Figure 103: Optional Outdoor Air Monitor
–
Set Up Menu
Press and release ↑/↓ during normal operation to select
IP/SI Units ↓
Set Up ↓↑
LCD1 U/M=FPM ↓
1
LCD1 U/M=FPM ↓
Set LCD1 Units?
Set Area1?
Set Out1 Units?
2
Set Out1?
Set FS1?
LCD1 U/M=CPM ↑
AR1=0.00SQF ↑
1
AR1=0.000 SQF ↓↑
OUT1 U/M=FPM ↓
1
OUT1 U/M=FPM ↓↑
2
OUT1=0–10V ↓
OUT1 U/M=CPM ↑
2
OUT1=0–5V ↓↑
FS1=5000FPM ↓↑
FS1=10000FPM for GF1
or
FS1=5000CFM ↓↑
FS1=10000CFM for GF1
1
FS1=5000FPM ↓↑
1
FS1=10000FPM for GF1
or
1
FS1=5000CFM ↓↑
1
FS1=10000CFM for GF1
2
OUT1=4–20mA ↑
1
OUT1=4-20mA ↓↑
:
System
Enter (Move →)
Esc (Normal Operation)
Enter (Move →)
Esc (Move ←)
Enter (Move →)
Esc (Move ←)
Enter (Action, Move →→)
Esc (Move ←←)
Visible only when LCD U/M=CFM
FS1 units determined by
OUT1 U/M setting
Displays airflow in FPM.
Outputs airflow in FPM.
In addition, “SW1” must be set
to the VDC position to change
airflow output to 0–10VDC.
In addition, “SW1” must be set
to the VDC position to change
airflow output to 0–5VDC.
In addition, “SW1” must be set to
the mA position to change airflow
output to 4–20mA.
Set area between
0.00 and 999.99 sq.ft. Area
affects the LCD display reading
and output when set for CFM.
Fullscale analog output value
from 100 to 15,000 for FPM
(up to 999,999 for CFM) in
increments of 1.
Value must be ≥ LL1 + 10 or, if
LL1=0, value must be ≥ 100.
Displays airflow in CFM (User
must input AR1 area.
Outputs airflow in CFM (User
must input AR1 area.
IM 1058-8 • MAVERICK II ROOFTOP SYSTEMS
130
www.DaikinApplied.com
a
PPendIx
– k
eyPad
/d
IsPlay
m
enU
s
TrUCTUre