes.

High voltage
To avoid electrical shock, make sure to disconnect the
power supply 1 minute or more before servicing the
electrical parts. Even after 1 minute, always measure
the voltage at the terminals of main circuit capacitors
or electrical parts and, before touching, make sure
that those voltages are 50 V DC or less.

NOTE

To persons in charge of electrical wiring work:

Do not operate the unit until the refrigerant piping is
complete. (Running it before the piping is ready will break
the compressor.)

Summary of Contents for REQ71B8V3B

Page 1: ...INSTALLATION MANUAL REQ71B8V3B REQ71B2V3B REQ100B8V3B REQ71B8W1B REQ71B2W1B REQ100B8W1B REQ125B8W1B Split System air conditioners...

Page 2: ...4 5 6 6 3 1 2 3 4 5 A B A E B C D H H1 L1 A A B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 A A B1 B1 B1 B1 B1 B1 B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 1 1 2...

Page 3: ...hold til bestemmelsene i 13 noudattaen m r yksi 14 za dodr en ustanoven p edpisu 15 prema odredbama 16 k veti a z 17 zgodnie z postanowieniami Dyrektyw 18 n urma prevederilor 19 ob upo tevanju dolo b...

Page 4: ...cuit Insufficient capacity of the power supply circuit or improper electrical construction may lead to electric shocks or fire Make sure that all wiring is secure using the specified wires and ensurin...

Page 5: ...thinner or gasoline are handled Such gases may cause a fire Where the air contains high levels of salt such as that near the ocean Where voltage fluctuates a lot such as that in factories In vehicles...

Page 6: ...ease install a waterproof plate within 150 mm of the underside of the unit in order to prevent the invasion of water from the lower direction 6 When installing the unit in a place frequently exposed t...

Page 7: ...omply with relevant local and national regulations The minimal pipe thickness for R410A piping must be in accordance with the table below O Annealed 1 2H Half hard Suction side obstacle Obstacle is pr...

Page 8: ...rd If oil color is identical to the circled color or darker replace the piping install new piping or clean the piping thoroughly If oil color is lighter the pipes can be reused without cleaning An oil...

Page 9: ...erly Check for refrigerant leakage after tightening the cap Cautions for handling service port After the work tighten the valve cover in place Tightening torque 10 8 14 7 N m Precautions when connecti...

Page 10: ...arming potential Please fill in with indelible ink the factory refrigerant charge of the product the additional refrigerant amount charged in the field and the total refrigerant charge on the fluorina...

Page 11: ...ulations NOTE Piping length is the 1 way length gas or liquid Connected piping length is between Class 7 5 30 m 30 40 m 40 50 m 71 0 20 0 70 1 20 100 125 0 10 0 60 1 10 NOTE In case of complete rechar...

Page 12: ...not use a wire conduit be sure to protect the wires with vinyl tubes to prevent the edge of the knock out hole from cutting the wires Follow the electric wiring diagram for electrical wiring works For...

Page 13: ...in case of W1 units E0 or E6 will be displayed on the remote controller of the indoor unit Operation will be impossible with either one of these phenomena If this happens turn off the power re check...

Page 14: ...A Q1M Q2M Thermo switch M1F M2F Q1RP Phase reverse circuit R1T Thermistor air R2T Thermistor coil R3T Thermistor discharge RC Signal receiver circuit S1PH Pressure switch HIGH S1PL Pressure switch LOW...

Page 15: ...NOTES NOTES...