background image

VFD Compressor Control

Control of the VFD compressor is accomplished with a digital 

output enable signal and a 0-10VDC analog modulating 

control signal.

General VFD Compressor Start Sequence

On a call for VFD compressor operation the VFD enable 

output is energized (on) and the 0-10VDC analog control 

signal is set to 3.33VDC (50 rps) for 10 seconds. During this 

10 second initial period the VFD compressor’s internal logic 

ramps the compressor to 50 rps to insure compressor startup oil 

lubrication. After 10 seconds the VFD compressor control signal 

begins modulation to maintain the cooling discharge set point.

NOTE: 

In addition to enabling VFD compressor operation 

the VFD enable output is used to energize the liquid 

line drop solenoid on the VFD circuit. (Only for Low 

Ambient Option)

Compressor Stage Up Transition

When the VFD compressor has been operating at maximum 

capacity for the cooling stage time period and there is a call 

for more cooling capacity the following transition sequence is 

followed when staging up.
During each fixed compressor stage UP sequence, the VFD 

compressor speed is reduced to its minimum, as a fixed speed 

compressor is turned on. Note that the VFD compressor 

speed range is extended for these staging points to assure 

smooth transition and to minimize capacity gaps. Typically, the 

VFD compressor is overdriven (higher speed than normal full 

load rating speed) before staging up a fixed compressor. The 

VFD is held at minimum speed for 30 seconds before normal 

modulation resumes .

Compressor Stage Down Transition

When the VFD compressor has been operating at minimum 

capacity for the cooling stage time period and there is a call 

for less capacity the following transition sequence is followed 

when staging down.
During each fixed speed compressor stage DOWN sequence, 

the VFD compressor speed is increased to maximum speed 

(which varies with unit size and number of operating fixed 

compressors) as a fixed speed compressor is turned off. Note 

that the VFD compressor speed range has been extended 

for these staging points to assure smooth transition and to 

minimize capacity gaps. Typically, the VFD compressor will be 

overdriven (higher speed than normal full load rating speed) 

when staging down a fixed compressor.

Dehumidification Transition During 

Cooling State

When dehumidification operation becomes active while the 

unit is in the Cooling operating state, The VFD compressor 

is ramped to its maximum capacity. If the VFD capacity at 

this point is already above 75% of its full modulation a fixed 

compressor is also turned on. The compressors are held at this 

capacity for 1 minute before normal modulation resumes, to 

maintain leaving coil temperature (LCT).

•  VFD compressor will load up completely before starting 

any fixed speed compressors to achieve LCT of 45F 

(default) with the VFD compressor option. LCT may be 

set between 45F to 52F.

•  If reheat signal is at 100% for 10 minutes and the unit is 

unable to raise the DAT to desired point, the controller 

will stage off 1 fixed compressor and modulate the VFD 

compressor speed to achieve the DAT set point.

Oil Balance/Boost Operational Sequence

When a low oil level is indicated in the VFD compressor sump, 

the unit switches to either an oil balance or oil boost state. The 

VFD compressor speed is increased during these modes to 

promote the return of refrigerant oil to the VFD compressor.
To avoid short cycling of the oil balance/boost sequence, no 

action is taken until a low oil indication has been present for 5 

consecutive run minutes.
The unit determines whether to enter the oil balance or oil 

boost mode based on the running conditions when a low oil 

indication is experienced. The balance mode is only used when 

a VFD compressor is part of a tandem compressor set. The 

balance mode is usually entered first, and is utilized to move 

oil from the fixed speed compressor to the VFD compressor. If 

this mode fails to resolve the low oil indication issue, the unit 

will then go into the boost mode. The boost mode is utilized 

to return oil from the refrigerant system to the compressors. 

VFD compressors that are not part of a tandem compressor 

arrangement will skip the balance mode and only utilize the 

boost mode .

The balance mode will be entered if the VFD compressor is 

part of a tandem compressor arrangement and the fixed speed 

compressor is running, and there is a low oil indication. Upon 

entering the oil balance mode the fixed speed compressor is 

turned off and the VFD compressor speed is increased to the 

oil boost value shown in Table 20. The VFD compressor runs 

at this condition until the optical oil sensor verifies that oil is 

present for 3 continuous minutes. Unit Controller default is set 

for a 10 minute max balance.

U

nIT

 o

PTIons

 

www.DaikinApplied.com 

57 

IM 1058-8 • MAVERICK II ROOFTOP SYSTEMS

Summary of Contents for MPS015 F

Page 1: ...1058 8 Group Applied Air Systems Part Number IM 1058 Date July 2017 Maverick II Commercial Packaged Rooftop Systems Heating and Cooling Models MPS015F 0050F 15 to 50 Tons R 410A Refrigerant MicroTech III Unit Controller Energy Recovery Wheel ...

Page 2: ...urement Technology 48 Unit Options 53 Economizer Enthalpy Contro 53 External Time Clock 53 Exhaust Fan Option 53 Proof of Airflow and Dirty Filter Switch 53 Duct High Pressure Limit 53 Convenience Receptacle Field Powered 54 Convenience Receptacle Unit Powered 54 Condenser Fan Operation for Variable Speed Compressor Low Ambient Option 55 VFD Compressor Operation 56 Variable Speed Scroll Compressor...

Page 3: ...n Manual bulletin number VFDs OM 844 MD2 OM 895 MD3 OM 1190 MD4 OM 1191 MD5 OM 847 MD6 MPS Unit Controller Discharge Air Control VAV or CAV Space Comfort Control SCC OM 920 LonWorks Integration IM 918 BACnet Integration IM 917 BACnet IP Comm Module IM 916 Unit Nameplate The unit nameplate is located on the outside of the main control box door It includes the unit model number serial number electri...

Page 4: ... file a claim In most cases equipment is shipped F O B factory and claims for freight damage should be filed by the consignee Before unloading the unit check the unit nameplate to make sure the voltage complies with the power supply available Service Clearance Allow service clearances as approximately indicated in Figure 1 Also Daikin recommends providing a roof walkway to the rooftop unit as well...

Page 5: ...air recirculation Overhead Clearance 1 Unit s surrounded by screens or solid walls must have no overhead obstructions over any part of the unit 2 The area above the condenser must be unobstructed in all installations to allow vertical air discharge 3 The following restrictions must be observed for overhead obstructions above the air handler section a There must be no overhead obstructions above th...

Page 6: ...urbing assembly and securely tighten all screws 4 Position curb assembly over roof openings Curb must be level within 0 25 inches from side to side and 1 50 inches over its length Check that top surface of curb is flat with no bowing or sagging 5 Weld curb assembly in place Caulk all seams watertight Remove backing from 0 25 1 50 wide gasket and apply to surfaces shown by crosshatching 6 Check tha...

Page 7: ...Figure 3 Roof Curb Layout MPS 015F 020G Mechanical Installation www DaikinApplied com 7 IM 1058 8 MAVERICK II ROOFTOP SYSTEMS ...

Page 8: ...m TYP 1 63 41 mm 93 70 2380 mm 171 18 INSIDE CURB 4348 mm 63 69 1610 mm 2 00 51 mm 2 00 51 mm 1 00 26 mm 1 00 26 mm 2 00 51 mm 3 75 95 mm PLAN VIEW 23 86 606 mm CURB CROSS SECTION KNOCKOUT DETAIL F HOT WATER ONLY CHASE 1 00 25 mm 19 00 483 mm 0 38 9 7 mm 0 38 9 7 mm IM 1058 8 MAVERICK II ROOFTOP SYSTEMS 8 www DaikinApplied com Mechanical Installation ...

Page 9: ...YP 32 mm 1 63 41 mm 69 39 1763 mm 105 45 2678 mm 208 57 INSIDE CURB 5298 mm 71 38 1813 mm 15 87 403 mm 28 25 718 mm 2 00 51 mm 2 00 51 mm 1 00 25 mm 3 75 95 mm 28 92 735 mm PLAN VIEW F 1 00 25 mm 26 00 660 mm HOT WATER ONLY CHASE 0 38 9 7 mm 0 38 9 7 mm Mechanical Installation www DaikinApplied com 9 IM 1058 8 MAVERICK II ROOFTOP SYSTEMS ...

Page 10: ...Figure 6 MPS 015 020 Roof Curb with Energy Recovery Wheel IM 1058 8 MAVERICK II ROOFTOP SYSTEMS 10 www DaikinApplied com Mechanical Installation ...

Page 11: ...Mechanical Installation Figure 7 MPS 026 035 Roof Curb with Energy Recovery Wheel Mechanical Installation www DaikinApplied com 11 IM 1058 8 MAVERICK II ROOFTOP SYSTEMS ...

Page 12: ...Figure 8 MPS 040 050 Roof Curb with Energy Recovery Wheel IM 1058 8 MAVERICK II ROOFTOP SYSTEMS 12 www DaikinApplied com Mechanical Installation ...

Page 13: ...le length from the bracket to the hook should always be longer than the distance between the outer lifting points If the unit is stored at the construction site for an intermediate period take these additional precautions 1 Support the unit well along the length of the base rail 2 Level the unit no twists or uneven ground surface 3 Provide proper drainage around the unit to prevent flooding of the...

Page 14: ... 040 350 175 350 307 050 350 175 350 307 Table 8 Curb Weights Unit tons Curb Height inches Weight lbs without ERW with ERW 015 035 14 341 458 015 035 24 501 674 040 050 14 481 619 040 050 24 708 908 Table 9 Energy Recovery Section Weights Unit Size tons Weight lbs 015 020 1200 026 035 1540 040 050 1000 Table 10 Additional Weights Motors Exhaust Fans 015 020 HP Additional Motor Weight lbs Unit tons...

Page 15: ...into the building drainage system pitch the drain line away from the unit a minimum of 1 8 per foot The drain line must penetrate the roof external to the unit Refer to local codes for additional requirements Sealed drain lines require venting to provide proper condensate flow Where the cooling coils have intermediate condensate pans on the face of the evaporator coil copper tubes near both ends o...

Page 16: ...nd replace if necessary Protect the unit from overhead runoff from overhangs or other such structures CAUTION Transportation rigging or maintenance can damage the unit s weather seal Periodically inspect the unit for leakage Standing moisture can promote microbial growth disease or damage to the equipment and building Installing Ductwork On vertical supply vertical return units if a Daikin roof cu...

Page 17: ...ct diameters away from take off points bends neckdowns attenuators vanes or other irregularities 5 Use a static pressure tip Dwyer A302 or equivalent or the bare end of the plastic tubing for the duct tap If the duct is lined inside use a static pressure tip device 6 Install the duct tap so that it senses only static pressure not velocity pressure If a bare tube end is used it must be smooth squar...

Page 18: ...way from the condenser fans walls or anything else that may cause air turbulence Mount it high enough above the roof so it is not affected by snow Not connecting the reference tap to the sensor results in unsatisfactory operation 6 Use an outdoor static pressure tip Dwyer A306 or equivalent to minimize the adverse effects of wind Place some type of screen over the sensor to keep out insects Loosel...

Page 19: ... long wires are required it may be necessary to increase the wire size to prevent excessive voltage drop Wires should be sized for a maximum of 3 voltage drop Supply voltage must not vary by more than 10 of nameplate Phase voltage imbalance must not exceed 2 Calculate the average voltage of the three legs The leg with voltage deviating the farthest from the average value must not be more than 2 aw...

Page 20: ... alarm output External discharge air temperature reset Outdoor air damper minimum position adjustment Descriptions of these field connections are included in the MicroTech III Unit Controller manual OM 920 WARNING Electrical shock hazard Can cause severe injury or death Connect only low voltage NEC Class II circuits to terminal block TB2 IM 1058 8 MAVERICK II ROOFTOP SYSTEMS 20 www DaikinApplied c...

Page 21: ...ating the fans Figure 18 shows a typical spring mount with a height adjustment nut and a shipping bolt After removing the shipping bolts rock the fan assembly by hand to check for freedom of movement Adjusting Spring Mounts During operation all fans should ride level Level the fan assembly by performing the following 1 Loosen the 3 8 cap screw do not remove 2 Loosen the spring cap nut 3 Rotate the...

Page 22: ... to the furnace assembly It contains information including gas type maximum and minimum input rating manifold pressure maximum and minimum inlet gas pressure maximum and minimum airflow requirements output capacity and electrical rating for the furnace The plate also includes model number serial number and scan code This plate is to always remain attached to the furnace This furnace must be applie...

Page 23: ...e furnace down and closes at 130 F The auxiliary limit switch is a manual reset and opens up at 180 F to shut the furnace down Figure 19 Gas Heat Section Gas Heating Capacity Data Table 15 MPS 015F 050F Gas Heating Capacities Data Unit Size 015 020 026 035 040 050 Low Heat High Heat Low Heat High Heat Low Heat High Heat Heating Input MBh 240 480 300 600 400 800 Heating Output MBh 192 384 240 480 3...

Page 24: ...ill void all warranty coverage by the manufacturer Questions regarding specific contaminants should be referred to your local gas utility Ventilation Flue Pipe Requirements The Daikin rooftop unit is equipped with an outdoor air hood to supply adequate combustion air The unit also has a flue outlet assembly and requires no additional chimney flue pipe Breidert cap draft inducer etc Factory Checkou...

Page 25: ...e flue box must be installed over the combustion exhaust openings All holes are prepunched the fasteners are furnished and everything is shipped inside the fan section 1 Remove and discard the shipping covers 2 Position the flue box over the exhaust openings 3 Line assembly holes up 4 Install screws to fasten the flue box to the side of the unit Figure 21 Flue Box Installation Outdoor Air OA Hood ...

Page 26: ...h pressure regulator and the outlet pressure must furnish gas to the appliance pressure regulator within the pressure range mentioned above Gas Piping Gas piping must be sized to provide the minimum required pressure at the burner when the burner is operating at maximum input Consult your local utility on any questions on gas pressure available allowing piping pressure drops and local piping requi...

Page 27: ...o confirm gas heating value has been devalued for applicable elevations Table 16 Furnace Identification for Altitude Elevation ft Part Number Natural Gas Fired Furnace with 50 MBH Burners 2000 2999 910166410 3000 3999 910166411 4000 4999 910166412 5000 5999 910166413 6000 6999 910166415 Natural Gas Fired Furnace with 45 MBH Burners 2000 2999 910166412 3000 3999 910166416 4000 4999 910166417 5000 5...

Page 28: ...ducing gas regulator as required to obtain 7 0 wc gas pressure 2 The gas pipe manifold pressure for high fire should be set at 3 2 wc Adjust the High Pressure Adjustment on the Honeywell VR8305Q Gas Safety Control Valve Figure 25 as required Screwing the adjustment clockwise will increase pressure counter clockwise will decrease pressure 3 The gas pipe manifold pressure for low fire stage 1 should...

Page 29: ...d gas pressure at the Inlet Pressure Tap of the Honeywell VR8305Q Gas Safety Control Valve Figure 25 and confirm pressure is at 11 0 wc Adjust upstream pressure reducing gas regulator as required to obtain 11 0 wc gas pressure 2 The gas pipe manifold pressure for high fire should be set at 8 2 wc Adjust the High Pressure Adjustment on the Honeywell VR8305Q Gas Safety Control Valve Figure 25 as req...

Page 30: ... 1 55 0 622 Butane 2 00 0 547 Table 18 Pressure Drop Other Than 0 3 Pressure Drop Multiplier Pressure Multiplier 0 1 0 577 1 0 1 83 0 2 0 815 2 0 2 58 0 3 1 000 3 0 3 16 0 4 1 16 4 0 3 65 0 6 1 42 6 0 4 47 0 8 1 64 8 0 5 15 Sequence of Operation Staged Control Low Heat Option 2 Stage Control The following details the sequence of operation for the low heat option 1 Unit DDC control calls for heat 2...

Page 31: ...h is checked for combustion airflow 5 45 second prepurge cycle starts 6 Spark ignitor is activated 7 Gas valve receives a signal to open fully 8 Burner is ignited and runs for 30 seconds in high fire 9 Modulating burner gas valve and induction blower motor receives a signal to modulate burner output to match the unit discharge air temperature setting 10 If modulating burner is unable to meet disch...

Page 32: ...r Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water Start Up Responsibility The start up organization is responsible for determining that the furnace as installed and as applied will operate within the limits specified on the furnace rating plate 1 The furnace must not operate at an ...

Page 33: ...nostic information Maintenance Planned maintenance is the best way to avoid unnecessary expense and inconvenience Have this system inspected at regular intervals by a trained and experienced service technician The following service intervals are typical for average situations but will have to be adjusted to suit your particular circumstances Fuel pressure settings and control settings should be ma...

Page 34: ...ure 3 Replace pressure switch if fails to function correctly 3 Flashes Lockout Ignition locked out from too many ignition attempts Ignition lockout from too many trials 1 Verify gas supply is present 2 Verify gas safety valve is working correctly 3 Verify gas manifold pressure is adequate and correct 4 Check spark igniter is not cracked or dirty Check spark igniter wire is not covered with oil and...

Page 35: ... air pressure reads above zero level when the inducer is off 3 Flashes Flame is on when is should be off or flame is off when it should be on 4 Flashes Gas valve is on when is should be off or gas valve is off when it should be on 5 Flashes Safety relay is on when it should be off or safety relay is off when it should be on 6 Flashes Excessive plenum temperature 7 Flashes High limit switch is open...

Page 36: ...gniter board modulating gas valve and to the induce draft motor 24VAC 115VAC LOW PRESSURE SWITCH LPS HIGH PRESSURE SWITCH HPS L1 1 2 7 8 Inducer Fan Motor Modulating Gas Valve C 24 VAC violet green orange W2 W1 R FS black red black FLAME SENSOR SPARK IGNITOR red white black white L1 L2 GND red white green UTEC 1171 63 P1 6 P1 9 P1 5 P1 8 P2 3 P2 4 P2 2 orange orange ROS1 ROS2 SC30 2 stage gas valv...

Page 37: ... cracked ceramic and damaged or disconnected wire connection Check ignition wire for cracks coated with oil and debris 5 Check for air leaks at inducer fan assembly and flue 6 Check for recirculation of exhaust flue gases 7 If all above condition are OK replace ignition board 5 Flashes Lockout Burners light and then drop out resulting in too many flame failures Lockout from too many flame losses 1...

Page 38: ...tion is the secondary auxiliary high limit switch which shut the heater down at 285 F This switch requires a manual reset Figure 31 Electric Heat Section Electric Heating Capacity Data Table 22 MPS 015 050 Electric Heating Capacities Tons Nom cfm Stages Low Medium High kW Min cfm MBh Delta T kW Min cfm MBh Delta T kW Min cfm MBh Delta T 15 6000 4 18 950 61 9 5 36 1900 123 19 0 72 3800 246 38 0 17 ...

Page 39: ... be over cooled by the DX coil Hot gas from the unit condenser will be routed to an indoor coil downstream of the DX coil to reheat the air Hot gas reheat valves will control how much hot gas is routed to the indoor coil to maintain a discharge air setpoint Figure 33 Figure 32 Ideal for Neutral Air Ventilation Control Figure 33 Dual 2 Way Valve Refrigeration Schematic Optional Modulating Hot Gas R...

