Controller Settings for Normal Operation
When all start-up procedures are completed, set the controls
and program the MicroTech III controller for normal operation.
Use the following list as a guide; some items may not apply to
your unit.
1 .
Set the heating and cooling parameters as required for
normal unit operation:
a .
Temperature \ Zone Cooling \
b .
Temperature \ Zone Heating \
c. Temperature \ Discharge Cooling \
2 .
Set the low ambient compressor lockout setpoint as
required. Do not set it below 20°F.
3 .
Set the high ambient heat lockout temperature setpoint.
4 .
Set the alarm limits as required.
5 .
Set the duct static pressure control parameters as required.
6 .
Set the building static pressure control parameters as
required.
7 .
Set the economizer control parameters as required.
8 .
Set the date and time in keypad menu.
9 .
Set the operating schedule as required using keypad
menus .
NOTE:
Unit operation may also be controlled by the building
automation system.
Maintaining Control Parameter Records
Daikin recommends that the MicroTech III controller’s setpoints
and parameters be recorded and saved for future reference.