17
|
Electrical installation
Installer and user reference guide
98
LRYELRNUN5A7Y1
CO₂ Conveni-Pack outdoor unit
4P605460-1 – 2020.08
REMOTE
OFF ON
S1S
S1S
Factory-equipped operation switch:
OFF: Unit operation turned OFF
ON: Unit operation turned ON
Remote: Unit controlled (ON/OFF) with remote operation switch
Wiring remote operation switch:
Wiring
Sheathed cable (2 wires)
Vinyl cords
0.75~1.25 mm²
Maximum wiring length
130 m
Details – Remote low noise switch:
NOTICE
Low noise switch
. If you want to remotely turn ON/OFF low noise operation, you
must install a low noise switch. Use a voltage-free contact for microcurrent (≤1 mA,
12 V DC).
Low noise switch
Mode
OFF
Normal mode
ON
Low noise mode
Wiring low noise switch:
Wiring
Sheathed cable (2 wires)
Vinyl cords
0.75~1.25 mm²
Maximum wiring length
130 m