background image

IM 1272 • OPTILINE VERTICAL FAN COILS 24 www.DaikinApplied.com

Addendum

Fan Controls

1. 

Fan Output Adjustment:

 Fan output can be set to 

minimum adjustment (AO2 Low (E7)) from 0-5 Vdc 

and to maximum adjustment (AO2 High (E8)) from 

5 to 10 Vdc. 
These two values are adjusted by a balancing contractor 

that will measure minimum and maximum CFM the fan 

will supply and set the two values. 

2. 

Fan Control:

 Fan should have option to run continuously 

at low speed (Fan Low (E17)) (say 25–30% of max 

design airflow) during occupied and dead band for 

delivery outside air from suite HRV or OA vent duct 
If there is a call for heating or cooling the fan would ramp 

up to maximum design airflow for the FCU on the project. 

3. 

Fan Mode:

 By pressing FAN button to toggle AUTO icon 

ON and OFF to represent Auto Mode (“AUTO” show on 

screen) and Continuous Mode. Continuous Mode will 

keep fan running at pre-set minimum speed all time while 

Auto Mode will run from 0%. During dead band, Auto 

Mode will stop the fan while Continuous Mode will run 

the fan at low speed as set in (Fan Low (E17)). 
By pressing POWER button it will switch ON/OFF fan 

and heating/cooling outputs to their default positions.

Figure 16: Fan Control Diagram     

Special Notes

1.  Fan bar will be shown according to the fan output when 

reaches low speed, medium speed or 100% of max 

output. 

2.  ESI (Energy Saving Input) Contact status — When  the 

contact is activated (Vacation or Room unoccupied), 

a “Moon (

MODE

)” icon will be shown on the LCD and the 

thermostat will change the set point temperatures to 

Cooling & Heating to be ESIC & ESIH (refer to Engineer 

table for details).When the contact is deactivated (Open) 

(Room will be back to be occupied), it will set the set 

point values back to normal. 

3.  The icon 

MODE

MODE

MODE

, or 

MODE

 will be shown on LCD 

while the programmable Schedule 1, 2, 3, or 4 is running. 

4.  If “MODE” button is pressed, there are three Schedule 

modes “RUN, HALT, and STOP” for selection: 

a. 

RUN

 mode means Running on Schedules. And at 

the same time an icon (

MODE

) will be steadily shown 

on the LCD. 

b. 

HALT

 mode means temporarily using manual S.P 

instead of “current” Schedule. And the icon (

MODE

will be flashing on the LCD. 

c. 

STOP

 mode means using manual S.P instead 

of “all” Schedules. i.e. Temporarily disable all 

programmable Schedules. And the icon (

MODE

) will 

NOT be shown on the LCD. 

Examples of Engineering Mode: 

5.  E19 There is an adjustable time delay between heating 

and cooling from 0 to 5 minutes.This delay time can be 

adjusted by the “dLAy” parameter in the Engineer table. 

The default is set to 0 minutes. This feature can be used 

in addition to dead band for thermoelectric (Wax) control 

valve actuators that have long 3 minute travel time to 

prevent overlapping. 

6.  Proportional band “Pb” or (Stage Width) set in E12, 

Integral Time “I-t” set in E4, Dead band offset “db” 

set in E1.

7.  E22 Dead Band option “dbOP”parameter set to 0 will 

offset Heating from set point by db setting example 2 ºC 

and starts Cooling at the set point Parameter set to 1 will 

offset heating and cooling from the set point equally in 

total db set example 2 ºC (1 ºC heating and 1ºC cooling) 

8.  E20 “dirC” Cooling set to 0 for Normally Open Valve set 

to 1 for Normally Closed valve. 

9.  E21 “dirH” Heating set to 0 for Normally Open Valve set 

to 1 for Normally Closed valve. T and other parameters.

Summary of Contents for OptiLine FSG

Page 1: ...Installation Operation and Maintenance IM 1272 Group Fan Coils Part Number 910243712 Date July 2018 OptiLine Vertical Stack Fan Coil Model FSG...

Page 2: ...Receiving Inspection 4 Installation 5 Installation of Units with Risers Attached 5 Maintenance 7 Operating Instructions 8 Standard Thermostat Digital Programmable Thermostat 8 Adjusting the Maximum CF...

Page 3: ...Provide adequate combustion and ventilation air to the unit space as specified in the combustion and ventilation air section of these instructions WARNING Install this unit only in a location and pos...

Page 4: ...rocedure It is stressed that the component manufacturer s recommended procedures be strictly followed Thermostats and other accessories which have been shipped separately should be inspected for trans...

Page 5: ...fittings must be checked prior to pressure testing the system by the contractor as part of the installation procedure Mechanical fittings can loosen during transportation and handling If contractor in...

Page 6: ...ian must carry out the work The junction box is located behind the fan motor shield Electrical power to the unit should be disconnected by opening the remote disconnect device prior to removing the fa...

Page 7: ...the grille panel Grasp the bottom edge of the door and sharply pull the door forwards Lift the door to the horizontal position The filter is now accessible and is removed by sliding it upwards out of...

Page 8: ...al to a 0 10VDC Adjusting the Maximum CFM WARNING If the maximum CFM is adjusted to a value above the design airflow excessive air noise could occur The maximum CFM is factory set to the closest nomin...

Page 9: ...e than 100 F the A2 aquastat energizes the control valve If the water drops below 75 F the aquastat de energizes the control valve and energizes the electric heat relay The A2 aquatat has black yellow...

Page 10: ...d there is supply voltage to the fan motor replace the fan assembly If the system is change over or has auxiliary electric there check the voltage at the aquastats If no voltage is present at BLK or Y...

Page 11: ...r free and proper fan rotation Record electrical supply voltage and amperage Check all wiring for secure connections Close all unit isolation valves Flush water systems Open all isolation valves after...

Page 12: ...1 2 TB1 1 2 5 6 YEL BLK QC3 5 8 2 1 QC3 BLK BLK BLK BLK BLK N L L2 L1 MAX FUSE 15 AMPS SYM Description DISC SWITCH 1 POLE 120 277V 30A XMR1 TRANSFORMER 120 208 240 277 TO 24V 40VA CLASS 2 F1 FUSE 250V...

Page 13: ...12 AMPS BLK BLK BLK 2 1 BLK BLK L2 L1 TB1 1 2 5 6 YEL BLK QC3 5 8 2 1 QC3 L1 L2 SYM Description DISC SWITCH 2 POLE 120 277V 30A XMR1 TRANSFORMER 120 208 240 277 TO 24V 40VA CLASS 2 M1 MOTOR 208V 1 10...

Page 14: ...LD 22AWG 2 COND SHIELD AC DC SHIELDED WIRE GND L N QC3 QC3 2 M1 L2 GND SYM Description DISC SWITCH 1 POLE 120 277V 15A XMR1 TRANSFORMER 120 208 240 277 TO 24V 40VA CLASS 2 M1 EBM MOTOR 120V 1 5 HP CVA...

Page 15: ...WIRE N GND NC GND 1 8 AMPS FAN MOTOR QC3 M1 2 QC3 SYM Description DISC SWITCH 1 POLE 120 277V 15A XMR1 TRANSFORMER 120 208 240 277 TO 24V 40VA CLASS 2 M1 MOTOR 208 277 2 3 HP QC3 9 PIN QUICK CONNECT...

Page 16: ...rn ON OFF thermostat 7 Set point icons Display set point temperature while it is flashing 8 Fan icons Indicate Fan status 9 Flake icon Indicate working in Cooling mode 10 Hot spring icon Indicate work...

Page 17: ...uit of the controller Mounting front cover Lock front cover on the backplate by tightening the cover screw underneath with Philip screwdriver Wiring Example 1 All wires must be inserted above the reta...

Page 18: ...cription Remarks 1 Normal Display Display current room or set point temperature and current time day Setting SP parameter in engineer table to choose current room or set point temperature 2 Temperatur...

Page 19: ...d com 19 IM 1272 OPTILINE VERTICAL FAN COILS Figure 10 User Mode Operation Sequence Figure 11 Overview for the Settings of Clock and Programmable Schedules MODE Press MODE FAN or POWER button to escap...

Page 20: ...IM 1272 OPTILINE VERTICAL FAN COILS 20 www DaikinApplied com Addendum Figure 12 Detailed State Diagram for Clock Setting...

Page 21: ...13 Detailed State Diagram for Schedule Setting Press Mode button to select day shows steadily deselect day flash Press MODE button to toggle Cooling Heating Set points Press MODE button to toggle Cool...

Page 22: ...0 8 00 8 00 8 00 8 00 60 F 60 F 60 F 60 F 60 F 60 F 60 F Sch 3 MODE 18 00 18 00 18 00 18 00 18 00 18 00 18 00 70 F 70 F 70 F 70 F 70 F 70 F 70 F Sch 4 MODE 22 00 22 00 22 00 22 00 22 00 22 00 22 00 60...

Page 23: ...LS Control Actions ON OFF Valve Controls When Cooling or Heating is on a Running Gear MODE icon will be shown on the LCD Figure 14 Cooling and Heating Control Auto Changeover Dead band Option 0 Figure...

Page 24: ...o be ESIC ESIH refer to Engineer table for details When the contact is deactivated Open Room will be back to be occupied it will set the set point values back to normal 3 The icon MODE MODE MODE or MO...

Page 25: ...ter into engineer mode 2 Press UP or DOWN button to rotate the menu item and press MODE button to enter into the item 3 Press UP or DOWN button to change the setting and press MODE button to confirm t...

Page 26: ...0 10 0 10 0 0 0 18 0 18 0 0 1 C F E12 Pb Proportional Band or Stage Width 2 0 0 10 0 3 6 0 18 0 0 1 C F E13 LOC Bit Definition Bit 0 Mode Button 1 Down Buttons 2 Up Button 3 Fan Button 4 Power Button...

Page 27: ...F Type Step Default Range Default Range E21 dirH Heating Valve N C N O Setting 1 0 1 0 0 1 0 N O 1 N C E22 dbOP Dead band Options 1 0 1 1 0 1 0 DB is aligned to Cooling SP 1 SP is in the middle of DB...

Page 28: ...t to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Applied Representative for warranty details To find your local Daikin Applied Representative...

Reviews: