background image

4

contact the local office of the EPA.

National Codes

This product is designed and manufactured to permit 

installation in accordance with National Codes.  It is the 

installer’s responsibility to install the product in accordance 

with National Codes and/or prevailing local codes and 

regulations. 

The heating and cooling capacities of the unit should be 

greater than or equal to the design heating and cooling 

loads of the area to be conditioned. The loads should be 

calculated by an approved method or in accordance with 

ASHRAE Guide or Manual J - Load Calculations published 

by the Air Conditioning Contractors of America.

Obtain from:

American National Standards Institute

25 West 43rd Street, 4th Floor

New York, NY 10036 

www.ansi.org

System design and installation should also, where 

applicable, follow information presented in accepted 

industry guides such as the ASHRAE Handbooks. The 

manufacturer assumes no responsibility for equipment 

installed in violation of any code or regulation. The 

mechanical installation of the packaged roof top units 

consists of making final connections between the unit and 

building services; supply and return duct connections; and 

drain connections (if required).  The internal systems of 

the unit are completely factory-installed and tested prior to 

shipment.

Units are generally installed on a steel roof mounting 

curb assembly which has been shipped to the job site for 

installation on the roof structure prior to the arrival of the 

unit.  The model number shown on the unit’s identification 

plate identifies the various components of the unit such as 

refrigeration tonnage, heating output and voltage.

Carefully inspect the unit for damage including damage 

to the cabinetry.  Any bolts or screws which may have 

loosened in transit must be re-tightened.  

In the event of damage, the receiver should:

1. 

Make notation on delivery receipt of any visible 

damage to shipment or container.

2.  Notify carrier promptly and request an inspection.

3. 

In case of concealed damage, carrier should be 

notified as soon as possible-preferably within 5 days.

4.  File the claim with the following supporting 

documents:

a.  Original Bill of Lading, certified copy, or 

indemnity bond.

b. 

Original paid freight bill or indemnity in lieu 

thereof. 

c.  Original invoice or certified copy thereof, 

showing trade and other discounts or 

reductions.

d. 

Copy of the inspection report issued by carrier 

representative at the time damage is reported 

to the carrier. The carrier is responsible for 

making prompt inspection of damage and for 

a thorough investigation of each claim. The 

distributor or manufacturer will not accept 

claims from dealers for transportation damage.

NOTE: When inspecting the unit for 

transportation damage, remove all packaging 

materials. Recycle or dispose  of the packaging 

material according to local codes.

MAJOR COMPONENTS

The unit includes a hermetically sealed refrigerating system 

(consisting of a compressor, condenser coil, evaporator 

coil with flowrator), an indoor blower, a condenser fan, and 

all necessary internal electrical wiring.  The heat pump also 

includes a reversing valve, solenoid, defrost thermostat 

and control and loss of charge protection.  The system 

is factory-evacuated, charged and performance tested.  

Refrigerant amount and type are indicated on rating plate.

INSTALLATION

Pre-Installation Checkpoints

Carefully read all instructions for the installation prior 

to installing unit. Ensure each step or procedure is 

understood and any special considerations are taken into 

account before starting installation.  Assemble all tools, 

hardware and supplies needed to complete the installation. 

Some items may need to be purchased locally.

Before attempting any installation, the following points 

should be considered:

• 

 Structural strength of supporting members

•  Clearances and provision for servicing

• 

 Power supply and wiring

•  Air duct connections

•  Drain facilities and connections

•  Location may be on any four sides of a home, 

manufactured or modular, to minimize noise

UNIT LOCATION

WARNING

To prevent possible equipment damage, property 

damage, personal injury or death, the following 

bullet points must be observed when installing 

the unit. 

IMPORTANT NOTE: Remove wood shipping rails 

prior to installation of the unit.

NOTE:  Appliance is shipped from factory for 

vertical duct application. 

Summary of Contents for M Series

Page 1: ...N THIS MANUAL SHOULD SERVICE THE EQUIPMENT THE MANUFACTURER WILL NOT BE RESPONSIBLE FOR ANY INJURY OR PROPERTY DAMAGE ARISING FROM IMPROPER SERVICE OR SERVICE PROCEDURES IF YOU SERVICE THIS UNIT YOU A...

Page 2: ...MENT PARTS Ordering Parts When reporting shortages or damages or ordering repair parts give the complete unit model and serial numbers as stamped on the unit s nameplate Replacement parts for this app...

Page 3: ...ng or installing this unit Multiple power sources may be present Failure to do so may cause property damage personal injury or death WARNING To prevent the risk of property damage personal injury or d...

Page 4: ...ly within 5 days 4 File the claim with the following supporting documents a Original Bill of Lading certified copy or indemnity bond b Original paid freight bill or indemnity in lieu thereof c Origina...

