background image

Outdoor Unit 

Purging Air And Checking Gas Leakage 

it, 

WARNING-------------------------

• Do not mix any substance other than the specified refrigerant (R32) into the refrigeration cycle. 
• When refrigerant gas leaks occur, ventilate the room as soon and as much as possible. 
• To prevent air pollution,  a vacuum pump should be used for air purging wherever possible. 

• If using additional  refrigerant,  perform air purging from the refrigerant pipes and 

indoor unit using a vacuum pump, then  charge additional refrigerant. 

• Use a hexagonal wrench to operate the  stop valve rod.
• All refrigerant pipe joints should be tightened with a torque wrench at the

specified tightening torque. 

1) Connect projection side (on which pin is pressed) of charging hose (which comes from gauge 

manifold) to gas stop valve's service port. 

2)  Fully open gauge manifold's low-pressure valve (Lo) and completely close its high-pressure  valve (Hi). 

(High-pressure valve subsequently requires no operation.) 

3) Do vacuum pumping and make sure that the compound pressure gauge reads -0.1 MPa (-76cmHg) *1. 

4) Close gauge manifold's low-pressure valve (Lo) and stop vacuum pump. 

(Keep this state for a few minutes to make sure that the compound pressure gauge pointer does  not swing back.) *2. 

5)  Remove valve cap from liquid stop value and gas stop valve. 

6)  Tum the liquid stop valve's rod 90 degrees counterclockwise with a hexagonal wrench to open valve.  Close it after 5 seconds, and check for gas leakage. 

Using soapy water,  check for gas leakage from indoor unit's flare and outdoor unit's flare and valve rods. 

After the check is complete, wipe all soapy water off. 

7) Disconnect charging hose from gas stop valve's service port, then fully open liquid and gas stop valves.  (Do not attempt to tum valve rod beyond its stop.) 

8) Tighten valve caps and service port caps for the liquid and gas stop valves with a torque wrench at the specified torques. 

•1. Pipe length vs. vacuum pump run time 

Pipe length  I Up to 1 Sm 

More than 1 Sm 

Run time 

Not less than 10 min.  I Not less than 15 min. 

•2.  If the compound pressure gauge pointer swings back, 

refrigerant may have water content or a loose pipe joint 

may exists.  Check all pipe joints and retighten nuts as 

needed, then repeat steps 2) through 4). 

Wiring 

• For inter-unit wires connections, see ( INDOOR UNIT). 

WIRING). 

Terminal 

� 

• When connecting the connection wires to the terminal block using a single core wire, be sure to perform curing. 

block 

· ' 

Problems with the work may cause heat and fires. 

--

� 

� 

� 

-

-� 

•  Regarding the interconnecting 

and power cables. 

it, 

WARNING ---

Never use short cables for 

connecting end of conductor to 

each other. 

;JI  Drain Work 

1) Use the@drain socket for drainage. 

�  � 

QGood 

XWrong 

Stripping wire at terminal block 

• Precaution to be taken for power supply wiring. 

• When using stranded wires, make sure to use a round crimp-style terminal for connection to 

the power supply terminal block. Place the round crimp-style terminals on the wires up to 
the covered part and secure in place. 

2) When attaching the@drain socket to the bottom frame, make sure the connect the drain hose to the drain socket first. 
3) If the drain port is covered by a mounting base or floor surface, place additional foot bases of at leaset 30mm in height under the outdoor unit's feet. 
4) In cold areas, do not use a drain hose with outdoor unit. (Drain water may freeze. impairing heating performance.) 

Roundcrimp­

styleterminal 

Stranded wire 

m--Dralnport 

..r 

�=<•=•� 

®Drainsocket

j

�"!':��:'�:1'!��y, 

10 

Summary of Contents for MTKY50UV16V3A

Page 1: ...DAIKIN 3P665364 8T M22P098B DAIKIN ROOM AIR CONDITIONER OPERATION MANUAIL INVERTER MODELS A D F G MTKY50UV16V3A 3P665364 8 T M22P098B...

Page 2: ...quality and or longevity of the object concerned Do not expose plants or animals directly to the airflow from the unit as this may cause adverse effects Do not place appliances that produce nakedflame...

Page 3: ...es 11 Signal receiver Receives signals from the remote controller When the unit receives a signal you will hear a beep sound Case Sound type Operation start beep beep Settings changed Operation stop 1...

Page 4: ...n Cancels the timer setting 12 ONTIMER button 13 OFFTIMER button 14 GOOD SLEEP DISPLAY button 15 DEW CLEAN button Features avallable with selected models NOTE Notes on remote controller fJ _ 1 B 2 7 c...

Page 5: ...get it wet The maximum transmission distance is about 7m 4 Y Receiver To attach the accessory filters Set the accessory filters under the tabs of the filter frame on the indoor unit When attaching th...

Page 6: ...m the remote the default set temperature will be set as mentioned in below table Mode Set temperature before remote switched OFF Set temperature after remote switched ON Cool If set temperature 24 C D...

Page 7: ...he CHILD LOCK disables all the buttons except the CHILD LOCK button This function prevents children from operating the remote controller by mistake To set the CHILD LOCK Press and together for about 5...

