Indoor Unit Installation

Wall Mounting

3.

Installation.

• Install the indoor unit on the wall according to the installation drawings.

1) Hang the indoor unit on the hooks of 

 mounting plate. (2 places)

2) Fix the three holes in the lower portion of the indoor unit with M4 × 25L screws.

• Work should be performed to match the direction of the piping, as the extension auxiliary pipe (

, supplied) and installa-

tion methods vary depending on the direction the piping is brought out.

1) Select the extension auxiliary pipe in accordance with the 

direction of the piping. (This should be done without the 
included piping for wall-mounted right-back piping and 
ceiling-mounted upper right-side piping.)

2) Attach the heat insulation tube 

 to the extension auxil-

iary pipe. (Make sure there are no gaps.)

3) Attach the extension auxiliary pipe to the product.

A

Mounting plate

A

Electric component cover
(2 claws)

Front grille

M4 

×

 25L

J Side cover

(6 claws)

J Side cover

less than 1 

A Mounting plate

Indoor unit 
hook portion

Condition for installation

M

Bottom-
right piping

Right side 
piping

2)

3)

N

01_EN_3P171284-2D.fm  Page 7  Monday, August 23, 2010  2:33 PM

Summary of Contents for Inverter FLXS25BVMB

Page 1: ...FLXS60BAVMB FLKS60BAVMB English Deutsch Fran ais Nederlands Espa ol Italiano Portugues Installation manual R410A Split series Installationsanleitung Split Baureihe R410A Manuel d installation S rie sp...

Page 2: ...r Quality Control Department 1st of Nov 2008 DAIKIN TCF 015 K1 07 2007 FLKS25BVMB FLKS35BVMB FLXS25BVMB FLXS35BVMB FLK25BVMB FLK35BVMB FLX25BVMB FLX35BVMB FLKS50BVMB FLKS60BVMB FLXS50BVMB FLXS60BVMB F...

Page 3: ...clamping may cause termi nal overheating or fire After connecting interconnecting and supply wiring be sure to shape the cables so that they do not put undue force on the electrical covers or panels I...

Page 4: ...c ignition type fluorescent lamps inverter or rapid start type as they may shorten the remote control range 8 the unit is at least 1 metre away from any television or radio set unit may cause interfer...

Page 5: ...or different addresses 2 Remove the electric component cover Refer to the BEFORE INSTALLING THE INDOOR UNIT 3 Cut the jumper JA on PCB Wireless remote controller 4 Cut the jumper J4 2 In case of ceili...

Page 6: ...mote controller holder Wireless remote controller Space for installation work Min 200mm Space for installation work Min 200mm Mounting plate A Screws Field supply M4 25L 50mm or more from walls There...

Page 7: ...side pipinghole 65mm Rear side drainhose hole 40mm 55 50 35 40 45 22 40 Right side piping hole 65mm Drain hose 1 050 980 230 138 490 55 40 Wall Top side piping hole 65mm 35 Right side piping hole 80m...

Page 8: ...hose to the local drain pipe Position the interconnecting wire in the same direction as the piping Feed through portion of drain hose For determining the position of the drain hose perform the followi...

Page 9: ...ought out 1 Select the extension auxiliary pipe in accordance with the direction of the piping This should be done without the included piping for wall mounted right back piping and ceiling mounted up...

Page 10: ...service lid fits securely then close service lid Warning 1 Do not use tapped wires stranded wires extension cords or starburst connections as they may cause overheating electrical shock or fire 2 Do...

Page 11: ...in hose requires extension obtain an extension hose commercially available After connecting the local drain hose tape the slits of the heat insulation tube P Q Binding band Heat insulation tube Q P P...

Page 12: ...the flare nuts and gas leakage Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand Then tighten them fully with the torque wrenches 2 1 Caution on Piping Handling 1 Prote...

Page 13: ...the gas and liquid piping and to provide insulation dimen sions as below 3 Use separate thermal insulation pipes for gas and liquid refrigerant pipes Gas side Liquid side Gas pipe thermal insulation L...

Page 14: ...oner requires a small amount of power in its standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If th...

Page 15: ...1010 HT 3P171284 2D M02B074J Two dimensional bar code is a code for manufacturing 00_CV_3P171284 2D fm Page 2 Monday August 23 2010 2 27 PM...

Reviews: