Pump Down Operation

Trial Operation and Testing (1)

1.

Trial operation and testing.

1-1 Measure the supply voltage and make sure that it falls in the specified range.
1-2 Trial operation should be carried out in either cooling or heating mode.

1) In cooling mode, select the lowest programmable temperature; in heating mode, select the highest 

programmable temperature.
Trial operation may be disabled in either mode depending on the room temperature.
In that case, use the remote controller for trial operation as described below.

2) After trial operation is complete, set the temperature to a normal level (78˚F to 82˚F (26˚C to 28˚C)in cooling 

mode, 68˚F to 75˚F (20˚C to 24˚C) in heating mode).

• For protection, the system disables restart operation for 3 minutes after it is turned off.

1-3 Carry out the test operation in accordance with the operation manual to ensure that all functions and 

parts, such as louver movement, are working properly.

• The air conditioner requires a small amount of power in its standby mode.  If the system is not to be used for 

some time after installation, shut off the circuit breaker to eliminate unnecessary power consumption.

• If the circuit breaker trips to shut off the power to the air conditioner, the system will restore the original 

operation mode when the circuit breaker is opened again.

Trial operation from remote controller.

1) Press the MODE button and select the trial operation mode. (cooling and heating). 

2) Press the ON/OFF button to turn on the system.

3) Press the both of TEMP button and the MODE button at the same time. 

4) Press the MODE button twice. (    will be displayed and the unit will enter test run mode.)

• Test run mode will stop automatically after around 30 minutes. To stop test run mode, press the 

ON/OFF button.

1) After closing the liquid stop valve, close the gas stop valve within 3 minutes, then stop the forced operation.

CAUTION

In order to protect the environment, be sure to pump down when relocating or disposing of the unit.

1) Remove the valve cap from liquid stop valve and gas stop valve.
2) Carry out forced cooling operation.
3) After 5 to 10 minutes, close the liquid stop valve with a hexagonal wrench.
4) After 2 to 3 minutes, close the gas stop valve and stop forced cooling operation.

How to force cooling operation mode

n

Using the indoor unit ON/OFF switch

Press the indoor unit ON/OFF switch for at least 5 seconds. (Operation will start.)

• Forced cooling operation will stop automatically after around 15 minutes.

To stop force cooling operation, press the indoor unit ON/OFF switch.

n

Using the main unit’s remote controller

1) Press the MODE button and select the cooling mode. 
2) Press the ON/OFF button to turn on the system.
3) Press the both of TEMP button and the MODE button at the same time. 
4) Press the MODE button twice. (    will be displayed and the unit will enter test run mode.) 

• Test run mode will stop automatically after around 30 minutes. To stop test run mode, press the 

ON/OFF button.

Gas 
stop valve

Valve cap

Hexagonal 
wrench

Close

Liquid 
stop valve

Summary of Contents for M08B128

Page 1: ...stabs or other injuries Tear apart and throw away plastic packaging bags so that children will not play with them Children playing with plastic bags face the danger of death by suffocation Do not ins...

Page 2: ...ping is removed causing abnormally high pressure which could lead to equipment damage or and personal injury When installing or relocating the system be sure to keep the refrigerant circuit free from...

Page 3: ...w to remove the indoor unit Push up the marked area at the lower part of the front grille to release the claws If it is difficult to release remove the front grille Opening service lid Service lid is...

Page 4: ...ddresses 1 In the same way as when connecting to an HA system remove the metal plate electrical wiring cover 2 Cut the address jumper JA on the printed circuit board 3 Cut the address jumper J4 in the...

Page 5: ...nter unit wiring Refer to 4 Wiring 6 Press the bottom frame of the indoor unit with both hands to set it on the mounting plate hooks Make sure that the wires do not catch on the edge of the indoor uni...

Page 6: ...he conduit mounting plate 2 Insert the wires including the ground wire into J tube 3 Strip wire ends 9 16 inch 15mm 4 Match wire colors with terminal numbers on indoor and outdoor unit s terminal bloc...

Page 7: ...Flare the pipe 5 Check that the flaring is properly made 1 Do not use mineral oil on flared part 2 Prevent mineral oil from getting into the system as this would reduce the lifetime of the units 3 Nev...

Page 8: ...eration mode cooling and heating 2 Press the ON OFF button to turn on the system 3 Press the both of TEMP button and the MODE button at the same time 4 Press the MODE button twice will be displayed an...

Page 9: ...are thermally insulated Fall vibration noise Water leakage Water leakage System is properly ground to earth Electrical leakage Indoor unit properly receives remote controller commands Inoperative Indo...

Page 10: ...3P228446 2B M08B128...

Reviews: