Fresh air intake kit - KDDP55D160-2

*1. Hang and 

fi

 x the T-tube assembly for installation. The load of the T-tube assembly may create a clearance between the indoor unit and suction 

chamber. 
*2. Install the inspection hatch (450 x 450 mm or more). Either one of the inspection hatches must be installed.

Indoor unit

Standard Decoration panel

Designer Decoration panel

SPLIT

A (mm)

FCAG35-71B

264

306

FXFQ20-63B

FCAG100-140B

306

348

FXFQ80-100B

FCAHG71-140H

348

390

FXFQ125B

(2) Install the inspection hatch (unit: mm).

Inspection hatch 450 x 450 mm or more
(See note *2.)

Inspection hatch 450 x 450 mm or more
(See note *2.)

T-tube assembly
(Field supply)

725

2. Installation of sensor assembly and suction chamber

When the indoor unit is already installed, perform the following operations in accordance with the precautions below.

 

Make sure to turn off the power supply before starting the operation.

 

Remove the decoration panel from the indoor unit. (For details, please refer to the installation manual provided with the decoration panel.)

Installation of sensor assembly

1.  Refer to the installation manual of the indoor unit, remove the control box lid of indoor unit.
2.  Install the sensor assembly on bell mouth of the indoor unit using the provided screws.
3.  Remove the connector (X16A) of the existing sensor from the printed circuit board of the indoor unit.
4.  Connect the wire harness of the sensor assembly that was attached to the indoor unit to the connector (X16A) on the printed circuit board of the 

indoor unit.

5.  Use the provided clamps to 

fi

 x the wire harness (to the other wire harness) as shown in the 

fi

 gure below.

6.  When all wiring operations are completed, install the control box lid in accordance with the installation manual provided with the air conditioner.

Sensor assembly

Screw

Control box lid
1. Remove the control box lid.
(Screw - 2 positions)

Bell mouth

2. Fix the sensor assembly
on bell mouth using
the provided screws.

3. Remove the connector
of the existing sensor.
4. Connect the connector
of the sensor assembly that
was installed.

Sensor wire harness

Sensor assembly

Bell mouth

Installation of suction chamber

The 

fi

 gure shows the installation procedure for a new indoor unit.

1.  Adhere the desiccant tape to the corner air outlet sealing material, and then attach them to the air outlet of the indoor unit. (2 positions) Fig.1, Fig.2.
2.  Install the suction chamber on the indoor unit using hooks (4 positions). Fig.3, Fig.5.
3.  Fix the hooks at the four positions with reference to Fig.4.
4.  Install the indoor unit and suction chamber while aligning their contours. Fig.4, Fig.6.