Safety Precautions 

• The precautions described herein are classified as WARNING and CAUTION. They both contain important 

information regarding safety.  Be sure to observe all precautions without fail. 

• Meaning of WARNING and CAUTION notices 

� WARNING 

Failure lo follow these instructions properly may result in personal injury or loss of life. 

� CAUTION 

Failure to observe these instructions properly may result in property damage or personal injury, which may be serious depending on the circumstances. 

• The safety marks shown in this manual have the following meanings: 

I  Be sure to follow the instructions. 

Be sure to establish an earth connection. 

(S) 

Never attempt. 

• After completing installation, conduct a trial operation to check for faults and explain to the customer how to 

operate the air conditioner and take care of it with the aid of the operation manual. 

�  WARNING 

• Ask your dealer or qualified personnel to carry out installation work. 

Do not attempt to install the air conditioner yourself.  Improper installation may result in water leakage, electric shocks  or fire. 

• Install the air conditioner in accordance with the instructions in this installation manual. Improper installation may result in water leakage, electnc shocks or Ire. 

•  Be sure to use only the specified accessories and parts for installation work. Failure to use the specified parts may result in the unit falYng, water leakage, electric shocks or fre. 

• Install the air conditioner on a foundation strong enough to withstand the weight of the unit. A foundabon of osufficient streng� may result•�, equipment falling and causog oju�. 

• Electrical work must be perfonmed in accordance with relevant local and national regulations and with instructions in this installation manual. 

Be sure to use a dedicated power supply circuit  only.  Insufficiency of power circuit capacity and improper workmanship may result in electric shocks or fire. 

•  Use a  cable of suitable  length.  Do not use tapped wires or an extension lead, as this may cause overheating, electric shocks or fire. 

• Make sure that all wiring is secured, the specified wires are used, and that there is no strain on the terminal 

connections or wires.  Improper connections or securing of wires may result in abnormal heat build-up or fire. 

• When wiring the power supply and connecting the wiring between the indoor and outdoor units, position the wires so that the 

control box lid can  be  securely fastened.  Improper positioning of the control box lid may result in electric shocks, fire or over heating terminals. 

• If refrigerant gas leaks  during installation,  ventilate the area immediately. 

0

Toxic gas may be produced if the refrigerant comes into contact with fire. 

• After completing installation, check for refrigerant gas leakage. Toxic gas may be produced if the refngerant gas 

0

leaks into the room and comes into contact with a source of fire, such as a fan heater, stove or cooker. 

• When installing or relocating the air conditioner, be sure to bleed the refrigerant circuit to ensure ii is free of air, and use only the specified 

refrigerant (R32). The presence of air or other foreign matter in the refrigerant circuit causes abnormal pressure rise, which may result in equipment damage and even injury. 

•  During installation, attach the refrigerant piping securely before running the compressor. If the refrigerant pipes are not attached and the stop

valve is open when the compressor is run, air will be sucked in, causing abnormal pressure in the refrigeration cycle, which may result in equipment damage and even injury. 

•  During pump-down, stop the compressor  before removing the refrigerant piping. If the compressor is stil running and the stop valve is open during pump-down, 

air will be sucked in when the refrigerant piping is removed, causing abnormal pressure in the refrigeration cycle, which may result in equipment damage and even injury. 

• Be sure to earth the air conditioner. 

0

Do not earth the unit to a utility pipe,  lightning conductor or telephone earth lead.  Imperfect earthing may result in electric shocks. 

•  Be sure to  install an earth leakage circuit breaker.  Failure to install an earth leakage circuit breaker may result in electric shocks or fire. 

• Do not pump down when the refrigerant has leaked,  otherwise the compressor may be damaged. 

�  CAUTION 

• Do not install the air conditioner at any place where there is a danger of flammable gas leakage. 

(S) 

In the event of a gas leakage, build-up of gas near the air conditioner may cause a fire to break out. 

• While following the instructions in this installation manual, install drain piping to ensure proper drainage and insulate 

piping to  prevent  condensation.  Improper drain piping may result in indoor water leakage and property damage. 

• Tighten the flare nut acoording to the specified method such as with a torque wrench. lflhe flare nut is too tight. it may crack after prolonged use, causing refngerant leakage. 
• Take adequate steps to prevent the outdoor unit being used as a sheller by small animals. 

Small animals making contact with electrical parts can cause malfunctions, smoke or fire.  Please instruct the customer to keep the area around the unit clean. 

• The temperature of refrigerant circuit will be high, please keep the inter-unit wires away from copper pipes that are not lhenmally insulated. 

Summary of Contents for MTKY50UV16V3A

Page 1: ...DAIKIN 3P665364 8T M22P098B DAIKIN ROOM AIR CONDITIONER OPERATION MANUAIL INVERTER MODELS A D F G MTKY50UV16V3A 3P665364 8 T M22P098B...

Page 2: ...quality and or longevity of the object concerned Do not expose plants or animals directly to the airflow from the unit as this may cause adverse effects Do not place appliances that produce nakedflame...

Page 3: ...es 11 Signal receiver Receives signals from the remote controller When the unit receives a signal you will hear a beep sound Case Sound type Operation start beep beep Settings changed Operation stop 1...

Page 4: ...n Cancels the timer setting 12 ONTIMER button 13 OFFTIMER button 14 GOOD SLEEP DISPLAY button 15 DEW CLEAN button Features avallable with selected models NOTE Notes on remote controller fJ _ 1 B 2 7 c...

