OM 1085-6 • MICROTECH III CONTROLLER 30 www.DaikinApplied.com
Troubleshooting Guide and FAQ
Table 9: I/O Expansion Module Configuration Jumpers for SmartSource Single and Two Stage Compressor (Series2) and
SmartSource Compact
I/O Expansion Module Option
Hardware Jumpers Setting
Description
Fan Row Selection (V6.2 & Newer)
JP1 & JP2
—
Fan row selection for the: FanOnly, Hydronic Heating, and Hydronic Cooling
machine states.
Secondary Heating
JP3 & JP4
JP3 = Open
None
JP4 = Open
JP3 = Shorted
Supplemental Electric Heat
JP4 = Open
JP3 = Open
Boilerless Electric Heat
JP4 = Shorted
JP3 = Shorted
Hydronic Heating (v6.0 & Newer)
JP4 = Shorted
Cooling / Dehumidification
JP5 & JP6
JP5 = Open
None
JP6 = Open
JP5 = Shorted
HGR Dehumidification
JP6 = Open
JP5 = Open
Hydronic Cooling (Waterside Economizer)
JP6 = Shorted
Not Used
JP7
JP7 = Open
—
Compressor Capacity
JP8
JP8 = Open
Single Stage Compressor
JP8 = Shorted
Dual Stage Compressor
Table 10: Model Types and Options for SmartSource Single and Two Stage Compressor (Series2) and SmartSource
Compact
3
Model
Number
Compressor
Type
Supplemental
Electric Heat
Boilerless
Electric Heat
Hydronic
Heat
2
HGR
Waterside
Economizer
1
1
Single Stage
—
—
—
—
—
2
Single Stage
—
—
—
X
—
3
Single Stage
—
—
—
—
X
4
Single Stage
X
—
—
—
—
5
Single Stage
X
—
—
X
—
6
Single Stage
X
—
—
—
X
7
Single Stage
—
X
—
—
—
8
Single Stage
—
X
—
X
—
9
Single Stage
—
X
—
—
X
10
Single Stage
—
—
X
—
—
11
Single Stage
—
—
X
X
—
12
Single Stage
—
—
X
—
X
13
Two Stage
—
—
—
—
—
14
Two Stage
—
—
—
X
—
15
Two Stage
—
—
—
—
X
16
Two Stage
X
—
—
—
—
17
Two Stage
X
—
—
X
—
18
Two Stage
X
—
—
—
X
19
Two Stage
—
X
—
—
—
20
Two Stage
—
X
—
X
—
21
Two Stage
—
X
—
—
X
22
Two Stage
—
—
X
—
—
23
Two Stage
—
—
X
X
—
24
Two Stage
—
—
X
—
X
1
Except for SmartSource Two Stage Compressor (Series2) WSHP with a single speed fan with no options selected, all other SmartSource Two Stage Compressor
(Series2) WSHPs require both the unit controller and I/O expansion module.
2
Hydronic heating is only available for unit controller software v6.0 and newer.
3
An “X” means that option is available for the corresponding WSHP model.
Summary of Contents for MicroTech III