Field Gas Heat Connections
The appliance must be isolated from the gas supply system by
closing off the manual shut off valve during any pressure testing
less than 0.5 psi (3.5 kPa) of the gas supply piping system.
The appliance and its individual shut-off valve must be
disconnected from the gas supply system during any pressure
testing greater than or equal to 0.5 psi (3.5 kPa).
Regulator to be sized for the maximum total Btu input required
for the heater(s).
Figure 24: Field Gas Heat Connections
Altitude Conversion
For elevations up to 2000 feet, rating plate input ratings apply.
For high altitudes (elevations over 2000 ft) contact Daikin
for part numbers. Or contact local
gas supplier to confirm gas heating value has been devalued
for applicable elevations.
Table 16: Furnace Identification for Altitude
Elevation (ft .)
Part Number
Natural Gas Fired Furnace with 50 MBH Burners
2000–2999
910166410
3000–3999
910166411
4000–4999
910166412
5000–5999
910166413
6000–6999
910166415
Natural Gas Fired Furnace with 45 MBH Burners
2000–2999
910166412
3000–3999
910166416
4000–4999
910166417
5000–5999
910166415
6000–6999
910166418
LPG Gas Fired Furnace with 50 MBH Burners
2000–2999
910166419
3000–3999
910166420
4000–4999
910166421
5000–5999
910166422
6000–6999
910166424
LPG Gas Fired Furnace with 45 MBH Burners
2000–2999
910166425
3000–3999
910166422
4000–4999
910166427
5000–5999
910166428
6000–6999
910166429
From Gas Meter
Unit Gas Supply
Connection*
Manual Gas
Shut-Off Valve
with 1/4" NPT
Test Plug
* Factory-supplied grommet must be utilized