Function of Thermistor
SiBE05-513A
30
Function and Control
2.2
Cooling Only Model
A
Outdoor Heat
Exchanger
Thermistor
(DCB)
1. The outdoor heat exchanger thermistor is used for controlling target discharge temperature.
The system sets a target discharge temperature according to the outdoor and indoor heat
exchanger temperature, and controls the electronic expansion valve opening so that the
target discharge temperature can be obtained.
2. The outdoor heat exchanger thermistor is used for detecting disconnection of the discharge
thermistor when cooling.
When the discharge pipe temperature becomes lower than the outdoor heat exchanger
temperature, the discharge pipe thermistor is judged as disconnected.
3. The outdoor heat exchanger thermistor is used for high pressure protection during cooling
operation.
B
Discharge
Pipe Thermistor
(DOT)
1. The discharge pipe thermistor is used for controlling temperature of the discharge pipe.
If the temperature of discharge pipe (used in place of the inner temperature of the
compressor) rises abnormally, the operating frequency drops or the operation halts.
2. The discharge pipe thermistor is used for detecting disconnection of the discharge
thermistor.
C
Indoor Heat
Exchanger
Thermistor
(DCN)
1. The indoor heat exchanger thermistor is used for controlling target discharge temperature.
The system sets a target discharge temperature according to the outdoor and indoor heat
exchanger temperature, and controls the electronic expansion valve opening so that the
target discharge temperature can be obtained.
2. The indoor heat exchanger thermistor is used for preventing freezing.
During the cooling operation, if the temperature drops abnormally, the operating frequency
becomes lower, then the operation halts.
3. The indoor heat exchanger thermistor is used for anti-icing control.
During the cooling operation, if the heat exchanger temperature in the room where operation
is halted becomes -1°C, it is assumed as icing.
A
C
B
Compressor
(R2828)
Summary of Contents for Inverter FLKS25BVMB
Page 10: ...SiBE05 513A List of Functions 1 Part 1 List of Functions 1 List of Functions 2 ...
Page 13: ...List of Functions SiBE05 513A 4 List of Functions ...
Page 19: ...Specifications SiBE05 513A 10 Specifications ...
Page 55: ...Control Specification SiBE05 513A 46 Function and Control ...
Page 83: ...Instruction SiBE05 513A 74 System Configuration ...
Page 129: ...Check SiBE05 513A 120 Service Diagnosis ...
Page 167: ...Outdoor Unit SiBE05 513A 158 Removal Procedure ...
Page 171: ...Others SiBE05 513A 162 Others ...
Page 177: ...Wiring Diagrams SiBE05 513A 168 Appendix ...
Page 181: ...SiBE05 513A iv Index ...