Page 5: ...ses have holes under the outdoor coil to permit drainage of defrost water accumulation The unit must be situated to permit free unobstructed drainage of the defrost water and ice A minimum of 2 cleara...

Page 6: ...36 minimum clearance is required between the condenser coils Adequate clearance around the unit should be kept for safety service maintenance and proper unit operation A clearance of 48 is recommende...

Page 7: ...bserved when installing the unit Provisions for forks have been included in the unit base frame No other fork locations are approved Unit must be lifted by the four lifting holes located at the base f...

Page 8: ...is unit Multiple power sources may be present Failure to do so may cause property damage personal injury or death WARNING HIGH VOLTAGE To avoid personal injury or death due to electrical shock do not...

Page 9: ...t the power leads at the point of distribution in accordance with the unit data plate The unit must be electrically grounded in accordance with local codes or in the absence of local codes with the la...

Page 10: ...ever connecting thermostat wires to terminals on sub base DO NOT use larger than 18 AWG wire A transition to 18 AWG wire may be required before entering thermostat sub base NOTE Refer to unit wiring d...

Page 11: ...must first be performed in accordance with this manual Damage or repairs due to failure to comply with these requirements are not covered under the warranty After the machines are used for temporary h...

Page 12: ...airflow setting to be between 300 and 500 CFM per ton see Table below For models with electric heat the total airflow must not be less than that required for operation of the electric heaters See App...

Page 13: ...quid small line near liquid line access fitting with adequate contact and insulate for best possible reading 3 Check subcooling and superheat System should have a subcooling and superheat within the r...

Page 14: ...operation if outdoor ambient is mild If the outdoor ambient is low and the unit operates properly in the heating cycle you may check the pressure cutout operation by blocking off the indoor return air...

Page 15: ...surfaces of the outdoor coil under certain weather conditions of temperature and relative humidity Therefore it is necessary to reverse the flow of the refrigerant to provide hot gas in the outdoor co...

Page 16: ...for Electrical Failure 1 Place unit into the cooling mode Test for 24 volts at the solenoid If there is no voltage present at coil check the control voltage 2 If voltage is present loosen the nut on...

Page 17: ...be made at least every two months more often if necessary because of local conditions and usage Dirty throwaway filters should be discarded and replaced with a new clean filter Disposable return air f...

Page 18: ...18 Wiring Example Electric Heat Wiring Example...

Page 19: ...2080 939 0 74 0 4 2056 952 0 75 0 6 1973 1000 0 79 0 6 1967 1003 0 79 0 8 1887 1048 0 83 0 8 1890 1051 0 83 T3 0 2 2176 878 0 69 T3 0 2 2145 902 0 71 0 4 2080 939 0 74 0 4 2056 952 0 75 0 6 1973 1000...

Page 20: ...2 6 5 119 129 125 150 134 148 150 150 7 2 6 5 142 155 150 175 6 9 1 0 3 3 5 Direct Drive Standard Static 1 GPH1660M 208 230 1 60 1 26 9 152 9 EH 1S15 11 3 15 0 54 2 62 5 EH 1S20 15 0 20 0 72 2 83 3 EH...

Page 21: ...RB LOCATION EMBOSS FOR THRU THE BASE UTILITIES RETURN 11 X 25 SUPPLY 12 X 17 Horizontal Discharge Vertical Discharge NOTE Refer to IOD 7082 included in the literature pack for installing horizontal du...

Page 22: ...lectric Heater Heater Type X Staged S SCR modulating Voltage 1 208 230 1 60 Single phase 60 Hz Chassis S Small Kilowatt 5 5 kW 10 10 kW 15 15 kW 18 18 KW 20 20 kW 30 30 kW EH S05 5 1500 EH S10 10 1500...

Page 23: ...1 F1 BK RD 208 230V 1PH 60Hz L1 L2 T1 T2 C S CM BR RD GR BK GR RD FB3 F3 F3 5 BK RD RD YL BR BK PU BK RD PU BK 5 L1 L2 T1 T2 BK BC COMP RC COM H F PU PU CMC L1 L2 T1 T2 FB2 F2 F2 BK RD BK RD BK PU BR...

Page 24: ...LP Liquid Propane Residential Package Outdoor Section ELECTRICAL Supply Voltage Measure L1 and L2 Voltage L1 L2 Compressor Amps Condenser Fan Amps PRESSURES TEMPERATURES Suction Circuit Pressure Suct...

Page 25: ...25 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 26: ...26 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 27: ...27 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 28: ...OODMAN BRAND AMANA BRAND GOODMAN BRAND AMANA BRAND PRODUCT REGISTRATION Thank you for your recent purchase Though not required to get the protection of the standard warranty registering your product i...

Reviews: