background image

 

O-UC12-FEB23-3 

Page 2 

Figure 1: Minimum Wall Distance and Drain Trap 

 

 

Field piping 

 

Use of incorrect pipe sizes affects the system’s

 

oil return and pressure drops. Refer 
information given on 

Page 3

. All local codes of 

practice must be observed in the installation of 
refrigerant piping. 

 

To ensure satisfactory operation and performance, the 
following points should be noted for field piping 
arrangements: 

 

Pipework routes must be as simple and as short as 
possible. 

 

Use of incorrect pipe sizes can affect system 
pressures/temperatures and gas velocity for proper oil 
return. 

 

Avoid low points on pipework where oil can accumulate. 

 

Use only clean, dehydrated refrigeration grade copper 
tube with long radius bends. 

 

When brazing use only silver alloy rods. 

 

Run braze without over filling to ensure there is no 
leakage into the tube. 

 

To prevent oxidization, blow oxygen free nitrogen 
through pipework when brazing. 

 

Protect the casing of the unit when brazing connections. 

 

Install insulation with a minimum wall thickness of 3/8” on 

suction lines to prevent sweating and ensure only 
superheated vapor is returned to compressor suction. 

 

Adequately support all pipe work at a maximum of 2-
meter intervals. 
 

Pressure testing 

 

The unit cooler has been pressure tested in the factory 
prior to dispatch. The indoor unit contains a holding 
charge of oxygen free nitrogen. 

 

 

Once the pipework installation is complete, it should be 
pressure tested prior to evacuation to test for leaks. 

 

A pressure leak test should be carried out using oxygen 
free nitrogen (OFN). NEVER USE OXYGEN FOR 
PRESSURE TESTING SYSTEMS. A calibrated nitrogen 
pressure regulator must always be used. Before starting 
any pressure testing, ensure the area surrounding the 
system is safe, inform relevant personnel and fit warning 
signs indicating high pressure testing. Also, use correct 
PPE as required. 

 

A simple procedure for testing as follows: 

 

Connect a pressure hose from the regulator to the 
schrader connection on the service port of the unit. 

 

Pressure system slowly up to 3 bar (45 psi) for 5 minutes 
and check for any signs of leakage. 

 

Increase pressure slowly up to 10 bar (150 psi) for 5 
minutes and check for any signs of leakage. 

 

Increase pressure slowly up to 20 bar (300 psi) and 
check for any signs of leakage. Leave system under 
pressure for 24 hours. 

Summary of Contents for O-UC12-FEB23-3

Page 1: ...3 Low Temperature Scan below QR code to download latest manual from Website https drm daikinmalaysia com download AIR COOLED COMMERCIAL REFRIGERATION SLIM UNIT COOLER INSTALLATION MAINTENANCE IOM NO O...

Page 2: ...task in question SAFETY SYMBOLS The following symbols are used in this document to alert the reader to specific situations WARNING Warning Risk of serious injury or death to person CAUTION Caution Da...

Page 3: ...Wave with fins spacing 5mm copper bare tubes with nominal diameter of 10mm This fins pattern stands out for better performance of air flow and heat transfer Superheat measurement air tightness test a...

Page 4: ...mm 12 7 12 7 Nominal capacities are rated in accordance with EN 328 SC3 wet coil condition for R404A with TD 7K Sound Pressure Level is measured at 1m away from every side of the unit and 1m below fa...

Page 5: ...0 95 1 1 LFSLHS0300AXV1 1 1 1 0 95 1 1 TD Correction Factor To calculate cooling capacity for different temperature difference multiply the cooling capacity obtained from section 2 2 2 with respectiv...

Page 6: ...e identified and operatives have suitable PPE Ensure the working area has adequate ventilation during brazing procedures The units contain moving machinery and electrical power hazards which may cause...

Page 7: ...ting and ensure only superheated vapor is returned to compressor suction Adequately support all pipe work at a maximum of 2 meter intervals Pressure testing The unit cooler has been pressure tested in...

Page 8: ...the drain fitting MUST be fitted the right way around otherwise it will not tighten against the drip tray One side of the nut has an angled recess this must be facing towards the drip tray The fittin...

Page 9: ...with longer length as shown in below diagram Cable type and sizing must be selected for the application and the electrical installation should conform to the current local standards The power cable to...

Page 10: ...y in room Limit access to cold room do not keep doors open during stocking Accumulation of ice or water in drain pan Drain line plugged Clean drain line Make sure drain line is insulated properly Drai...

Page 11: ...O UC12 FEB23 3 Page 2 Wiring Diagram LFSLHS0200AXV1 LFSLHS0300AXV1...

Page 12: ...ON MALAYSIA SDN BHD 34543 W Shah Alam Plant 11A Jalan Utas 15 7 Seksyen 15 40200 Shah Alam Selangor Malaysia Banting Plant Lot 10 Jalan Perusahaan 8 Kawasan Perusahaan Pekan Banting 42700 Banting Sela...

Reviews: