background image

14

8.  Turn the thermostat system switch to “OFF” and 

disconnect all power when servicing the unit.

 

WARNING

HIGH VOLTAGE!

Disconnect all power before 

servicing or installing this unit.  

Multiple power sources may be 

present.  Failure to do so may cause 

property damage, personal injury or 

death.

 

Heat Pump Start-Up Procedure 

1. 

Check the cooling mode for the heat pump in 

the same manner as above. The reversing valve 

is energized when the thermostat is placed in 

the cooling position. A clicking sound should be 

noticeable from the reversing valve. By lowering the 

temperature setting to call for cooling, the solenoid 

valve is energized. The compressor, blower and fan 

should then be running. After the cooling mode is 

checked out, turn the thermostat system switch to 

“OFF”.

2.  Turn the thermostat system switch to “HEAT” and fan 

switch to “AUTO”.

3.  Slowly raise the heating temperature setting. When 

the heating first stage makes contact, stop raising 

the temperature setting.. The compressor, blower 

and fan should now be running with the reversing 

valve in the deenergized (heating) position. After 

giving the unit time to settle out, make sure the unit 

is supplying heated air.

4.  If the outdoor ambient is above 80°F, the unit may 

trip on its high-pressure cutout when in heating 

mode.  The compressor should stop. The heating 

cycle must be thoroughly checked, so postpone 

the test to another day when conditions are more 

suitable but, DO NOT FAIL TO TEST.

5.  If the outdoor ambient is low and the unit operates 

properly in the heating cycle, you may check the 

pressure cutout operation by blocking off the indoor 

return air until the unit trips.

6. 

If unit operates properly in the heating cycle, raise 

the temperature setting until the heating second 

stage makes contact.  Supplemental resistance 

heat, if installed should now come on. Make sure it 

operates properly.

NOTE:  15.2  SEER2  model  has  two  stages  of 

compressor  heat.  During  resistance  heat  test, 

increase temperature setting until third stage heat 

is energized.

NOTE:  If  outdoor  thermostats  are  installed  the 

outdoor  ambient  must  be  below  the  set  point  of 

these  thermostats  for  the  heaters  to  operate.  It 

may be necessary to jumper these thermostats to 

check heater operation if outdoor ambient is mild.

If the outdoor ambient is low and the unit operates properly 

in the heating cycle, you may check the pressure cutout 

operation by blocking off the indoor return air until the unit 

trips.  If unit operates properly in the heating cycle, raise 

the temperature setting until the heating second stage 

makes contact.  Supplemental resistance heat, if installed 

should now come on.  Make sure it operates properly.

7.  THERMOSTATS WITH EMERGENCY HEAT. For 

thermostats with an emergency heat switch, raise 

the temperature setting until the heating second 

stage makes contact.  The emergency heat switch 

is located at the bottom of the thermostat.  Move the 

switch to emergency heat. The heat pump will stop, 

the blower will continue to run, all heaters will come 

on and the thermostat emergency heat light will 

come on.

8.  If checking the unit in the wintertime, when the 

outdoor coil is cold enough to acuate the defrost 

control, observe at least one defrost cycle to make 

sure the unit defrosts completely.

Final System Checks

1. 

Check to see if all supply and return air grilles are 

adjusted and the air distribution system is balanced 

for the best compromise between heating and 

cooling.

2.  Check for air leaks in the ductwork.

3.  Check air flow and refrigerant charge.  See Sections 

on 

Air Flow Measurement and Adjustment 

and 

Checking Charge.

4.  Ensure the unit is free of “rattles”, and the tubing 

in the unit is free from excessive vibration.  Also 

make sure tubes or lines are not rubbing against 

each other or sheet metal surfaces or edges.  If 

discovered, ensure issue is corrected.

5.  Set the thermostat at the appropriate setting for 

cooling and heating or automatic changeover for 

normal use.

6.  Ensure the Owner is instructed on the unit operation, 

filter, servicing, correct thermostat operation, etc.

NOTE:  The  “Air  Conditioner  Start-Up  Procedure” 

is  a  recommended  step  as  it  serves  as  a  system 

indicator that the unit will operate normally. 

Refrigeration Performance Check

Check that compressor RLA corresponds to values shown 

in Appendix B.  RLA draw can be much lower than values 

listed at low load conditions and low ambient condensing 

temperatures. Values in Appendix B can slightly exceed 

at high load conditions and high ambient condensing 

temperatures.

HEAT PUMP OPERATION

Cooling Cycle

 

When the heat pump is in the cooling cycle, it operates 

exactly as an Air Conditioner Unit.  

Summary of Contents for M Series

Page 1: ...N THIS MANUAL SHOULD SERVICE THE EQUIPMENT THE MANUFACTURER WILL NOT BE RESPONSIBLE FOR ANY INJURY OR PROPERTY DAMAGE ARISING FROM IMPROPER SERVICE OR SERVICE PROCEDURES IF YOU SERVICE THIS UNIT YOU A...

Page 2: ...MENT PARTS Ordering Parts When reporting shortages or damages or ordering repair parts give the complete unit model and serial numbers as stamped on the unit s nameplate Replacement parts for this app...

Page 3: ...ng or installing this unit Multiple power sources may be present Failure to do so may cause property damage personal injury or death WARNING To prevent the risk of property damage personal injury or d...

Page 4: ...ly within 5 days 4 File the claim with the following supporting documents a Original Bill of Lading certified copy or indemnity bond b Original paid freight bill or indemnity in lieu thereof c Origina...

Page 5: ...ses have holes under the outdoor coil to permit drainage of defrost water accumulation The unit must be situated to permit free unobstructed drainage of the defrost water and ice A minimum of 2 cleara...

Page 6: ...36 minimum clearance is required between the condenser coils Adequate clearance around the unit should be kept for safety service maintenance and proper unit operation A clearance of 48 is recommende...

Page 7: ...bserved when installing the unit Provisions for forks have been included in the unit base frame No other fork locations are approved Unit must be lifted by the four lifting holes located at the base f...

Page 8: ...is unit Multiple power sources may be present Failure to do so may cause property damage personal injury or death WARNING HIGH VOLTAGE To avoid personal injury or death due to electrical shock do not...

Page 9: ...t the power leads at the point of distribution in accordance with the unit data plate The unit must be electrically grounded in accordance with local codes or in the absence of local codes with the la...

Page 10: ...ever connecting thermostat wires to terminals on sub base DO NOT use larger than 18 AWG wire A transition to 18 AWG wire may be required before entering thermostat sub base NOTE Refer to unit wiring d...

Page 11: ...must first be performed in accordance with this manual Damage or repairs due to failure to comply with these requirements are not covered under the warranty After the machines are used for temporary h...

Page 12: ...airflow setting to be between 300 and 500 CFM per ton see Table below For models with electric heat the total airflow must not be less than that required for operation of the electric heaters See App...

Page 13: ...quid small line near liquid line access fitting with adequate contact and insulate for best possible reading 3 Check subcooling and superheat System should have a subcooling and superheat within the r...

Page 14: ...operation if outdoor ambient is mild If the outdoor ambient is low and the unit operates properly in the heating cycle you may check the pressure cutout operation by blocking off the indoor return air...

Page 15: ...surfaces of the outdoor coil under certain weather conditions of temperature and relative humidity Therefore it is necessary to reverse the flow of the refrigerant to provide hot gas in the outdoor co...

Page 16: ...for Electrical Failure 1 Place unit into the cooling mode Test for 24 volts at the solenoid If there is no voltage present at coil check the control voltage 2 If voltage is present loosen the nut on...

Page 17: ...be made at least every two months more often if necessary because of local conditions and usage Dirty throwaway filters should be discarded and replaced with a new clean filter Disposable return air f...

Page 18: ...18 Wiring Example Electric Heat Wiring Example...

Page 19: ...2080 939 0 74 0 4 2056 952 0 75 0 6 1973 1000 0 79 0 6 1967 1003 0 79 0 8 1887 1048 0 83 0 8 1890 1051 0 83 T3 0 2 2176 878 0 69 T3 0 2 2145 902 0 71 0 4 2080 939 0 74 0 4 2056 952 0 75 0 6 1973 1000...

Page 20: ...2 6 5 119 129 125 150 134 148 150 150 7 2 6 5 142 155 150 175 6 9 1 0 3 3 5 Direct Drive Standard Static 1 GPH1660M 208 230 1 60 1 26 9 152 9 EH 1S15 11 3 15 0 54 2 62 5 EH 1S20 15 0 20 0 72 2 83 3 EH...

Page 21: ...RB LOCATION EMBOSS FOR THRU THE BASE UTILITIES RETURN 11 X 25 SUPPLY 12 X 17 Horizontal Discharge Vertical Discharge NOTE Refer to IOD 7082 included in the literature pack for installing horizontal du...

Page 22: ...lectric Heater Heater Type X Staged S SCR modulating Voltage 1 208 230 1 60 Single phase 60 Hz Chassis S Small Kilowatt 5 5 kW 10 10 kW 15 15 kW 18 18 KW 20 20 kW 30 30 kW EH S05 5 1500 EH S10 10 1500...

Page 23: ...1 F1 BK RD 208 230V 1PH 60Hz L1 L2 T1 T2 C S CM BR RD GR BK GR RD FB3 F3 F3 5 BK RD RD YL BR BK PU BK RD PU BK 5 L1 L2 T1 T2 BK BC COMP RC COM H F PU PU CMC L1 L2 T1 T2 FB2 F2 F2 BK RD BK RD BK PU BR...

Page 24: ...LP Liquid Propane Residential Package Outdoor Section ELECTRICAL Supply Voltage Measure L1 and L2 Voltage L1 L2 Compressor Amps Condenser Fan Amps PRESSURES TEMPERATURES Suction Circuit Pressure Suct...

Page 25: ...25 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 26: ...26 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 27: ...27 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 28: ...OODMAN BRAND AMANA BRAND GOODMAN BRAND AMANA BRAND PRODUCT REGISTRATION Thank you for your recent purchase Though not required to get the protection of the standard warranty registering your product i...

Reviews: