16
|
Piping installation
Installer and user reference guide
66
LRYELRNUN5A7Y1
CO₂ Conveni-Pack outdoor unit
4P605460-1 – 2020.08
Requirement
Limit
LRYEN10*
LRYEN10* +
LRNUN5*
Maximum piping length
Examples:
▪
A+B+C+D+(E or F)
(a)
≤Limit
▪
a+c+d+(e or f)
(a)
≤Limit
▪
A2+B2+(C2 or D2)
(a)
≤Limit
▪
a2+b2+(c2 or d2)
(a)
≤Limit
Refrigeration side: 130 m
(b)
Air conditioning side: 130 m
Piping length between
LRYEN10*
and
LRNUN5*
Not specified, but piping must be
horizontal
Maximum branch piping length
▪
Example refrigeration side:
-
C+D+(E or F)
(a)
-
c+d+(e or f)
(a)
-
c+g
-
j
▪
Example air conditioner side:
-
B2+(C2 or D2)
(a)
-
b2+(c2 or d2)
(a)
Refrigeration side: 50 m
Air conditioning side: 30 m
Maximum height
difference
between outdoor
unit and indoor
unit
(b)
Outdoor higher
than indoor
Example: H2,
H4≤Limit
35 m
Outdoor unit lower
than indoor unit
Example: H2,
H4≤Limit
10 m
Maximum height difference between
blower coil and showcase
▪
Example: H3≤Limit
5 m
Maximum height difference between
air conditioners
▪
Example: H1≤Limit
0.5 m
(a)
Whichever is longer
(b)
For low load restrictions, see
"14.5.2 Constraints for refrigeration"
49].
To install an oil trap
If the outdoor unit is installed higher than the indoor unit, install an oil trap in the
gas piping every 5 meter. Oil traps will make the oil return more easily.