Troubleshooting Guide and FAQ
OM 1085-6 • MICROTECH III CONTROLLER
Enfinity Large Two Compressor (SS2C)
Table 11:
Unit Controller Configuration Jumpers for Enfinity Large Two Compressor (SS2C)
Unit Controller Option
Hardware Jumpers
Setting
Description
Normal / Test Mode
JP1
JP1 = Open
Normal Operation
JP1 = Shorted
Service / Test Mode
Fan Operation
JP2
JP2 = Open
Continuous Fan Operation (On)
JP2 = Shorted
Cycling Fan Operation (Auto)
Loop Fluid
JP3
JP3 = Open
Water Loop Fluid
JP3 = Shorted
Glycol Loop Fluid
Freeze Fault Protection
JP4
JP4 = Open
LWT Freeze Fault Protection is Disabled
JP4 = Shorted
LWT Freeze Fault Protection is Enabled
Room Sensor Setpoint Adjust Range
JP5
JP5 = Open
Short Range: -5 to +5 ºF (-2.78 to +2.78 ºC)
JP5 = Shorted
Long Range: 55 to 95 ºF (12.78 to 35 ºC)
Thermostat / Room Sensor
JP6
JP6 = Open
Thermostat Control
JP6 = Shorted
Room Sensor Control
Compressor Availability
JP7 & JP8
JP7 = Open
Both Compressors Available (Automatic Compressor Fail Replace)
JP8 = Open
JP7 = Shorted
Lead Compressor Available (Lag Compressor is Off-Line)
JP8 = Open
JP7 = Open
No Compressors Available
JP8 = Shorted
Table 12:
I/O Expansion Module Configuration Jumpers for Enfinity Large Two Compressor (SS2C)
I/O Expansion Module Option
Hardware Jumpers
Setting
Description
Not Used
JP1
JP1 = Open
—
Not Used
JP2
JP2 = Open
—
Secondary Heating
JP3 & JP4
JP3 = Open
None
JP4 = Open
JP3 = Shorted
Supplemental Electric Heat
JP4 = Open
JP3 = Open
Boilerless Electric Heat
JP4 = Shorted
JP3 = Shorted
Hydronic Heating
JP4 = Shorted
Cooling / Dehumidification
JP5 & JP6
JP5 = Open
None
JP6 = Open
JP5 = Shorted
HGR Dehumidification
JP6 = Open
JP5 = Open
Hydronic Cooling (Waterside Economizer)
JP6 = Shorted
Not Used
JP7
JP7 = Open
—
Lead Compressor Select
JP8
JP8 = Open
Compressor #1 is Lead
JP8 = Shorted
Compressor #2 is Lead
Table 13:
Model Types and Options for Enfinity Large Two Compressor (SS2C)
1, 2
Model Number
Supplemental Electric Heat Boilerless Electric Heat
Hydronic Heating
HGR Dehumid
Waterside Economizer
1
—
—
—
—
—
2
X
—
—
—
—
3
—
X
—
—
—
4
—
—
X
—
—
5
—
—
—
X
—
6
X
—
—
X
—
7
—
X
—
X
—
8
—
—
X
X
—
9
—
—
—
—
X
10
X
—
—
—
X
11
—
X
—
—
X
1
All Enfinity Large Two Compressor (SS2C) WSHP models require both the unit controller and I/O expansion module.
2
An “X” means that option is available for the corresponding WSHP model.