7
|
Operation
Installer and user reference guide
27
LRYELRNUN5A7Y1
CO₂ Conveni-Pack outdoor unit
4P605460-1 – 2020.08
7 Operation
7.1 Operation range
Use the system in the following temperature ranges for safe and effective
operation.
Refrigeration
A/C cooling
A/C heating
Outdoor
temperature
–20~43°C DB
(a)
–5~43°C DB
–20~16°C WB
Indoor
temperature
—
14~24°C WB
15~27°C DB
(a)
For low load restrictions, see
"14.5.2 Constraints for refrigeration"
7.2 Design pressure
Always keep the following design pressures in mind:
Side
Design pressure
Refrigeration
90 bar
Air conditioning
120 bar