IOM 1264-1 • NAVIGATOR
®
MODEL WWV CHILLERS
24 www.DaikinApplied.com
C
onTroller
o
peraTIon
Dynamic Set Point Ranges
The following settings have different ranges of adjustment based on other settings.
Table 21: Cool LWT and Network Cool Set Point Ranges
Available Mode Selection
Range
Cool, Test
40 to 68°F (4.44 to 20.0°C)
Cool w/Glycol, Cool/Ice w/Glycol,
Ice w/Glycol
25 to 68°F (-3.89 to 20.0°C)
Table 22: Evaporator and Condenser Fluid Freeze Set
Point Ranges
Available Mode Selection
Range
Cool, Test
35.6 to 42.8°F (2 to 6°C)
Cool w/Glycol, Cool/Ice w/Glycol, Ice
w/Glycol
-0.4 to 42.8°F (-18 to 6°C)
Table 23: Low Evaporator Pressure Hold and Unload
Available Mode Selection
Range
Cool - Pressure Unload
27.8 to 45 psi (191.6 to 310 kPa)
Cool w/Glycol, Cool/Ice w/
Glycol, Ice w/Glycol - Pressure
Unload
0 to 45 psi (0 to 310 kPa)
Circuit Level Set Points
The settings in this section all exist for each individual circuit.
Table 24: Set Points for Individual Circuits
Description
Default
Range
Mode, Enabling, Configuration
Circuit mode
Enable
Disable, Enable, Test
Capacity Control
Auto
Auto, Manual
Manual Speed
See below
See below
VR Control
Auto
Auto, Manual
Manual VR
See below
1.6, 1.8, 2.4, 3.1
The Manual Speed setting value will follow the target speed while Capacity Control = Auto. When Capacity Control is set to ManSpd, the Manual
Speed set point can be set to the desired value. The minimum will be the same minimum speed calculated for automatic control. The maximum
value is equal to the Compressor Maximum Speed setting.
The Manual VR setting value will follow the target capacity while VR Control = Auto. When VR Control is set to Manual, the Manual VR set point
can be set to the desired value.
Sensor Offsets
Evaporator Pressure Offset
0 psi (0 kPa)
-14.5 to 14.5 psi (-100 to 100 kPa)
Condenser Pressure Offset
0 psi (0 kPa)
-14.5 to 14.5 psi (-100 to 100 kPa)
Oil Pressure Offset
0 psi (0 kPa)
-14.5 to 14.5 psi (-100 to 100 kPa)
Suction Temperature Offset
0°F (0°C)
-9.0 to 9.0°F (-5.0 to 5.0°C)
Discharge Temperature Offset
0°F (0°C)
-9.0 to 9.0°F (-5.0 to 5.0°C)
Liquid Temperature Offset
0°F (0°C)
-9.0 to 9.0°F (-5.0 to 5.0°C)
Administrative and Service Support
Clear Cycle Timers
Off
Off, On
Service Pumpdown
Off
Off, On
Compressor Run Hours
0
0 to 999999 hours
Compressor Starts
0
0 to 65535
Event Log - Event Selection
Low Pressure Hold
Low Press Hold, Low Press Unload, High Press Hold, High Press
Unload, High Motor Amps Hold, High Motor Amps Unload,
Event Log - Day Selection
Current
Current, 2nd Day, 3rd Day, 4th Day, 5th Day, 6th Day, 7th Day
Circuit Test Mode Set Points
Circuit test mode set points can be changed when either the
unit mode is Test, or the circuit mode is Test. When neither the
unit nor the circuit are in Test mode, all the circuit test mode set
points for the circuit are automatically changed back to their
‘off’ values.
Description
Default
Range
Test Oil Feed Solenoid Output
Off
Off, On
Test VR 1.8 Output
Off
Off, On
Test VR 2.4 Output
Off
Off, On
Test VR 3.1 Output
Off
Off, On
Test EXV Position
0.0%
0.0 to 100.0%