Wiring intake (knockout hole) for low voltage. See
"17.3 Guidelines when knocking out knockout
90].
Details – DIII transmission wiring
"17.5 Specifications of standard wiring components"
92].
Details – Remote operation switch
NOTICE
Remote operation switch
. The unit is factory-equipped with an operation switch
with which you can turn unit operation ON/OFF. If you want to remotely turn ON/
OFF operation of the outdoor unit, a remote operation switch is required. Use a
voltage-free contact for microcurrent (≤1 mA, 12 V DC). Connect to X5M/1+2, and
set to "Remote".
REMOTE
OFF ON
S1S
S1S
Factory-equipped operation switch:
OFF: Unit operation turned OFF
ON: Unit operation turned ON
Remote: Unit controlled (ON/OFF) with remote operation switch
Wiring remote operation switch:
Wiring
Sheathed cable (2 wires)
Vinyl cords
0.75~1.25 mm²
Maximum wiring length
130 m
Details – Remote low noise switch
NOTICE
Low noise switch
. If you want to remotely turn ON/OFF low noise operation, you
must install a low noise switch. Use a voltage-free contact for microcurrent (≤1 mA,
12 V DC).
Low noise switch
Mode
OFF
Normal mode
ON
Low noise mode
Wiring low noise switch:
Wiring
Sheathed cable (2 wires)
Vinyl cords
0.75~1.25 mm²
Maximum wiring length
130 m