Page 40: ...d air to a desirable value MHGRH is comprised of a parallel coil arrangement with both the condenser and reheat coils of the micro channel type dual reheat valves which operate in concert with one another and a check valve MHGRH components will always be installed in circuit 2 During Dehumidification control w modulating Hot Gas Reheat MHGRH an analog signal 0 10Vdc is controlled as described belo...

Page 41: ... modulate the reheat valves from this starting position Reheat valve s must be at 0 0 Vdc position before starting the first compressor in the reheat circuit to prevent pressure spikes Upon termination of dehumidification reheat the maximum ramp down or decay rate of the reheat control valves shall be 1 per sec or 0 1V per sec Upon termination of dehumidification reheat staging of compressor s is ...

Page 42: ...event air and water leakage NOTE Factory installed piping is copper Dissimilar metal within the plumbing system can cause galvanic corrosion To avoid corrosion provide proper di electric fittings as well as appropriate water treatment CAUTION Coil freeze possible Can damage equipment Follow instructions for mixing antifreeze solution Some products have higher freeze points in natural state than wh...

Page 43: ...Hot Water Pressure Drop Data Figure 37 MPS 015 017 Low and High Heat Figure 38 MPS 020 Low and High Heat Optional Hot Water Heat www DaikinApplied com 43 IM 1058 8 MAVERICK II ROOFTOP SYSTEMS ...

Page 44: ...Figure 39 MPS 026 035 Low and High Heat Figure 40 MPS 040 050 Low and High Heat IM 1058 8 MAVERICK II ROOFTOP SYSTEMS 44 www DaikinApplied com Optional Hot Water Heat ...

Page 45: ...cumferential or to the inner post Cassette The steel structure that houses the rotor Cassettes are of punched sheet metal panelized construction Enthalpy wheel A generic name for an energy conservation wheel The term enthalpy refers to an air stream s total energy temperature and humidity level Exhaust air The air stream that is exhausted to the outside Exhaust air is building return air that has ...

Page 46: ...ion Figure 43 Purge Detail Any leakage must occur from outside to Exhaust Air due to pressure gradient Supply Air Outside Air at Atmospheric Pressure Exhaust Air Adjustable Purge See Detail Plenum Exhaust Fan draws a negative pressure NOTE Maintain the pressure gradient to prevent cross contamination from the Exhaust to Outside Supply Air OUTSIDE AIR EXHAUST AIR Adjust purge in this direction to d...

Page 47: ... so that less enthalpy transfer occurs and frosting of the wheel is avoided Frosting can occur on the enthalpy wheel when the exhaust air leaving the wheel is saturated This condition occurs when two lines intersect on a psychrometric chart and it does not occur when these two lines do not intersect see Figure 44 Energy Recovery Exhaust Hoods Units with the optional energy recovery section have on...

Page 48: ...4 VAC to the outdoor air monitor controller a 24VAC from the unit control panel to the controller terminals L1 and L2 Outdoor Air Monitor Controller Settings 1 Set Controller SW1 switch to Vdc 2 Set power switch to ON Outdoor Air Monitor Controller Configuration Set Up see Appendix Figure 102 on page 129 for navigating the Controller keypad 1 Set LCD1 U M to CFM 2 Set AR1 see Table 24 3 Set OUT1 U...

Page 49: ...Figure 47 MicroTech III Controller Figure 48 Transmitter and Connector Detail Transmitter Connector Optional Outdoor Air Monitor www DaikinApplied com 49 IM 1058 8 MAVERICK II ROOFTOP SYSTEMS ...

Page 50: ...nu See Appendix Figure 103 on page 130 If you wish to manually convert the velocity output to volumetric flow CFM or LPS simply multiply the indicated output velocity in FPM or MPS by the free area of the air flow probe installation location free area x 1000 for SI units when area is calculated in square meters For P sensors the total free area is programmed into the probe at the factory and is pr...

Page 51: ...he ON position The green Transmitter Status LED D3 on the main circuit board is flashing at 1 second intervals No problem normal operation No remedy required The green Transmitter Status LED D3 on the main circuit board is flashing at 2 second intervals The sensor detection system has detected one or more malfunctioning or missing sensors Check sensor probe cable connections If sensor probe connec...

Page 52: ...ctor of the transmitter does not match that of the host controls Compare the value of the Area or K factor of the transmitter with that of the host control system and make adjustments to ensure a match The returned value for airflow is zero when airflow is indicated on the LCD display of the transmitter The Low Limit airflow cutoff value is above the actual airflow reading Decrease the Low Limit a...

Page 53: ...y Filter Switch The proof of airflow switch PC7 and the dirty filter switch PC5 are supplied on all CAV units The tubing is installed to the switches per Figure 49 The proof of airflow switches senses the pressure difference between the positive pressure in the supply air fan compartment and the suction pressure on the leaving air side of the filters The differential pressure is factory set at 0 2...

Page 54: ...he receptacle shall be powered by a factory installed and wired 120V 20 amp power supply The power supply shall be wired to the line side of the unit s main disconnect so the receptacle is powered when the main unit disconnect is off This option shall include a GFI receptacle transformer and a branch circuit disconnect The electrical circuit shall be complete with primary and secondary overload pr...

Page 55: ...y Speed reference Level in which the VFD will stop the condenser fan motor under certain conditions If the head pressure were to fall below 250 PSIG with the condenser fan operating at minimum speed of 10Hz possibly due to a low ambient or high wind condition the VFD will shut down the condenser fan The VFD will restart the condenser fan at 20 Hz if head pressure rises to a level above 250 PSIG In...

Page 56: ... continue to operate on the remaining fixed speed compressors of the non VFD circuit until the unit can be serviced When the VFD compressor is at its maximum speed and more capacity is required a fixed speed compressor is started while the VFD compressor is reduced to minimum speed at which point it resumes modulating to maintain the discharge temperature When the VFD compressor is at its minimum ...

Page 57: ...hen dehumidification operation becomes active while the unit is in the Cooling operating state The VFD compressor is ramped to its maximum capacity If the VFD capacity at this point is already above 75 of its full modulation a fixed compressor is also turned on The compressors are held at this capacity for 1 minute before normal modulation resumes to maintain leaving coil temperature LCT VFD compr...

Page 58: ...isabled if the oil boost sequence is initiated more than 4 times in a 24 hour period If the oil balance boost sequence successfully restores the VFD compressor oil level the fixed compressor stage is returned to its pre oil balance boost condition and normal compressor sequencing and modulation resumes VFD Compressor Protection Unloading Control There are several modulating control functions that ...

Page 59: ...minutes the VFD compressor speed is increased by 5 rps increments up to a 60 rps operating speed Superheat is monitored at each speed for 10 minutes and if superheat remains below 20F the VFD compressor speed is increased an additional 5 rps When compressor discharge superheat level is at 20F or above the compressor speed is no longer increased If speed correction resolves problem the unit control...

Page 60: ... the discharge pressure exceeds 250 PSIG When the VFD compressor reaches 250 PSIG this speed becomes the new minimum speed of the VFD compressor As the discharge pressure rises above 250 PSIG the minimum allowable compressor speed is decreased in 5 rps increments every 30 seconds If the condenser coil splitter valve is closed and the VFD compressor discharge remains below 250 PSIG for 15 minutes t...

Page 61: ...e speed compressor enhances energy efficiency and capable of providing unit capacity modulation down to 20 and reduces compressor cycling and wear on compressor Daikin rooftop units with variable speed Inverter compressors are provided with Internal Permanent Magnet IPM motors Compressors are designed to vary capacity by modulating the speed of the scroll set The speed ratio for the IPM motor comp...

Page 62: ...l Dismanteling Optical Oil Level Sensor An optical oil sensor is used to monitor oil level in VFD compressor sump The sensor is mounted directly to a fitting on the VFD compressor shell and can be removed without having to depressurize reclaim the refrigeration system Optical oil indication signal is sent to MTIII Expansion Module C terminals X3 M Normal oil indication will provide a contact closu...

Page 63: ...t for an open loop configuration with 0 10Vdc reference corresponding to 1500 6000 Rpm The compressor drive generates a soft start with an initial ramp of 2 seconds In rush current or LRA to the VFD compressor is typically not more than a few percent more than rated nominal Current Compressor Speed modulation signal frequency signal compressor amperage are all displayed in real time on the compres...

Page 64: ...Wiring Diagrams Figure 61 VAV Power Fixed Speed Scroll Compressor IM 1058 8 MAVERICK II ROOFTOP SYSTEMS 64 www DaikinApplied com Wiring Diagrams ...

Page 65: ...Figure 61 continued VAV Power Fixed Speed Scroll Compressor Wiring Diagrams www DaikinApplied com 65 IM 1058 8 MAVERICK II ROOFTOP SYSTEMS ...

Page 66: ...Figure 62 MPS 026 VAV Power with Variable Speed Inverter Compressor IM 1058 8 MAVERICK II ROOFTOP SYSTEMS 66 www DaikinApplied com Wiring Diagrams ...

Page 67: ...Figure 62 continued MPS 026 VAV Power with Variable Speed Inverter Compressor Wiring Diagrams www DaikinApplied com 67 IM 1058 8 MAVERICK II ROOFTOP SYSTEMS ...

Page 68: ...Figure 63 MPS 030 050 VAV Power with Variable Speed Inverter Compressor IM 1058 8 MAVERICK II ROOFTOP SYSTEMS 68 www DaikinApplied com Wiring Diagrams ...

Page 69: ...Figure 63 continued MPS 030 050 VAV Power with Variable Speed Inverter Compressor Wiring Diagrams www DaikinApplied com 69 IM 1058 8 MAVERICK II ROOFTOP SYSTEMS ...

Page 70: ...Figure 64 VAV Control Inputs IM 1058 8 MAVERICK II ROOFTOP SYSTEMS 70 www DaikinApplied com Wiring Diagrams ...

Page 71: ...Figure 64 continued VAV Control Inputs Wiring Diagrams www DaikinApplied com 71 IM 1058 8 MAVERICK II ROOFTOP SYSTEMS ...

Page 72: ...Wiring Diagrams Figure 65 MPS 026 VAV Control with Variable Speed Inverter Compressor IM 1058 8 MAVERICK II ROOFTOP SYSTEMS 72 www DaikinApplied com Wiring Diagrams ...

Page 73: ...Figure 65 continued MPS 026 VAV Control with Variable Speed Inverter Compressor Wiring Diagrams www DaikinApplied com 73 IM 1058 8 MAVERICK II ROOFTOP SYSTEMS ...

Page 74: ...Figure 66 MPS 026 with Variable Speed Inverter Compressor without Low Ambient Option IM 1058 8 MAVERICK II ROOFTOP SYSTEMS 74 www DaikinApplied com Wiring Diagrams ...

Page 75: ...Figure 67 MPS 030 050 VAV Control with Variable Speed Inverter Compressor Wiring Diagrams www DaikinApplied com 75 IM 1058 8 MAVERICK II ROOFTOP SYSTEMS ...

Page 76: ...Wiring Diagrams Figure 67 continued MPS 030 050 VAV Control with Variable Speed Inverter Compressor IM 1058 8 MAVERICK II ROOFTOP SYSTEMS 76 www DaikinApplied com Wiring Diagrams ...

Page 77: ...Figure 68 MPS 040 050 with Variable Speed Inverter Compressor with Low Ambient Option Wiring Diagrams www DaikinApplied com 77 IM 1058 8 MAVERICK II ROOFTOP SYSTEMS ...

Page 78: ...Figure 69 VAV Control Outputs Staged Gas Heat IM 1058 8 MAVERICK II ROOFTOP SYSTEMS 78 www DaikinApplied com Wiring Diagrams ...

Page 79: ...Figure 69 continued VAV Control Outputs Staged Gas Heat Wiring Diagrams www DaikinApplied com 79 IM 1058 8 MAVERICK II ROOFTOP SYSTEMS ...

Page 80: ...Figure 70 CAV Power IM 1058 8 MAVERICK II ROOFTOP SYSTEMS 80 www DaikinApplied com Wiring Diagrams ...

Page 81: ...Figure 70 continued CAV Power Wiring Diagrams www DaikinApplied com 81 IM 1058 8 MAVERICK II ROOFTOP SYSTEMS ...

Page 82: ...Figure 71 CAV Control Inputs IM 1058 8 MAVERICK II ROOFTOP SYSTEMS 82 www DaikinApplied com Wiring Diagrams ...

Page 83: ...Figure 71 continued CAV Control Inputs Wiring Diagrams www DaikinApplied com 83 IM 1058 8 MAVERICK II ROOFTOP SYSTEMS ...

Page 84: ...Wiring Diagrams Figure 72 CAV Control Outputs Staged Gas Heat Figure 73 VAV CAV Control Outputs Modulating Gas Heat IM 1058 8 MAVERICK II ROOFTOP SYSTEMS 84 www DaikinApplied com Wiring Diagrams ...

Page 85: ...Figure 74 Electric Heat Option Power Figure 75 Electric Heat Option Outputs Wiring Diagrams www DaikinApplied com 85 IM 1058 8 MAVERICK II ROOFTOP SYSTEMS ...

Page 86: ...Figure 76 Energy Recovery IM 1058 8 MAVERICK II ROOFTOP SYSTEMS 86 www DaikinApplied com Wiring Diagrams ...

Page 87: ...Figure 76 continued Energy Recovery Wiring Diagrams www DaikinApplied com 87 IM 1058 8 MAVERICK II ROOFTOP SYSTEMS ...

Page 88: ...Wiring Diagrams Figure 77 Energy Recovery Main Control Board IM 1058 8 MAVERICK II ROOFTOP SYSTEMS 88 www DaikinApplied com Wiring Diagrams ...

Page 89: ...Figure 77 continued Energy Recovery Main Control Board Wiring Diagrams www DaikinApplied com 89 IM 1058 8 MAVERICK II ROOFTOP SYSTEMS ...

Page 90: ... for CAV units The unit goes into the heating mode of operation when the control temperature return or space temperature is below the heating setpoint by more than the deadband Example If the heating setpoint is 68 0 F and the deadband is 1 0 F the unit will not go into the heating mode of operation until the control temperature reaches 67 4 F When this takes place the heating mode of operation wi...

Page 91: ...into the cooling mode of operation when the control temperature return temperature is above the changeover setpoint by more than the deadband Example If the change over temperature is 70 0 F and the deadband is 1 0 F the unit will not go into the cooling mode of operation until the return temperature reaches 70 6 F When this takes place the cooling mode of operation will begin and the 1st stage of...

Page 92: ...ed 3 Verify that all construction debris is removed and that the filters are clean 4 Verify that all electrical work is complete and properly terminated 5 Verify that all electrical connections in the unit control panel are tight and that the proper voltage is connected 6 Verify all nameplate electrical data is compatible with the power supply 7 Verify the phase voltage imbalance is no greater tha...

Page 93: ... economizer operation in both low and high enthalpy states on the same day If this is the case repeat this procedure on another day when the opposite outdoor air enthalpy conditions exist Compressor Start Up CAUTION Low ambient temperature hazard Can cause compressor damage Do not attempt to start up and check out the refrigeration system when the outdoor air temperature is below 20 F With the sup...

Page 94: ...urn air entering the unit f Verify that the liquid line components expansion valve and distributor tubes are feeding the evaporator coil g Verify that all air handling section panels are closed 4 Verify that the condenser fans are cycling and rotating properly blowing air upward When the compressor starts at least one condenser fan should also start 5 Check the oil level in the compressor sightgla...

Page 95: ...e ideal tension is the lowest tension at which the belt will not slip under peak load conditions Over tensioning shortens belt and bearing life 2 Check tension frequently during the first 24 48 hours of operation 3 Keep belts free from foreign material which may cause slippage 4 Make V drive inspection on a periodic basis Adjust tension if the belt is slipping Do not apply belt dressing This may d...

Page 96: ...lty starting disconnect power and inspect for excessive interference between the wheel surface and each of the 4 diameter seals Diameter Seal Adjustment 1 Loosen diameter seal adjusting screws See Figure 81 2 Move adjustable diameter seals away from wheel 3 Using a inch feeler gauge adjust the diameter against the wheel See Figure 81 4 Tighten diameter seal adjusting screws 5 Apply power per the s...

Page 97: ...re setpoint 4 Set the alarm limits as required 5 Set the duct static pressure control parameters as required 6 Set the building static pressure control parameters as required 7 Set the economizer control parameters as required 8 Set the date and time in keypad menu 9 Set the operating schedule as required using keypad menus NOTE Unit operation may also be controlled by the building automation syst...

Page 98: ...ectric power to the unit when servicing control panel components Before servicing always inspect units for multiple disconnects to ensure all power is removed from the control panel and its components Planned Maintenance Preventive maintenance is the best way to avoid unnecessary expense and inconvenience Have this system inspected at regular intervals by a qualified service technician The require...

Page 99: ... Coil to Copper Tubing Figure 83 shows the aluminum condenser coil connection to the copper tubing in the unit Because of the low melting point of aluminum 1220 F compared to 1984 F for copper this brazed joint is performed with a low temperature brazing process CAUTION Potential equipment damage If a standard copper brazing process is performed at this joint the process will damage the aluminum c...

Page 100: ...ely removed prior to using low velocity clean water rinse Periodic Clean Water Rinse A monthly clean water rinse is recommended for coils that are applied in coastal or industrial environments to help to remove chlorides dirt and debris An elevated water temperature not to exceed 130ºF will reduce surface tension increasing the ability to remove chlorides and dirt Pressure washer PSI must not exce...

Page 101: ...o thoroughly wet out surface with no areas missed This may be accomplished by use of a pump up sprayer or conventional spray gun The method does not matter as long as the entire area to be cleaned is wetted After the substrate has been thoroughly wetted the salts will be soluble and is now only necessary to rinse them off 3 Rinse It is highly recommended that a hose be used as a pressure washer wi...

Page 102: ...non authorized trip point or setpoint adjustment voids all or portions of the unit s warranty Authorized setpoint adjustment is accomplished as follows 1 For motors with a 1 15 service factor rotate the arrow on the dial to correspond to the motor FLA 2 For motors with a 1 0 service factor multiply the motor FLA by 0 9 then rotate the arrow on the dial to correspond to that value To reset a trippe...

Page 103: ...Ds to provide short circuit protection These breakers are not adjustable To reset a tripped circuit breaker Clear the trip by rotating the lever down to the OFF position Then rotate lever up to the ON position see Figure 86 Breakers like MMPs have three distinct modes of operation which are clearly indicated by the handle position The positions are ON usually up OFF usually down and TRIPPED midway...

Page 104: ...activates after power line conditions return to an acceptable level for a specified amount of time Restart Delay The trip and restart delays prevent nuisance tripping due to rapidly fluctuating power line conditions There are two LEDs on the face of the PVM 1 in Figure 88 to indicate the following items in Table 32 Figure 88 Phase Voltage Monitor Table 32 LED Indication Status LED Indicator Normal...

Page 105: ...ovide adequate protection from vandalism mechanical contact etc Make sure all doors are securely closed and all latches closed Units should be fitted with covers over the supply and return air openings Preparation for Storage Supply Fans 1 Remove the drive belts tag them with the fan name and unit serial number and store them in a conditioned space out of direct sunlight 2 Once every two weeks rot...

Page 106: ...e temperature variations or other severe atmospheric conditions relubricate more frequently Use one of the greases shown in Table 33 While the bearing is at normal operating temperatures rotate the fan by hand and add only enough grease to purge the seals The seals bleed slightly when this occurs Do not overlubricate Table 33 Recommended Greases Manufacture Product Name Temp Range F Texaco Lubrica...

Page 107: ...Annually confirm set screw is secure Drive Belts The wheel drive belt is a urethane stretch belt designed to provide constant tension through the life of the belt No adjustment is required Inspect the drive belt annually for proper tracking and tension A properly tensioned belt will turn the wheel immediately after power is applied with no visible slippage during start up Belts are multilink with ...

Page 108: ...acid based coil cleaner such as Acti Klean available through Daikin Stock AK1 or alkaline detergent and warm water Soak in the solution until grease and tar deposits are loosened Note some staining of the desiccant may remain and is not harmful to performance Before removing rapidly run finger across surface of segment to separate polymer strips for better cleaning action Rinse dirty solution from...

Page 109: ... wheel 180 Install the second segment opposite the first for counter balance Rotate the two installed segments 90 to balance the wheel while the third segment is installed Rotate the wheel 180 again to install the fourth segment opposite the third Repeat this sequence with the remaining four segments Figure 91 Segment Retaining Clip Figure 92 Installing Wheel Segments Wheel Drive Motor Pulley Repl...

Page 110: ...placement Troubleshooting The following table may be used as a quick reference for identifying common symptoms and possible causes related to the recovery wheel Table 34 Energy Recovery Wheel Troubleshooting Symptom Cause Inadequate Wheel Performance Check wheel rotation speed see Variable Speed Frequency Control on page 47 Check for wheel integrity and adjust seals or replace worn seals see Energ...

Page 111: ...ant Replace pressure switch after reclaiming refrigerant Venting refrigerant to atmosphere is not allowed per most local laws and or codes Servicing Refrigerant Sensors or Switches The Maverick II includes the following refrigerant sensors or switches 1 Low refrigerant pressure sensing operating switch automatic reset a Disables associated compressors on a drop in suction pressure to approximately...

Page 112: ...Daikin Parts Department for compressor availability 2 Send a completed parts order form to the Daikin Parts Department 3 The Parts Department processes the order and the compressors are shipped from our Dayton OH warehouse via ground transportation If next day air is required indicate this on the parts order form and a freight charge will be billed to your account Air freight costs are not covered...

Page 113: ..._______________________________________________________________ Company name ________________________________________________________________________________________________ Address ______________________________________________________________________________________________________ City State Zip __________________________________________________________________________________________________ U...

Page 114: ...re all electrical power connections tight Check compressorelectrical box Yes No N A K Is the condensate drain trapped Yes No N A II FAN DATA A Check rotation of supply fan Yes No N A B Voltage at supply fan motor 1 2_____________ V 2 3 _____________ V 1 3 _____________ V C Supply fan motor amp draw per phase L1 _____________ L2 _____________ L3 _____________ D Fuse sizes __________________________...

Page 115: ...__ Phase 3 _______ C Low pressure cut out Circuit 1 __________ psig Circuit 2 __________ psig D Low pressure cut in Circuit 1 __________ psig Circuit 2 __________ psig E High pressure cut out Circuit 1 __________ psig Circuit 2 __________ psig F Discharge pressure one compressor Circuit 1 __________ psig Circuit 2 __________ psig G Discharge pressure fully loaded 2 3 compressors Circuit 1 ________...

Page 116: ...6 Phase L1 ___________ ____________ ____________ ___________ ___________ ____________ Phase L2 ___________ ____________ ____________ ___________ ___________ ____________ Phase L3 ___________ ____________ ____________ ___________ ___________ ____________ G FLA L1 ___________ L2____________ L3 ___________ H Operate electric heat with fans off Electric heat must cycle on high limit control Yes No N A...

Page 117: ... OK Yes No N A VIII Heat Recovery A Heat wheel rotates freely Yes No N A B Heat wheel VFD operates properly Yes No N A C Heat wheel VFD Model No _________________________ Serial No ___________________________ D Check for air bypass around heat wheel Yes No N A IX Design Flow Calibration A Verify power is supplied to the MicroTech III unit controller Yes No N A B Verify that the shipping screws hav...

Page 118: ...er replacement Thank you for completing this form Please sign and date below Signature _____________________________________________________________ Startup date ___________________________ Return completed form by mail to Daikin Warranty Department 13600 Industrial Park Boulevard Minneapolis MN 55441 or by email to AAH Wty_WAR_forms daikinapplied com Please fill out the Daikin Applied Quality Ass...

Page 119: ...pearance of the product i e paint fin damage etc Excellent Good Fair Poor 3 Did all sections of the unit fit together properly Yes No N A 4 Did the cabinet have any air leakage Yes No N A Location on unit ___________________________________________________________________________________ 5 Were there any refrigerant leaks Yes No N A From where did it occur Shipping Workmanship Design 6 Does the re...

Page 120: ...IAQ PPM XXXXppm Occ Clg Spt 72 0 F OA Flw XXXXXCFM Occ Htg Spt 68 0 F MinOAFlw Spt 2000CFM Disch Air XXX F OA Temp XXX F Rel Humidity XXX About This Unit SO_Item 123456_12345 Unit SN FBOU123456789 App Version 2506018xxx Cf1 15 xxxxxxxxxxxxxxxx Cf6 29 xxxxxxxxxxxxxxxx Main BSP X XX LON BSP X XX LON App Ver X XX BACnet BSP X XX D Net BSP X XX HMI GUID xxxxxxxx xxxx xxxx xxxx xxxxxxxxxxxx OBH GUID xx...

Page 121: ...et Up BACnet MSTP Set Up BACnet IP Set Up D Net Set Up Network Unit Set Up Commission Unit Unit Set Up Timer Settings SAF Set Up RF EF Set Up Htg Clg ChgOvr Set Up Cooling Set Up INV Cmp Set Up Econo Set Up Min OA Set Up Heating Set Up OA Fan Set Up Exp Valve Set Up Defrost Set Up Dehum Set Up Energy Rec Set Up D3 Set Up Alarm Configuration Service Menus Timer Settings Operating Hours Save Restore...

Page 122: ...DRT3 XXX F SRT XXX F DFT XXX F IRT XXX F ORT XXX F Occupancy Occupancy __________ Occ Mode Auto Net OccSrc _____________ UnoccSrc ___________ Tnt Ovrde Tm 0 min SAF Speed Control SAF Speed XXX Speed Cmd XXX Duct Press X Xin DuctSP Spt 1 0in IAQ PPM XXXXPPM OA Flw XXXXXCFM MinOAFlw Spt 2000CFM Bldg Press X XXin BldgSP Spt 0 05in RF EF Control RF EF Cap XXX Speed Cmd XXX Bldg Press X XXin BldgSP Spt...

Page 123: ...Htg OAT 0 ºF Clg Rate 0 4 ºF min Clg OAT 85 ºF Des Clg OAT 95 ºF DAYLIGHT SAVINGS DLS Strt Mon Mar DLS Strt Wk 2nd Week DLS End Mon Nov DLS End Wk 1st Week DLS Active Yes Cooling Occ Clg Spt 72 0 F Unocc Clg Spt 85 0 F DAT Clg Spt 55 0 F Economizer OAD Econo Pos XXX DAT Clg Spt 55 0 F Min OA Pos XXX Occ Clg Spt 72 0 F Unocc Clg Spt 85 0 F Min OA Damper Min OA Pos XXX Vent Limit 20 LoFlo V Lmt 30 D...

Page 124: ... SuplHtgHiOATLk 55 0 F OAT Diff 2 0 F Htg Reset None Min Htg Spt 55 0 F Min Htg Spt 0 Max Htg Spt 120 0 F Max Htg Spt 100 Min DAT Ctrl Yes Min DAT Limit 55 0 F Occ Heating Yes Unocc Diff 55 0 F Htg Wmup Tm 60s Htg Hld Period 240s MWUSensor RAT Timer Settings Service Time 0min Start Up 180s Recirculate 180s Zero OA Time 0min Tnt Override 120min Post Heat 0s Pwd Timeout 10min Low DAT 6min ClgStateDe...

Page 125: ...e 9 0ºF REFRIG CIRCUIT STATUS Htg EVI Meth SbC PTS XXX Xpsi IC SC Spt 9 0ºF PTD XXX Xpsi IC SC DB 2 0ºF Suction SH XX XºF HtgSC EVI Min 0 Discharge SH XX XºF Clg EVO Meth SbC Subcooling XX X F OC SC Spt 9 0ºF Eff SSH Spt XX X F OC SC DB 2 0ºF EffSH Base XX X F ClgSC EVO Min 0 Eff SC Spt XX X F ManCtrl EV Op Auto Eff SC Lo Lmt XXX SRT XXX F Disch Sat Tmp XXX X F Sucn Sat Tmp XXX X F IRT XXX F ORT X...

Page 126: ...___ OAAdd17 32 _________ OAAdd33 49 _________ OAAdd50 64 _________ SetOAAddr XX CurrOAAddr XX CurrOAAmps XXXA CurrOARLA XXXA Sensor Offsets Disch Air 0 0ºF Return Air 0 0ºF Space Temp 0 0ºF OA Temp 0 0ºF EF LC Temp 0 0ºF ER LAT 0 0ºF ER EAT 0 0ºF DRT1 0 0ºF DRT3 0 0ºF SRT 0 0ºF DFT 0 0ºF IRT 0 0ºF ORT 0 0ºF Network Input Status Net OAT In XXX XºF Net Space In XXX XºF NetCurrState _________ NetNext...

Page 127: ...__ MCB DI2 ____________ MCB DI3 ____________ MCB DI4 ____________ MCB DI5 ____________ MCB DI6 ____________ EMD DI1 ____________ Digital Output Status MCB DO1 __________ MCB DO2 __________ MCB DO3 __________ MCB DO4 __________ MCB DO5 __________ MCB DO6 __________ MCB DO7 __________ MCB DO8 __________ MCB DO9 __________ MCB DO10 __________ EMB DO1 __________ EMB DO2 __________ EMB DO3 __________ E...

Page 128: ...CONTROL OPTIONS SAF Ctlr DSP RF EF Ctlr Tracking D Net Set Up ApplyD NetChgs No DHCP On Act IP 0 0 0 0 ActMsk 0 0 0 0 ActGwy xxx xxx xxx xxx Gvn IP 127 0 0 1 GvnMsk 255 255 255 0 GvnGwy 127 0 0 1 Remote Srv En Disable Comm Status ________ D net BSP X X XX BMS Communications LON Set Up BACnet MSTP Set Up BACnet IP Set Up D Net Set Up Network Unit Set Up Trending Trending Ena No Apply Chgs No Sample...

Page 129: ...stem of units to S I MPS LPS sq M Pa C IP SI Units Select During Normal Operation Enter Move Esc Move Factory Default Current Setting Enter Move Esc Move Enter Action Move Esc Move IP SI IP SYS IP SI IP SYS IP SI SI SYS Set System Set Up Comm Set Up Ethernet Set Up Diagnostics www DaikinApplied com 129 IM 1058 8 MAVERICK II ROOFTOP SYSTEMS Appendix Keypad Display Menu Structure ...

Page 130: ...c Move Visible only when LCD U M CFM FS1 units determined by OUT1 U M setting Displays airflow in FPM Outputs airflow in FPM In addition SW1 must be set to the VDC position to change airflow output to 0 10VDC In addition SW1 must be set to the VDC position to change airflow output to 0 5VDC In addition SW1 must be set to the mA position to change airflow output to 4 20mA Set area between 0 00 and ...

Page 131: ...uce Temperature output Sets OUT2 to produce Alarm output In addition SW2 must be set to the VDC position to change airflow output to 0 10VDC In addition SW2 must be set to the VDC position to change airflow output to 0 5VDC In addition SW2 must be set to the mA position to change airflow output to 4 20mA 1 Factory default current setting 2 If a selection is made that requires SW1 to be set the LCD...

Page 132: ...ant to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Applied representative for warranty details To find your local Daikin Applied representative go to www DaikinApplied com Aftermarket Services To find your local parts office visit www DaikinApplied com or call 800 37PARTS 800 377 2787 To find your local service office visit www DaikinAppli...

Reviews: