background image

10

nuts) to prevent water leakage into building.  All required 

conduit and fittings are to be field supplied.

Supply voltage to roof top unit must not vary by more than 

10% of the value indicated on the unit data plate.  Phase 

voltage unbalance must not exceed 2%.  Contact your 

local power company for correction of improper voltage or 

phase unbalance.

4-1/2"

47-9/16"

7-1/2"

4-1/16 DIA.

POWER THRU

THE CURB

RETURN

19-3/8

31-3/8

LOW VOLTAGE

ENTRANCE

HIGH VOLTAGE ENTRANCE

(REMOVE PLUG)

electrical entrance and thru curb

(bottom view of unit) 

Low Voltage Control Wiring 

1.  A 24V thermostat must be installed for unit operation.

2. 

Locate thermostat or remote sensor in the 

conditioned space where it will sense average 

temperature. Do not locate the device where it may 

be directly exposed to supply air, sunlight or other 

sources of heat. Follow installation instructions 

packaged with the thermostat.

3.  Use #18 AWG wire for 24V control wiring runs not 

exceeding 75 feet. Use #16 AWG wire for 24V 

control wiring runs not exceeding 125 feet. Use #14 

AWG wire for 24V control wiring runs not exceeding 

200 feet. Low voltage wiring may be National 

Electrical Code (NEC) Class 2 where permitted by 

local codes.

4.  Route thermostat wires from sub-base terminals 

to the unit. Control wiring should enter through the 

condenser panel opening or through curb indicated 

in “Electrical Entrance” figure. Connect thermostat 

and any accessory wiring to low voltage terminal 

block TB1 in the main control box.

NOTE:  Field-supplied conduit may need to be 

installed depending on unit/curb configuration. 

Use #18 AWG solid conductor wire whenever 

connecting thermostat wires to terminals on 

sub-base. DO NOT use larger than #18 AWG wire. 

A transition to #18 AWG wire may be required 

before entering thermostat sub-base.

 

NOTE: Refer to unit wiring diagrams for 

thermostat or remote sensor connections.

CIRCULATING AIR AND FILTERS

Ducting

Ducting work should be fabricated by the installing 

contractor in accordance with local codes.  Industry 

manuals may be used as a guide when sizing and 

designing the duct system-such as NESCA (National 

Environmental Systems Contractors Association, 1501 

Wilson., Arlington, Virginia 22209). 

The unit should be placed as close as possible to the 

space to be air-conditioned allowing clearance dimensions 

as indicated.  Ducts should run as directly as possible 

to supply and return outlets.  Use of non-flammable 

weatherproof flexible connectors on both supply and return 

connections at the unit to reduce noise transmission is 

recommended.  

CONDENSATE DRAIN PIPING

The condensate drain connection of the evaporator is a 

¾” NPT half coupling.  A trap must be provided to have 

proper condensate draining.  Install condensate drain trap 

as shown in FIGURE 9: CONDENSATE DRAIN TRAP 

PLUMBING.  Ensure drain connection is 3/4” or larger.  Do 

not operate unit without trap and ensure unit is level or 

slightly inclined toward drain. 

DRAI

N

CO

NNEC

TI

ON

UN

IT

2" M

IN

IMUM

FLEX

IB

LE

TUBI

NG-HOSE

OR

 PIPE

3" M

IN

IMUM

POSI

TI

VE

 LIQUID

SEA

IS

 R

EQ

UI

RE

D

drain connection 

Horizontal Drain 

Drainage of condensate directly onto the roof may be 

acceptable; refer to local code. It is recommended that a 

small drip pad of either stone, mortar, wood or metal be 

provided to prevent any possible damage to the roof. 

Vertical Drain

To use the bottom drain connection, remove the drain plug 

from the bottom connection and install it in the horizontal 

connection.

Summary of Contents for M Series

Page 1: ...N THIS MANUAL SHOULD SERVICE THE EQUIPMENT THE MANUFACTURER WILL NOT BE RESPONSIBLE FOR ANY INJURY OR PROPERTY DAMAGE ARISING FROM IMPROPER SERVICE OR SERVICE PROCEDURES IF YOU SERVICE THIS UNIT YOU A...

Page 2: ...MENT PARTS Ordering Parts When reporting shortages or damages or ordering repair parts give the complete unit model and serial numbers as stamped on the unit s nameplate Replacement parts for this app...

Page 3: ...ng or installing this unit Multiple power sources may be present Failure to do so may cause property damage personal injury or death WARNING To prevent the risk of property damage personal injury or d...

Page 4: ...ly within 5 days 4 File the claim with the following supporting documents a Original Bill of Lading certified copy or indemnity bond b Original paid freight bill or indemnity in lieu thereof c Origina...

Page 5: ...ses have holes under the outdoor coil to permit drainage of defrost water accumulation The unit must be situated to permit free unobstructed drainage of the defrost water and ice A minimum of 2 cleara...

Page 6: ...36 minimum clearance is required between the condenser coils Adequate clearance around the unit should be kept for safety service maintenance and proper unit operation A clearance of 48 is recommende...

Page 7: ...bserved when installing the unit Provisions for forks have been included in the unit base frame No other fork locations are approved Unit must be lifted by the four lifting holes located at the base f...

Page 8: ...is unit Multiple power sources may be present Failure to do so may cause property damage personal injury or death WARNING HIGH VOLTAGE To avoid personal injury or death due to electrical shock do not...

Page 9: ...t the power leads at the point of distribution in accordance with the unit data plate The unit must be electrically grounded in accordance with local codes or in the absence of local codes with the la...

Page 10: ...ever connecting thermostat wires to terminals on sub base DO NOT use larger than 18 AWG wire A transition to 18 AWG wire may be required before entering thermostat sub base NOTE Refer to unit wiring d...

Page 11: ...must first be performed in accordance with this manual Damage or repairs due to failure to comply with these requirements are not covered under the warranty After the machines are used for temporary h...

Page 12: ...airflow setting to be between 300 and 500 CFM per ton see Table below For models with electric heat the total airflow must not be less than that required for operation of the electric heaters See App...

Page 13: ...quid small line near liquid line access fitting with adequate contact and insulate for best possible reading 3 Check subcooling and superheat System should have a subcooling and superheat within the r...

Page 14: ...operation if outdoor ambient is mild If the outdoor ambient is low and the unit operates properly in the heating cycle you may check the pressure cutout operation by blocking off the indoor return air...

Page 15: ...surfaces of the outdoor coil under certain weather conditions of temperature and relative humidity Therefore it is necessary to reverse the flow of the refrigerant to provide hot gas in the outdoor co...

Page 16: ...for Electrical Failure 1 Place unit into the cooling mode Test for 24 volts at the solenoid If there is no voltage present at coil check the control voltage 2 If voltage is present loosen the nut on...

Page 17: ...be made at least every two months more often if necessary because of local conditions and usage Dirty throwaway filters should be discarded and replaced with a new clean filter Disposable return air f...

Page 18: ...18 Wiring Example Electric Heat Wiring Example...

Page 19: ...2080 939 0 74 0 4 2056 952 0 75 0 6 1973 1000 0 79 0 6 1967 1003 0 79 0 8 1887 1048 0 83 0 8 1890 1051 0 83 T3 0 2 2176 878 0 69 T3 0 2 2145 902 0 71 0 4 2080 939 0 74 0 4 2056 952 0 75 0 6 1973 1000...

Page 20: ...2 6 5 119 129 125 150 134 148 150 150 7 2 6 5 142 155 150 175 6 9 1 0 3 3 5 Direct Drive Standard Static 1 GPH1660M 208 230 1 60 1 26 9 152 9 EH 1S15 11 3 15 0 54 2 62 5 EH 1S20 15 0 20 0 72 2 83 3 EH...

Page 21: ...RB LOCATION EMBOSS FOR THRU THE BASE UTILITIES RETURN 11 X 25 SUPPLY 12 X 17 Horizontal Discharge Vertical Discharge NOTE Refer to IOD 7082 included in the literature pack for installing horizontal du...

Page 22: ...lectric Heater Heater Type X Staged S SCR modulating Voltage 1 208 230 1 60 Single phase 60 Hz Chassis S Small Kilowatt 5 5 kW 10 10 kW 15 15 kW 18 18 KW 20 20 kW 30 30 kW EH S05 5 1500 EH S10 10 1500...

Page 23: ...1 F1 BK RD 208 230V 1PH 60Hz L1 L2 T1 T2 C S CM BR RD GR BK GR RD FB3 F3 F3 5 BK RD RD YL BR BK PU BK RD PU BK 5 L1 L2 T1 T2 BK BC COMP RC COM H F PU PU CMC L1 L2 T1 T2 FB2 F2 F2 BK RD BK RD BK PU BR...

Page 24: ...LP Liquid Propane Residential Package Outdoor Section ELECTRICAL Supply Voltage Measure L1 and L2 Voltage L1 L2 Compressor Amps Condenser Fan Amps PRESSURES TEMPERATURES Suction Circuit Pressure Suct...

Page 25: ...25 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 26: ...26 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 27: ...27 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 28: ...OODMAN BRAND AMANA BRAND GOODMAN BRAND AMANA BRAND PRODUCT REGISTRATION Thank you for your recent purchase Though not required to get the protection of the standard warranty registering your product i...

Reviews: