reParInG
U
nIT
for
o
PeraTIon
Spring Isolated Fans
WARNING
Moving machinery hazard. Can cause severe injury ordeath.
Before servicing equipment, disconnect power and lockoff.
More than one disconnect may be required to de-energizeunit.
Prior to operating the fans for the first time, refer to
Test, and Start Procedures on page 92
Releasing Spring Mounts
The spring-mounted supply fan is locked down with four
shipping bolts for shipment. Remove each shipping bolt before
shows a typical spring mount
with a height adjustment nut and a shipping bolt.After removing
the shipping bolts, rock the fan assembly by hand to check for
freedom of movement.
Adjusting Spring Mounts
During operation all fans should ride level. Level the fan
assembly by performing the following:
1 .
Loosen the 3/8" cap screw (do not remove).
2 .
Loosen the spring cap nut.
3 .
Rotate the 5/8" adjustment nut counter-clockwise to raise
the fan assembly, or clockwise to lower the fan assembly.
4 .
Tighten the 3/8" cap screw.
5 .
Tighten the spring cap nut.
Figure 18: Spring Mounts
P
reParInG
U
nIT
for
o
PeraTIon
www.DaikinApplied.com
21