![background image](http://html1.mh-extra.com/html/daikin/multi-r32-split-series/multi-r32-split-series_installers-reference-manual_4701102040.webp)
7
|
Piping installation
Installer reference guide
40
4MWXM-A9
R32 Split series
4P708645-1 – 2022.09
7.2.8 To connect the refrigerant piping to the outdoor unit
▪
Piping length.
Keep field piping as short as possible.
▪
Piping protection.
Protect the field piping against physical damage.
1
Connect the liquid refrigerant connection from the indoor unit to the liquid
stop valve of the outdoor unit.
a1
b2
c1
b1
d1
d2
a2
To air-conditioning unit:
a1
Liquid stop valve
b1
Gas stop valve
c1
Liquid service port
d1
Gas service port
To DHW tank:
a2
Liquid stop valve
b2
Gas stop valve
d2
Gas service port
2
Connect the gas refrigerant connection from the indoor unit to the gas stop
valve of the outdoor unit.
NOTICE
It is recommended that the refrigerant piping between indoor and outdoor unit is
installed in a ducting or the refrigerant piping is wrapped with finishing tape.
7.3 Checking the refrigerant piping
7.3.1 About checking the refrigerant piping
The outdoor unit's
internal
refrigerant piping has been factory tested for leaks. You
only have to check the outdoor unit's
external
refrigerant piping.
Before checking the refrigerant piping
Make sure the refrigerant piping is connected between the outdoor unit and the
indoor unit.
Typical workflow
Checking the refrigerant piping typically consists of the following stages:
1
Checking for leaks in the refrigerant piping.
2
Performing vacuum drying to remove all moisture, air or nitrogen from the
refrigerant piping.
If there is a possibility of moisture being present in the refrigerant piping (for
example, water may have entered the piping), first carry out the vacuum drying
procedure below until all moisture has been removed.
Summary of Contents for Multi+ R32 Split Series
Page 1: ...Installer reference guide R32 Split series 4MWXM52A2V1B9...
Page 31: ...6 Unit installation Installer reference guide 31 4MWXM A9 R32 Split series 4P708645 1 2022 09...
Page 77: ......
Page 78: ......
Page 79: ......
Page 80: ...4P708645 1 2022 09 Copyright 2022 Daikin Verantwortung f r Energie und Umwelt...