background image

13

To  obtain  the  amount  of  subcooling,  subtract  109°F 

from  120°F.  The  difference  is  11°  subcooling.  See  the 

specification sheet or technical information manual for the 

design subcooling range for your unit.

SUBCOOLING FORMULA = SATURATED LIQUID LINE 

TEMPERATURE - LIQUID LINE TEMPERATURE

Checking Superheat

EXAMPLE:

a. Suction Pressure = 143 PSI

b. Corresponding Temp.  = 50°F

c. Thermometer on Suction Line = 59°F

To obtain the degrees temperature of superheat, subtract 

50.0  from  59.0°F. The  difference  is  9°  Superheat.  The  9° 

Superheat would fall in the ± range of allowable superheat.

SUPERHEAT  =  SUCTION  LINE  TEMP  -  SAT.  SUCTION 

TEMP.

Superheat Adjustment

NOTE: Superheat adjustments should not be made 

until indoor ambient conditions have stabilized.  

This could take up to 24 hours depending on 

indoor temperature and humidity.  Before checking 

superheat, run the unit in cooling for 10-15 

minutes or until refrigerant pressures stabilize.  

Use the following guidelines and methods 

to check unit operation and ensure that the 

refrigerant charge is within limits.

For TXV systems, to adjust superheat, unscrew the cover 

from the expansion valve, locate the adjustment screw, and 

turn it clockwise (in) to increase superheat or counterclock

-

wise (out) to decrease superheat.  It is recommended to 

make small adjustments at a time, 1/8-1/4 turn increments.  

Replace adjustment cap.  Wait a minimum of 10 minutes 

between adjustments to allow time for the TXV and pres

-

sures to stabilize. 

Refrigerant Charge Check

NOTE: For optimal performance, follow charging 

instructions below.

Units with (TXV) Device

Single Stage Cooling Application: Refer to the Design Su

-

perheat & Subcooling table
Two-Stage Cooling Application: Run unit on Low Stage 

cooling and refer to Design Superheat & Subcooling table.

1.  Purge gauge lines.  Connect service gauge manifold 

to access fittings.  Run system at least 10 minutes to 

allow pressure to stabilize.

2. 

Temporarily install thermometer on liquid (small) line 

near liquid line access fitting with adequate contact 

and insulate for best possible reading.

3.  Check  subcooling  and  superheat.  System  should 

have a subcooling and superheat within the range 

listed  on  the  Design  Superheat  and  Subcooling 

table.

a. If subcooling and superheat are low, adjust TXV 

superheat, then check subcooling.

  NOTE: 

To adjust superheat, turn the valve stem 

clockwise  to  increase  and  counterclockwise  to 

decrease.

b. If  subcooling  is  low  and  superheat  is  high,  add 

charge to raise subcooling then check superheat.

c. If subcooling and superheat are high, adjust TXV 

valve superheat, then check subcooling.

d. If subcooling is high and superheat is low, adjust 

TXV valve superheat and remove charge to lower 

the subcooling.

NOTE: 

Do NOT adjust the charge based on suction 

pressure unless there is a gross undercharge.

4.  Disconnect manifold set, installation is complete.

Design Superheat & Subcooling

Model

Superheat 

±2°F

Subcooling 

±1°F

Expansion 

Device

Cooling 

Stage

Outdoor 

ambient (°F)

GPHM56041

15

10

Fixed TXV

Low 

82

START-UP PROCEDURES AND CHECKLIST

WARNING

HIGH VOLTAGE!

Disconnect all power before 

servicing or installing this unit.  

Multiple power sources may be 

present.  Failure to do so may cause 

property damage, personal injury or 

death.

Begin with power turned off at all disconnects.

Air Conditioning  Start-Up Procedure

1.  Turn thermostat system switch to “Cool,” and fan 

switch to “Auto” and turn temperature setting as high 

as it will go.

2. 

Inspect all registers and set them to the normal open 

position.

3.  Turn on the electrical supply at the disconnect.
4.  Turn the fan switch to the “ON” position.  The blower 

should operate after a 7 second delay.

5.  Turn the fan switch to “AUTO” position.  The blower 

should begin ramping down after an approximate 

60-second delay.

6.  Slowly lower the cooling temperature until the unit 

starts.  The compressor, blower, and fan should now 

be operating.  Allow the unit to run 10 minutes, make 

sure cool air is being supplied by the unit.

7. 

Turn the temperature setting to the highest position, 

stopping the unit.  The indoor blower will continue to 

run for approximately 60 seconds.

Summary of Contents for M Series

Page 1: ...N THIS MANUAL SHOULD SERVICE THE EQUIPMENT THE MANUFACTURER WILL NOT BE RESPONSIBLE FOR ANY INJURY OR PROPERTY DAMAGE ARISING FROM IMPROPER SERVICE OR SERVICE PROCEDURES IF YOU SERVICE THIS UNIT YOU A...

Page 2: ...MENT PARTS Ordering Parts When reporting shortages or damages or ordering repair parts give the complete unit model and serial numbers as stamped on the unit s nameplate Replacement parts for this app...

Page 3: ...ng or installing this unit Multiple power sources may be present Failure to do so may cause property damage personal injury or death WARNING To prevent the risk of property damage personal injury or d...

Page 4: ...ly within 5 days 4 File the claim with the following supporting documents a Original Bill of Lading certified copy or indemnity bond b Original paid freight bill or indemnity in lieu thereof c Origina...

Page 5: ...ses have holes under the outdoor coil to permit drainage of defrost water accumulation The unit must be situated to permit free unobstructed drainage of the defrost water and ice A minimum of 2 cleara...

Page 6: ...36 minimum clearance is required between the condenser coils Adequate clearance around the unit should be kept for safety service maintenance and proper unit operation A clearance of 48 is recommende...

Page 7: ...bserved when installing the unit Provisions for forks have been included in the unit base frame No other fork locations are approved Unit must be lifted by the four lifting holes located at the base f...

Page 8: ...is unit Multiple power sources may be present Failure to do so may cause property damage personal injury or death WARNING HIGH VOLTAGE To avoid personal injury or death due to electrical shock do not...

Page 9: ...t the power leads at the point of distribution in accordance with the unit data plate The unit must be electrically grounded in accordance with local codes or in the absence of local codes with the la...

Page 10: ...ever connecting thermostat wires to terminals on sub base DO NOT use larger than 18 AWG wire A transition to 18 AWG wire may be required before entering thermostat sub base NOTE Refer to unit wiring d...

Page 11: ...must first be performed in accordance with this manual Damage or repairs due to failure to comply with these requirements are not covered under the warranty After the machines are used for temporary h...

Page 12: ...airflow setting to be between 300 and 500 CFM per ton see Table below For models with electric heat the total airflow must not be less than that required for operation of the electric heaters See App...

Page 13: ...quid small line near liquid line access fitting with adequate contact and insulate for best possible reading 3 Check subcooling and superheat System should have a subcooling and superheat within the r...

Page 14: ...operation if outdoor ambient is mild If the outdoor ambient is low and the unit operates properly in the heating cycle you may check the pressure cutout operation by blocking off the indoor return air...

Page 15: ...surfaces of the outdoor coil under certain weather conditions of temperature and relative humidity Therefore it is necessary to reverse the flow of the refrigerant to provide hot gas in the outdoor co...

Page 16: ...for Electrical Failure 1 Place unit into the cooling mode Test for 24 volts at the solenoid If there is no voltage present at coil check the control voltage 2 If voltage is present loosen the nut on...

Page 17: ...be made at least every two months more often if necessary because of local conditions and usage Dirty throwaway filters should be discarded and replaced with a new clean filter Disposable return air f...

Page 18: ...18 Wiring Example Electric Heat Wiring Example...

Page 19: ...2080 939 0 74 0 4 2056 952 0 75 0 6 1973 1000 0 79 0 6 1967 1003 0 79 0 8 1887 1048 0 83 0 8 1890 1051 0 83 T3 0 2 2176 878 0 69 T3 0 2 2145 902 0 71 0 4 2080 939 0 74 0 4 2056 952 0 75 0 6 1973 1000...

Page 20: ...2 6 5 119 129 125 150 134 148 150 150 7 2 6 5 142 155 150 175 6 9 1 0 3 3 5 Direct Drive Standard Static 1 GPH1660M 208 230 1 60 1 26 9 152 9 EH 1S15 11 3 15 0 54 2 62 5 EH 1S20 15 0 20 0 72 2 83 3 EH...

Page 21: ...RB LOCATION EMBOSS FOR THRU THE BASE UTILITIES RETURN 11 X 25 SUPPLY 12 X 17 Horizontal Discharge Vertical Discharge NOTE Refer to IOD 7082 included in the literature pack for installing horizontal du...

Page 22: ...lectric Heater Heater Type X Staged S SCR modulating Voltage 1 208 230 1 60 Single phase 60 Hz Chassis S Small Kilowatt 5 5 kW 10 10 kW 15 15 kW 18 18 KW 20 20 kW 30 30 kW EH S05 5 1500 EH S10 10 1500...

Page 23: ...1 F1 BK RD 208 230V 1PH 60Hz L1 L2 T1 T2 C S CM BR RD GR BK GR RD FB3 F3 F3 5 BK RD RD YL BR BK PU BK RD PU BK 5 L1 L2 T1 T2 BK BC COMP RC COM H F PU PU CMC L1 L2 T1 T2 FB2 F2 F2 BK RD BK RD BK PU BR...

Page 24: ...LP Liquid Propane Residential Package Outdoor Section ELECTRICAL Supply Voltage Measure L1 and L2 Voltage L1 L2 Compressor Amps Condenser Fan Amps PRESSURES TEMPERATURES Suction Circuit Pressure Suct...

Page 25: ...25 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 26: ...26 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 27: ...27 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 28: ...OODMAN BRAND AMANA BRAND GOODMAN BRAND AMANA BRAND PRODUCT REGISTRATION Thank you for your recent purchase Though not required to get the protection of the standard warranty registering your product i...

Reviews: