IM 1272 • OPTILINE VERTICAL FAN COILS 22 www.DaikinApplied.com
Addendum
Table 6: DefaultSetPointforProgrammableSchedules
COOL
SUN
MON
TUE
WED
THU
FRI
SAT
Sch.1
MODE
6:00
6:00
6:00
6:00
6:00
6:00
6:00
78°F
78°F
78°F
78°F
78°F
78°F
78°F
Sch. 2
MODE
8:00
8:00
8:00
8:00
8:00
8:00
8:00
85°F
85°F
85°F
85°F
85°F
85°F
85°F
Sch. 3
MODE
18:00
18:00
18:00
18:00
18:00
18:00
18:00
78°F
78°F
78°F
78°F
78°F
78°F
78°F
Sch. 4
MODE
22:00
22:00
22:00
22:00
22:00
22:00
22:00
78°F
78°F
78°F
78°F
78°F
78°F
78°F
HEAT
SUN
MON
TUE
WED
THU
FRI
SAT
Sch.1
MODE
6:00
6:00
6:00
6:00
6:00
6:00
6:00
70°F
70°F
70°F
70°F
70°F
70°F
70°F
Sch. 2
MODE
8:00
8:00
8:00
8:00
8:00
8:00
8:00
60°F
60°F
60°F
60°F
60°F
60°F
60°F
Sch. 3
MODE
18:00
18:00
18:00
18:00
18:00
18:00
18:00
70°F
70°F
70°F
70°F
70°F
70°F
70°F
Sch. 4
MODE
22:00
22:00
22:00
22:00
22:00
22:00
22:00
60°F
60°F
60°F
60°F
60°F
60°F
60°F
•
Unoccupied Set Points:
activated by occupancy
contact; Cooling: 82ºF/ Heating: 60ºF for factory defaults.
And These two can be re-set by ESIC(E2) and ESIH(E3)
parameters in Engineer Mode table.
• When
schedules are activated,
refer to cooling/ heating
set points according to current schedule.
• When
pause or stop schedules,
refer to manual set
point or latest set point as cooling set point and dead
band for heating set point deviation.
• Programmable Cooling Set Point range:
50ºF ~ 98ºF;
Programmable
Heating Set Point range:
40ºF ~ 90ºF
;
make sure to set heating lower than cooling set point to
have proper controls.