background image

11

English

Refrigerant Piping Work

2-2. Selection of Copper and Heat Insulation materials

• When using commercial copper pipes and fittings, observe the following:
1) Insulation material:  Polyethylene foam

Heat transfer rate:  0.041 to 0.052W/mK (0.035 to 0.045kcal/mh

°

C)

Refrigerant gas pipe’s surface temperature reaches 110

°

C max.

Choose heat insulation materials that will withstand this temperature.

2) Be sure to insulate both the gas and liquid piping and to provide insulation dimen-

sions as below.

3) Use separate thermal insulation pipes for gas and liquid refrigerant pipes.

Gas side

Liquid side

Gas pipe thermal insulation

Liquid pipe 

thermal 

insulation

20/25/35 class

50/60 class

20/25/35 class

50/60 class

O.D. 9.5mm

O.D. 12.7mm

O.D. 6.4mm

I.D. 12-15mm

I.D. 14-16mm

I.D. 8-10mm

Minimum bend radius

Thickness 10mm Min.

30mm or more 40mm or more 30mm or more

Thickness 0.8mm (C1220T-O)

Gas pipe

Liquid pipe

Gas pipe 
insulation

Liquid pipe 
insulation

Finishing tape

Drain hose

Inter-unit wiring

01_EN_3P171284-2D.fm  Page 11  Monday, August 23, 2010  2:33 PM

Summary of Contents for Inverter FLXS25BVMB

Page 1: ...FLXS60BAVMB FLKS60BAVMB English Deutsch Fran ais Nederlands Espa ol Italiano Portugues Installation manual R410A Split series Installationsanleitung Split Baureihe R410A Manuel d installation S rie sp...

Page 2: ...r Quality Control Department 1st of Nov 2008 DAIKIN TCF 015 K1 07 2007 FLKS25BVMB FLKS35BVMB FLXS25BVMB FLXS35BVMB FLK25BVMB FLK35BVMB FLX25BVMB FLX35BVMB FLKS50BVMB FLKS60BVMB FLXS50BVMB FLXS60BVMB F...

Page 3: ...clamping may cause termi nal overheating or fire After connecting interconnecting and supply wiring be sure to shape the cables so that they do not put undue force on the electrical covers or panels I...

Page 4: ...c ignition type fluorescent lamps inverter or rapid start type as they may shorten the remote control range 8 the unit is at least 1 metre away from any television or radio set unit may cause interfer...

Page 5: ...or different addresses 2 Remove the electric component cover Refer to the BEFORE INSTALLING THE INDOOR UNIT 3 Cut the jumper JA on PCB Wireless remote controller 4 Cut the jumper J4 2 In case of ceili...

Page 6: ...mote controller holder Wireless remote controller Space for installation work Min 200mm Space for installation work Min 200mm Mounting plate A Screws Field supply M4 25L 50mm or more from walls There...

Page 7: ...side pipinghole 65mm Rear side drainhose hole 40mm 55 50 35 40 45 22 40 Right side piping hole 65mm Drain hose 1 050 980 230 138 490 55 40 Wall Top side piping hole 65mm 35 Right side piping hole 80m...

Page 8: ...hose to the local drain pipe Position the interconnecting wire in the same direction as the piping Feed through portion of drain hose For determining the position of the drain hose perform the followi...

Page 9: ...ought out 1 Select the extension auxiliary pipe in accordance with the direction of the piping This should be done without the included piping for wall mounted right back piping and ceiling mounted up...

Page 10: ...service lid fits securely then close service lid Warning 1 Do not use tapped wires stranded wires extension cords or starburst connections as they may cause overheating electrical shock or fire 2 Do...

Page 11: ...in hose requires extension obtain an extension hose commercially available After connecting the local drain hose tape the slits of the heat insulation tube P Q Binding band Heat insulation tube Q P P...

Page 12: ...the flare nuts and gas leakage Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand Then tighten them fully with the torque wrenches 2 1 Caution on Piping Handling 1 Prote...

Page 13: ...the gas and liquid piping and to provide insulation dimen sions as below 3 Use separate thermal insulation pipes for gas and liquid refrigerant pipes Gas side Liquid side Gas pipe thermal insulation L...

Page 14: ...oner requires a small amount of power in its standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If th...

Page 15: ...1010 HT 3P171284 2D M02B074J Two dimensional bar code is a code for manufacturing 00_CV_3P171284 2D fm Page 2 Monday August 23 2010 2 27 PM...

Reviews: