SiBE05-513A
Troubleshooting
Service Diagnosis
83
4.3
Freeze-up Protection Control
or
High Pressure Control
Remote
Controller
Display
A5
Method of
Malfunction
Detection
High pressure control (heat pump model only)
During heating operations, the temperature detected by the indoor heat exchanger
thermistor is used for the high pressure control (stop, outdoor fan stop, etc.)
Freeze-up protection control (operation halt) is activated during cooling operation according
to the temperature detected by the indoor unit heat exchanger thermistor.
Malfunction
Decision
Conditions
High pressure control
During heating operations, the temperature detected by the indoor heat exchanger
thermistor is above 65°C
Freeze-up protection
When the indoor unit heat exchanger temperature is below 0°C during cooling operation.
Supposed
Causes
Operation halt due to clogged air filter of the indoor unit.
Operation halt due to dust accumulation on the indoor unit heat exchanger.
Operation halt due to short-circuit.
Detection error due to faulty indoor unit heat exchanger thermistor.
Detection error due to faulty indoor unit PCB.
Summary of Contents for Inverter FLKS25BVMB
Page 10: ...SiBE05 513A List of Functions 1 Part 1 List of Functions 1 List of Functions 2 ...
Page 13: ...List of Functions SiBE05 513A 4 List of Functions ...
Page 19: ...Specifications SiBE05 513A 10 Specifications ...
Page 55: ...Control Specification SiBE05 513A 46 Function and Control ...
Page 83: ...Instruction SiBE05 513A 74 System Configuration ...
Page 129: ...Check SiBE05 513A 120 Service Diagnosis ...
Page 167: ...Outdoor Unit SiBE05 513A 158 Removal Procedure ...
Page 171: ...Others SiBE05 513A 162 Others ...
Page 177: ...Wiring Diagrams SiBE05 513A 168 Appendix ...
Page 181: ...SiBE05 513A iv Index ...