SiBE05-513A
Problem Symptoms and Measures
Service Diagnosis
77
2.
Problem Symptoms and Measures
Symptom
Check Item
Details of Measure
Reference
Page
None of the Units
Operates.
Check the power supply.
Check to make sure that the rated voltage is
supplied.
—
Check the type of the indoor units.
Check to make sure that the indoor unit type is
compatible with the outdoor unit.
—
Check the outdoor air temperature.
Heating operation cannot be used when the
outdoor air temperature is 21°C or higher (only
for heat pump model), and cooling operation
cannot be used when the outdoor air
temperature is below
–
10°C.
—
Diagnosis with remote controller
indication
—
Check the remote controller
addresses.
Check to make sure that address settings for
the remote controller and indoor unit are
correct.
—
Operation Sometimes
Stops.
Check the power supply.
A power failure of 2 to 10 cycles can stop air
conditioner operation. (Operation lamp OFF)
—
Check the outdoor air temperature.
Heating operation cannot be used when the
outdoor air temperature is 21°C or higher (only
for heat pump model), and cooling operation
cannot be used when the outdoor air
temperature is below
–
10°C.
—
Diagnosis with remote controller
indication
—
Equipment operates but
does not cool, or does not
heat (only for heat pump
model).
Check for wiring and piping errors in
the indoor and outdoor units
connection wires and pipes.
Conduct the wiring/piping error check described
on the product diagnosis nameplate.
—
Check for thermistor detection errors. Check to make sure that the main unit’s
thermistor has not dismounted from the pipe
holder.
—
Check for faulty operation of the
electronic expansion valve.
Set the units to cooling operation, and compare
the temperatures of the liquid side connection
pipes of the connection section among rooms to
check the opening and closing operation of the
electronic expansion valves of the individual
units.
—
Diagnosis with remote controller
indication
—
Diagnosis by service port pressure
and operating current
Check for insufficient gas.
Large Operating Noise and
Vibrations
Check the output voltage of the
power transistor.
—
Check the power transistor.
—
—
Check the installation condition.
Check to make sure that the required spaces
for installation (specified in the Technical
Guide, etc.) are provided.
—
Summary of Contents for Inverter FLKS25BVMB
Page 10: ...SiBE05 513A List of Functions 1 Part 1 List of Functions 1 List of Functions 2 ...
Page 13: ...List of Functions SiBE05 513A 4 List of Functions ...
Page 19: ...Specifications SiBE05 513A 10 Specifications ...
Page 55: ...Control Specification SiBE05 513A 46 Function and Control ...
Page 83: ...Instruction SiBE05 513A 74 System Configuration ...
Page 129: ...Check SiBE05 513A 120 Service Diagnosis ...
Page 167: ...Outdoor Unit SiBE05 513A 158 Removal Procedure ...
Page 171: ...Others SiBE05 513A 162 Others ...
Page 177: ...Wiring Diagrams SiBE05 513A 168 Appendix ...
Page 181: ...SiBE05 513A iv Index ...