background image

Align the centers of both flares and tighten the flare nuts 3 or 4 turns by hand. Then tighten them fully 
with the torque wrenches. 

Refrigerant Piping Work

2.

Refrigerant piping.

2-1. Caution on piping handling.

1) Protect the open end of the pipe against dust and moisture.
2) All pipe bends should be as gentle as possible. Use a pipe bender for bending. 

2-2. Selection of copper and heat insulation materials.

• When using commercial copper pipes and fittings, observe the following:

1) Insulation material:  Polyethylene foam

Heat transfer rate:  0.041 to 0.052W/mK (0.024-0.030Btu/fth˚F (0.035-0.045kcal/mh˚C))
Refrigerant gas pipe’s surface temperature reaches 230˚F (110˚C) max.
Choose heat insulation materials that will withstand this temperature.

2) Be sure to insulate both the gas and liquid piping and to provide 

insulation dimensions as below.

3) Use separate thermal insulation pipes for gas and liquid refrigerant pipes.

Flare nut tightening torque

Gas side

Liquid side

45.6-55.6ft 

l

 lbf

(61.8-75.4N 

l

 m)

24.1-29.4ft 

l

 lbf

(32.7-39.9N 

l

 m)

5/8 inch (15.9mm)

3/8 inch (9.5mm)

1) Use the flare nut fixed to the main unit. (To prevent cracking of the flare nut by aged deterioration.)
2) To prevent gas leakage, apply refrigeration oil only to the inner surface of the flare. (Use refrigeration 

oil for R410A.)

3) Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage.

CAUTION

1.

Flaring the pipe end.

1) Cut the pipe end with a pipe cutter.
2) Remove burrs with the cut surface facing 

downward so that the chips do not enter the 
pipe.

3) Put the flare nut on the pipe.
4) Flare the pipe.
5) Check that the flaring is properly made.

1) Do not use mineral oil on flared part.
2) Prevent mineral oil from getting into the system as this would reduce the lifetime of the units.
3) Never use piping which has been used for previous installations. Only use parts which are delivered 

with the unit.

4) Never install a drier to this R410A unit in order to guarantee it’s lifetime.
5) The drying material may dissolve and damage the system.
6) Incomplete flaring may cause refrigerant gas leakage.

WARNING

Gas pipe thermal insulation

Liquid side

Gas side

Liquid pipe thermal insulation

I.D. 0.630-0.787 inch (16-20mm)

O.D. 3/8inch (9.5mm)

O.D. 5/8 inch (15.9mm)

I.D. 0.472-0.591 inch (12-15mm)

Minimum bend radius

Thickness 0.393 inch (10mm) Min.

1-3/16 inch (30mm) or more

1-15/16 inch (50mm) or more

Thickness 0.031 inch (0.8mm) (C1220T-O)

Thickness 0.039 inch (1mm) (C1220T-O)

Wall

If no flare cap is 
available, cover the 
flare mouth with 
tape to keep dirt or 
water out.

Be sure to 
place a cap.

Rain

Gas pipe

Liquid pipe

Gas pipe 
insulation

Liquid pipe 
insulation

Finishing tape

Drain hose

Inter-unit wiring

Torque wrench

Piping union

Flare nut

Do not apply refrigeration 
oil to the outer surface.

Flare nut

Apply refrigeration oil to the 
inner surface of the flare.

Do not apply refrigeration oil to the flare 
nut to avoid tightening with over torque.

Spanner

[Apply oil]

[Tighten]

(Cut exactly at 

right angles.)

 Remove burrs

Set exactly at the position shown below.

A

Flaring

Die

A

0-0.020 inch (0-0.5mm)

Clutch-type

Flare tool for R410A

0.039-0.059 inch (1.0-1.5mm)

Clutch-type (Rigid-type)

0.059-0.079 inch (1.5-2.0mm)

Wing-nut type (Imperial-type)

Conventional flare tool

Check

Flare’s inner 
surface must 
be flaw-free.

The pipe end must 
be evenly flared in 
a perfect circle.

Make sure that the 
flare nut is fitted.

Summary of Contents for M08B128

Page 1: ...stabs or other injuries Tear apart and throw away plastic packaging bags so that children will not play with them Children playing with plastic bags face the danger of death by suffocation Do not ins...

Page 2: ...ping is removed causing abnormally high pressure which could lead to equipment damage or and personal injury When installing or relocating the system be sure to keep the refrigerant circuit free from...

Page 3: ...w to remove the indoor unit Push up the marked area at the lower part of the front grille to release the claws If it is difficult to release remove the front grille Opening service lid Service lid is...

Page 4: ...ddresses 1 In the same way as when connecting to an HA system remove the metal plate electrical wiring cover 2 Cut the address jumper JA on the printed circuit board 3 Cut the address jumper J4 in the...

Page 5: ...nter unit wiring Refer to 4 Wiring 6 Press the bottom frame of the indoor unit with both hands to set it on the mounting plate hooks Make sure that the wires do not catch on the edge of the indoor uni...

Page 6: ...he conduit mounting plate 2 Insert the wires including the ground wire into J tube 3 Strip wire ends 9 16 inch 15mm 4 Match wire colors with terminal numbers on indoor and outdoor unit s terminal bloc...

Page 7: ...Flare the pipe 5 Check that the flaring is properly made 1 Do not use mineral oil on flared part 2 Prevent mineral oil from getting into the system as this would reduce the lifetime of the units 3 Nev...

Page 8: ...eration mode cooling and heating 2 Press the ON OFF button to turn on the system 3 Press the both of TEMP button and the MODE button at the same time 4 Press the MODE button twice will be displayed an...

Page 9: ...are thermally insulated Fall vibration noise Water leakage Water leakage System is properly ground to earth Electrical leakage Indoor unit properly receives remote controller commands Inoperative Indo...

Page 10: ...3P228446 2B M08B128...

Reviews: