background image

12

Nameplate Voltage - 

That voltage assigned to a piece of 

equipment for the purpose of designating its voltage class 

and for the purpose of defining the minimum and maximum 

voltage at which the equipment will operate.

Utilization Voltage - 

The voltage of the line terminals 

of the equipment at which the equipment must give fully 

satisfactory performance. Once it is established that supply 

voltage will be maintained within the utilization range under 

all system conditions, check and calculate if an unbalanced 

condition exists between phases. Calculate percent voltage 

unbalance as follows: 

TOTAL EXTERNAL STATIC PRESSURE 

CHECK

The total external static pressure must be checked on this 

unit to determine if the airflow is proper.

Total External Static Testing

1. 

Using a digital manometer measure the static 

pressure of the return duct at the inlet of the unit 

(Negative Pressure).  

Total External Static

2. 

Measure the static pressure of the supply duct 

(Positive Pressure).

3.  Add the two readings together

NOTE: Both readings may be taken simultaneously 

and read directly on the manometer if so desired.

4.  Consult proper table for quantity of air.

If the external static pressure exceeds the minimum or 

maximum allowable statics, check for closed dampers, dirty 

filter, undersized or poorly laid out ductwork.

AIR FLOW ADJUSTMENTS

When the final adjustments are complete, the current 

draw of the motor should be checked and compared to 

the full load current rating of the motor. The amperage 

must not exceed the service factor stamped on the motor 

nameplate. 

If an economizer is installed, check the unit operating 

balance with the economizer at full outside air and at 

minimum outside air.

High stage airflow setting to be between 300 and 500 

CFM per ton, see Table below. For models with electric 

heat the total airflow must not be less than that required 

for operation of the electric heaters. See Appendix D for 

minimum airflow for specific electric heaters. 

NOTE: Never run CFM below 300 CFM per ton, 

evaporator freezing or poor unit performance is 

possible.

Model

Minimum

Maximum

GPHM56041

1500

1850

2500

Nominal

High Stage Airflow Setting, CFM 

(without electric heat) 

EEM - Standard Static Drive Motor

Adjust the CFM for the unit by changing the position of 

the low voltage leads on the terminal block TB1. Refer to 

Appendix A for blower performance at each speed tap 

 

NOTE: If more than one lead is energized 

simultaneously, the motor will run at the higher 

speed.

Fan speed for G (Fan), Y1 (Low Cool) and W1 (Low Heat) 

are fixed setting on TB1/T1 and cannot be moved.

Purple wire Y2 (High Cool) and Brown wire W2 (High Heat) 

are connected to TB1/T2. These wires can be moved 

together or separately and placed on any unoccupied 

terminal T3-T5.

Note: for proper operation Y2 and W2 should have a higher 

speed setting than the G, Y1 and W1 speed setting.

If Electric Heater kit is installed use the red wire provided 

with the literature kit to jumper terminal TB1/W1 to an 

unoccupied speed tap that satisfies the minimum airflow 

required for the heater kit. This must be a different tap 

than Y2 is connected to. Refer to Appendix D for minimum 

required airflow for electric heaters.

Note: On Heat Pump units, the Yellow (YL) wire 

from relay BR1 to TB1/T2 must always be moved 

to the same terminal location as the Brown (BR) 

wire after adjustments are made, to ensure 

proper blower speed during defrost operation. 

SUPERHEAT AND SUBCOOLING

Checking Subcooling

NOTE: Units with a TXV should be charged to 

Subcooling only.

EXAMPLE:

a. Liquid Line Pressure = 417 PSI

b. Corresponding Temp. = 120°F

c. Thermometer on Liquid line = 109°F.

Summary of Contents for M Series

Page 1: ...N THIS MANUAL SHOULD SERVICE THE EQUIPMENT THE MANUFACTURER WILL NOT BE RESPONSIBLE FOR ANY INJURY OR PROPERTY DAMAGE ARISING FROM IMPROPER SERVICE OR SERVICE PROCEDURES IF YOU SERVICE THIS UNIT YOU A...

Page 2: ...MENT PARTS Ordering Parts When reporting shortages or damages or ordering repair parts give the complete unit model and serial numbers as stamped on the unit s nameplate Replacement parts for this app...

Page 3: ...ng or installing this unit Multiple power sources may be present Failure to do so may cause property damage personal injury or death WARNING To prevent the risk of property damage personal injury or d...

Page 4: ...ly within 5 days 4 File the claim with the following supporting documents a Original Bill of Lading certified copy or indemnity bond b Original paid freight bill or indemnity in lieu thereof c Origina...

Page 5: ...ses have holes under the outdoor coil to permit drainage of defrost water accumulation The unit must be situated to permit free unobstructed drainage of the defrost water and ice A minimum of 2 cleara...

Page 6: ...36 minimum clearance is required between the condenser coils Adequate clearance around the unit should be kept for safety service maintenance and proper unit operation A clearance of 48 is recommende...

Page 7: ...bserved when installing the unit Provisions for forks have been included in the unit base frame No other fork locations are approved Unit must be lifted by the four lifting holes located at the base f...

Page 8: ...is unit Multiple power sources may be present Failure to do so may cause property damage personal injury or death WARNING HIGH VOLTAGE To avoid personal injury or death due to electrical shock do not...

Page 9: ...t the power leads at the point of distribution in accordance with the unit data plate The unit must be electrically grounded in accordance with local codes or in the absence of local codes with the la...

Page 10: ...ever connecting thermostat wires to terminals on sub base DO NOT use larger than 18 AWG wire A transition to 18 AWG wire may be required before entering thermostat sub base NOTE Refer to unit wiring d...

Page 11: ...must first be performed in accordance with this manual Damage or repairs due to failure to comply with these requirements are not covered under the warranty After the machines are used for temporary h...

Page 12: ...airflow setting to be between 300 and 500 CFM per ton see Table below For models with electric heat the total airflow must not be less than that required for operation of the electric heaters See App...

Page 13: ...quid small line near liquid line access fitting with adequate contact and insulate for best possible reading 3 Check subcooling and superheat System should have a subcooling and superheat within the r...

Page 14: ...operation if outdoor ambient is mild If the outdoor ambient is low and the unit operates properly in the heating cycle you may check the pressure cutout operation by blocking off the indoor return air...

Page 15: ...surfaces of the outdoor coil under certain weather conditions of temperature and relative humidity Therefore it is necessary to reverse the flow of the refrigerant to provide hot gas in the outdoor co...

Page 16: ...for Electrical Failure 1 Place unit into the cooling mode Test for 24 volts at the solenoid If there is no voltage present at coil check the control voltage 2 If voltage is present loosen the nut on...

Page 17: ...be made at least every two months more often if necessary because of local conditions and usage Dirty throwaway filters should be discarded and replaced with a new clean filter Disposable return air f...

Page 18: ...18 Wiring Example Electric Heat Wiring Example...

Page 19: ...2080 939 0 74 0 4 2056 952 0 75 0 6 1973 1000 0 79 0 6 1967 1003 0 79 0 8 1887 1048 0 83 0 8 1890 1051 0 83 T3 0 2 2176 878 0 69 T3 0 2 2145 902 0 71 0 4 2080 939 0 74 0 4 2056 952 0 75 0 6 1973 1000...

Page 20: ...2 6 5 119 129 125 150 134 148 150 150 7 2 6 5 142 155 150 175 6 9 1 0 3 3 5 Direct Drive Standard Static 1 GPH1660M 208 230 1 60 1 26 9 152 9 EH 1S15 11 3 15 0 54 2 62 5 EH 1S20 15 0 20 0 72 2 83 3 EH...

Page 21: ...RB LOCATION EMBOSS FOR THRU THE BASE UTILITIES RETURN 11 X 25 SUPPLY 12 X 17 Horizontal Discharge Vertical Discharge NOTE Refer to IOD 7082 included in the literature pack for installing horizontal du...

Page 22: ...lectric Heater Heater Type X Staged S SCR modulating Voltage 1 208 230 1 60 Single phase 60 Hz Chassis S Small Kilowatt 5 5 kW 10 10 kW 15 15 kW 18 18 KW 20 20 kW 30 30 kW EH S05 5 1500 EH S10 10 1500...

Page 23: ...1 F1 BK RD 208 230V 1PH 60Hz L1 L2 T1 T2 C S CM BR RD GR BK GR RD FB3 F3 F3 5 BK RD RD YL BR BK PU BK RD PU BK 5 L1 L2 T1 T2 BK BC COMP RC COM H F PU PU CMC L1 L2 T1 T2 FB2 F2 F2 BK RD BK RD BK PU BR...

Page 24: ...LP Liquid Propane Residential Package Outdoor Section ELECTRICAL Supply Voltage Measure L1 and L2 Voltage L1 L2 Compressor Amps Condenser Fan Amps PRESSURES TEMPERATURES Suction Circuit Pressure Suct...

Page 25: ...25 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 26: ...26 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 27: ...27 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 28: ...OODMAN BRAND AMANA BRAND GOODMAN BRAND AMANA BRAND PRODUCT REGISTRATION Thank you for your recent purchase Though not required to get the protection of the standard warranty registering your product i...

Reviews: