IOM 1264-1 • NAVIGATOR
®
MODEL WWV CHILLERS
22 www.DaikinApplied.com
C
onTroller
o
peraTIon
Tower Control
Tower Control
None
None, Condenser EWT, Condenser LWT
Number of Tower Fan Stages
1
1, 2
Tower Fan Stage 1 On Temperature
70°F (21.11°C)
66.2 to 120°F (19 to 48.89°C)
Tower Fan Stage 2 On Temperature
75°F (23.89°C)
66.2 to 120°F (19 to 48.89°C)
Tower Fan Stage Off Differential
3°F (1.67°C)
1 to 10.0°F (0.56 to 5.56°C)
Tower Fan Stage On Delay
2 minutes
1 to 60 minutes
Tower Fan Stage Off Delay
5 minutes
1 to 60 minutes
Tower Fan Stage On Position/Speed
80%
0 to 100%
Tower Fan Stage Off Position/Speed
30%
0 to 100%
Valve/VFD Control Configuration
None
None, Valve Set Point, Valve Stage, VFD Stage, Valve SP/VFD
Stage
Valve Type
NC to Tower
NC to Tower, NO to Tower
Valve/VFD Set Point
18.33°C (65°F)
15.56 to 48.89°C (60 to 120°F)
Minimum Valve Position
10%
0 to 100%
Maximum Valve Position
90%
0 to 100%
Minimum VFD Speed
25%
0 to 100%
Maximum VFD Speed
100%
0 to 100%
Valve PID Proportional Gain Factor
1.0
0 to 100
Valve PID Integral Time
2.0 minutes
0 to 100 minutes
VFD PID Proportional Factor
1.0
0 to 100
VFD PID Integral Time
2.0 minutes
0 to 100 minutes
Unit Sensor Offsets
Evaporator LWT Senser Offset
0°F (0°C)
-9.0 to 9.0°F (-5.0 to 5.0°C)
Evaporator EWT Senser Offset
0°F (0°C)
-9.0 to 9.0°F (-5.0 to 5.0°C)
Condenser LWT Senser Offset
0°F (0°C)
-9.0 to 9.0°F (-5.0 to 5.0°C)
Condenser EWT Senser Offset
0°F (0°C)
-9.0 to 9.0°F (-5.0 to 5.0°C)
Circuit Configuration
Pumpdown Pressure
200.0 kPa (29.0 psi)
70 to 280 kPa (10.2 to 40.6 psi)
Pumpdown Time Limit
120 sec
0 to 180 sec
Start To Start Time Delay
15 min
15 to 60 minutes
Stop To Start Time Delay
3 min
3 to 20 minutes
Alarm and Limit Settings - Unit
Evaporator Fluid Freeze
36°F (2.2°C)
See section below
Evaporator Flow Loss Delay
15 sec
5 to 15 sec
Evaporator Recirculate Timeout
3 min
1 to 10 min
Condenser Fluid Freeze
36°F (2.2°C)
See section below
Condenser Flow Loss Delay
15 sec
5 to 15 sec
Condenser Recirculate Timeout
3 min
1 to 10 min
Alarm and Limit Settings - Circuits
Low Evap Pressure Unload
29.0 psi (200.0 kPa)
See below
Low Evap Pressure Hold Offset
2.2 psi (15 kPa)
1.5 to 7.3 psi (10 to 50 kPa)
High Oil Pressure Delay
30 sec
10-30 sec
High Oil Pressure Difference
36.3 psi (250 kPa)
0.0 to 60.2 psi (0.0 to 415.0 kPa)
High Discharge Temperature
230°F (110°C)
149 to 230°F (65 to 110°C)
High Condenser Pressure Hold Offset
2.7°F (1.5°C)
2.7 to 27°F (1.5 to 15°C) - Value forced to be at least 0.9°F (0.5°C)
greater than the High Condenser Pressure Unload Offset setting.
High Condenser Unload Offset
1.8°F (1.0°C)
1.8 to 25.2°F (1.0 to 14°C)