Page 5: ...get it wet The maximum transmission distance is about 7m 4 Y Receiver To attach the accessory filters Set the accessory filters under the tabs of the filter frame on the indoor unit When attaching th...

Page 6: ...m the remote the default set temperature will be set as mentioned in below table Mode Set temperature before remote switched OFF Set temperature after remote switched ON Cool If set temperature 24 C D...

Page 7: ...he CHILD LOCK disables all the buttons except the CHILD LOCK button This function prevents children from operating the remote controller by mistake To set the CHILD LOCK Press and together for about 5...

Page 8: ...the LCD The flaps horizontal blades will begin to swing To set the flaps at desired position This function is effective while the flaps are in auto swing mode Press i lswiN when the flaps reach the de...

Page 9: ...gain disappears from the LCD Notes on ECONO operation ECONO operation can only be set when the unit is running Pressing t 1 causes the settings to be cancelled and disappears from the LCD ECONO operat...

Page 10: ...F and the stop lime default 2HR are displayed on the LCD ON OFF c J The TIMER lamp lights orange 0 1 TEMP ISP ay 2 Press v while C is blinking Each pressing of the button changes tempera ture shift va...

Page 11: ...Dry mode OFF Cooling operation To cancel DEW CLEAN operation Turn OFF the machine from Remote Controller Wi Fi Control NOTE Note on LED Brightness Control Ld indicates the brightness light feature wh...

Page 12: ...ward you to disengage one of the front panel shafts 2 Disengage the front panel shaft on the other side in the same manner 3 After disengaging both front panel shafts pull the front panel toward yours...

Page 13: ...he filters into slots of the front grille Close the front panel slowly and push the panel at the 3 points I Accessory filter I Filter type Ag ion filter Micro filter PM 2 5 Maintenance The accessory f...

Page 14: ...lter 1 set Ag ion filter 1 set Anti Microbial filter 1 set Micro filter PM2 5 1 set l Operation with dirty filters 1 cannot deodorise the air 3 results in poor cooling Part No KAF970A45 KAF057A41 KAF5...

Page 15: ...tuations It automatically resumes operation in about 3 minutes Voltage range protection 130V 285V A sound is heard A sound like flowing water This sound is generated because the refrigerant in the air...

Page 16: ...been tripped or the fuse blown operate Is there a power failure OPERATION lamp is off Are batteries set in the remote controller Is the timer setting correct The room does not cool down Is the airflo...

Page 17: ...er and call your service centre The air conditioner automatically resumes operation in about 3 minutes You should just wait for a while If there is a risk lightning could strike in the neighbourhood s...

Page 18: ...7 DC FAN MOTOR FAULT EB OVERCURRENT INPUT F3 HIGH TEMPERATURE DISCHARGE PIPE CONTROL F6 HIGH PRESSURE CONTROL IN COOLING FB OPERATION HALT DUE TO COMPRESSOR INTERNAL TEMPERATURE ABNORMALITY OUTDOOR HO...

Page 19: ......

Page 20: ......

Page 21: ...re installed securely Fall vibration noise No refrigerant gas leaks Incomplete cooling function Refrigerant gas and liquid pipes and indoor drain hose Water leakage extension are thermally insulated D...

Page 22: ...charging hose from gas stop valve sservice port then fullyopenliquidandgas stopvalves Do not attempt to tum valve rod beyond its stop 8 Tighten valve caps and service port caps for the liquid and gas...

Page 23: ...333 407 kgf cm 220 280 kgf cm Gas side 0 D 12 7mm 49 5 60 3N m 48 1 59 7N m 505 615 kgf cm 0 D 15 9mm 61 8 75 4N m 490 610 kgf cm I 10 8 14 7N m 110 150 kgf cm 630 770 kgf cm 14 2 17 2N m 21 6 27 4N m...

Page 24: ...condensation or water dripping f Heat insulationpipe cover Slit 1111q11111J Slit Vinyl tape This illustration shows the case of the left rear piping Sectional view wire Insulation tape Overwrap more t...

Page 25: ...if wire is not included with the unit A TableNo 6 Llc WARNING Use a stabiliser if required by the voltage supply condition Oo not use tapped wires extension cords or starburst connections as they may...

Page 26: ...s the bottom frameof theindoorunit with bothhands to set it on the A mountingplatehooks Makesure the wire lead do notcatchon the edge of the indoorunit 9 Securethe indoorunit to the A mountingplatewit...

Page 27: ...ntionspols 7spats1nall 1100 Liquid pipe end Gaspipeend Drainhose position Applicable Unit Size Type H X W X D A B C i 298 X 800 X 229 800 116 5 116 5 0 298 X 821 X 235 821 128 126 5 298 X 885 X 229 88...

Page 28: ...tions When there is no work space because the unit is close to ceiling Upper hook CAUTION 1 Push up Be sure to wear protection gloves Place both hands under the centre of the front grille and while pu...

Page 29: ...avoid noise from the outdoor unit and vibration Mechanical noise and vibration may occur depending on how the unit is installed and the environment in which it is used Dimensions of ODU installation...

Page 30: ...nit may cause interference with the picture or sound 9 the unit can be installed at the recommended height 1 8m 10 no laundry equipment is nearby fflGl l li11 114 The outdoor unit should be positioned...

Page 31: ...gas leaks during installation ventilate the area immediately 0 Toxic gas may be produced if the refrigerant comes into contact with fire After completing installation check for refrigerant gas leakag...