Page 8: ...the LCD The flaps horizontal blades will begin to swing To set the flaps at desired position This function is effective while the flaps are in auto swing mode Press i lswiN when the flaps reach the de...

Page 9: ...gain disappears from the LCD Notes on ECONO operation ECONO operation can only be set when the unit is running Pressing t 1 causes the settings to be cancelled and disappears from the LCD ECONO operat...

Page 10: ...F and the stop lime default 2HR are displayed on the LCD ON OFF c J The TIMER lamp lights orange 0 1 TEMP ISP ay 2 Press v while C is blinking Each pressing of the button changes tempera ture shift va...

Page 11: ...Dry mode OFF Cooling operation To cancel DEW CLEAN operation Turn OFF the machine from Remote Controller Wi Fi Control NOTE Note on LED Brightness Control Ld indicates the brightness light feature wh...

Page 12: ...ward you to disengage one of the front panel shafts 2 Disengage the front panel shaft on the other side in the same manner 3 After disengaging both front panel shafts pull the front panel toward yours...

Page 13: ...he filters into slots of the front grille Close the front panel slowly and push the panel at the 3 points I Accessory filter I Filter type Ag ion filter Micro filter PM 2 5 Maintenance The accessory f...

Page 14: ...lter 1 set Ag ion filter 1 set Anti Microbial filter 1 set Micro filter PM2 5 1 set l Operation with dirty filters 1 cannot deodorise the air 3 results in poor cooling Part No KAF970A45 KAF057A41 KAF5...

Page 15: ...tuations It automatically resumes operation in about 3 minutes Voltage range protection 130V 285V A sound is heard A sound like flowing water This sound is generated because the refrigerant in the air...

Page 16: ...been tripped or the fuse blown operate Is there a power failure OPERATION lamp is off Are batteries set in the remote controller Is the timer setting correct The room does not cool down Is the airflo...

Page 17: ...er and call your service centre The air conditioner automatically resumes operation in about 3 minutes You should just wait for a while If there is a risk lightning could strike in the neighbourhood s...

Page 18: ...7 DC FAN MOTOR FAULT EB OVERCURRENT INPUT F3 HIGH TEMPERATURE DISCHARGE PIPE CONTROL F6 HIGH PRESSURE CONTROL IN COOLING FB OPERATION HALT DUE TO COMPRESSOR INTERNAL TEMPERATURE ABNORMALITY OUTDOOR HO...

Page 19: ......

Page 20: ......

Page 21: ...re installed securely Fall vibration noise No refrigerant gas leaks Incomplete cooling function Refrigerant gas and liquid pipes and indoor drain hose Water leakage extension are thermally insulated D...

Page 22: ...charging hose from gas stop valve sservice port then fullyopenliquidandgas stopvalves Do not attempt to tum valve rod beyond its stop 8 Tighten valve caps and service port caps for the liquid and gas...

Page 23: ...333 407 kgf cm 220 280 kgf cm Gas side 0 D 12 7mm 49 5 60 3N m 48 1 59 7N m 505 615 kgf cm 0 D 15 9mm 61 8 75 4N m 490 610 kgf cm I 10 8 14 7N m 110 150 kgf cm 630 770 kgf cm 14 2 17 2N m 21 6 27 4N m...

Page 24: ...condensation or water dripping f Heat insulationpipe cover Slit 1111q11111J Slit Vinyl tape This illustration shows the case of the left rear piping Sectional view wire Insulation tape Overwrap more t...

Page 25: ...if wire is not included with the unit A TableNo 6 Llc WARNING Use a stabiliser if required by the voltage supply condition Oo not use tapped wires extension cords or starburst connections as they may...

Page 26: ...s the bottom frameof theindoorunit with bothhands to set it on the A mountingplatehooks Makesure the wire lead do notcatchon the edge of the indoorunit 9 Securethe indoorunit to the A mountingplatewit...

Page 27: ...ntionspols 7spats1nall 1100 Liquid pipe end Gaspipeend Drainhose position Applicable Unit Size Type H X W X D A B C i 298 X 800 X 229 800 116 5 116 5 0 298 X 821 X 235 821 128 126 5 298 X 885 X 229 88...

Page 28: ...tions When there is no work space because the unit is close to ceiling Upper hook CAUTION 1 Push up Be sure to wear protection gloves Place both hands under the centre of the front grille and while pu...

Page 29: ...avoid noise from the outdoor unit and vibration Mechanical noise and vibration may occur depending on how the unit is installed and the environment in which it is used Dimensions of ODU installation...

Page 30: ...nit may cause interference with the picture or sound 9 the unit can be installed at the recommended height 1 8m 10 no laundry equipment is nearby fflGl l li11 114 The outdoor unit should be positioned...

Page 31: ...gas leaks during installation ventilate the area immediately 0 Toxic gas may be produced if the refrigerant comes into contact with fire After completing installation check for refrigerant gas leakag...

Page 32: ...DAIKIN 3P665364 8T M22P099A DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL MODELS A D F G MTKY50UV16V3A C JNVERTER 3P665364 8T M22P099A...

Reviews: